Inspection Reports for Canterbury Inn Assisted Living Community

1324 3rd Ave, Longview, WA 98632, United States, WA, 98632

Back to Facility Profile

Deficiencies per Year

16 12 8 4 0
2023
2024
Severe High Moderate Low Unclassified
Inspection Report Follow-Up Deficiencies: 0 Nov 13, 2024
Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility to verify correction of previous deficiencies.
Findings
The follow-up inspection found no deficiencies and confirmed that the facility meets Assisted Living Facility licensing requirements. Previously cited deficiencies were corrected.
Report Facts
Residents sampled: 12 Total residents: 97 Deficiencies cited: 14 Staff continuing education hours missing: 2 Residents missing negotiated service agreements: 6 Residents missing Medicaid policy signature on or before admission: 3
Employees Mentioned
NameTitleContext
Kyle GehlenALF Licensor - LTCDepartment staff who did the on-site verification
Jennifer SiharathALF LicensorDepartment staff who did the on-site verification
Michael BurdickField ManagerSigned enforcement letter and correspondence
Staff AExecutive DirectorAcknowledged findings and deficiencies during exit interviews
Staff CDirector of NursingConfirmed resident use of transfer pole
Staff GCertified Nursing Assistant/Medication TechnicianHad incomplete continuing education hours
Staff HLicensed Practical Nurse/Assistant Director of Resident ServicesHad incomplete continuing education hours
Inspection Report Re-Inspection Deficiencies: 15 Jul 30, 2024
Visit Reason
The Office of the State Fire Marshal conducted a re-inspection at Canterbury Retirement Inn to verify correction of previously identified fire and safety violations.
Findings
The facility was found to have multiple unresolved fire and safety violations including missing electrical covers, blocked electrical panels, noncompliant fire doors, missing fire drill records for 2023 and 2024, and failure to secure oxygen tanks. Several reports required for compliance were not provided.
Deficiencies (15)
Description
Electrical cover missing in maintenance office and room 313
Annual fire door inspection report not provided; multiple fire doors out of compliance (attic access door not self-closing, cross corridor door by room 601 side gap, door 605 bottom gap)
Cigarette found in garbage can; no ashtray present in smoking area
Electrical cover missing in boiler room, laundry room, maintenance office, and room 313; broken electrical flex conduit in culinary manager area
Electrical panel blocked by item near room 122
Extension cord found as permanent wiring in laundry room
Kitchen appliance not restrained from movement
Boiler room has holes in wall; hole in stairwell by room 608; hole in wall trash by room 508
Fire damper fusible link painted in storage room by rooms 508 or 608
Multiple fire doors found wedged open during inspection (rooms 101, 103, 104, 105, 106, 118, 124)
Annual trip test and 3 year trip test for sprinkler system not documented; facility in process of replacing dry pendant fire sprinkler heads
Carbon monoxide detector in room 148 is in trouble
Annual emergency light testing not provided; exit sign by dining room failed to be illuminated
Oxygen tank in room 124 not secured; repair made during inspection
Fire drills missing for 2023 and 2024
Report Facts
Fire doors wedged open: 7 Fire drills missing years: 2
Employees Mentioned
NameTitleContext
Nicholas WoldenDeputy State Fire MarshalSigned inspection report
Inspection Report Life Safety Deficiencies: 7 Jun 12, 2023
Visit Reason
The Office of the State Fire Marshal conducted a fire safety inspection at Canterbury Retirement Inn on June 12, 2023.
Findings
The facility was found to have multiple fire safety violations including failure to maintain fire resistance rated construction, inadequate inspection and maintenance of fire protection systems, missing fire sprinkler components, lack of required fire drills, and failure to provide necessary inspection reports and testing.
Deficiencies (7)
Description
Facility failed to maintain fire resistance rated construction in boiler room around fire sprinkler piping
Facility failed to maintain/provide fire rated door/hatch in mechanical room by 608 and 142
Facility failed to provide quarterly fire sprinkler inspection reports and annual forward flow testing; fire sprinkler trim ring missing from fire sprinkler head by room 151
Facility failed to provide heat survey results and proper fusible link selection for kitchen hood suppression system
Facility failed to provide sensitivity testing of the fire alarm smoke detectors
Facility failed to provide 5 year hydro testing of fire department connection (FDC)
Facility failed to provide the third quarter swing shift and night shift fire drills
Report Facts
Inspection date: Jun 12, 2023 Next inspection scheduled: Jul 12, 2023
Employees Mentioned
NameTitleContext
Nicholas D. WoldenDeputy State Fire MarshalConducted the fire safety inspection
Raymond SabinoArea DirectorAuthorized Facility Representative signing the report
Report