Inspection Report
Life Safety
Deficiencies: 10
Aug 14, 2025
Visit Reason
The Office of the State Fire Marshal conducted a fire safety inspection at Chuckanut Ridge Assisted Living to assess compliance with fire protection and safety codes.
Findings
The inspection found multiple deficiencies including lack of documentation for semi-annual hood cleanings, annual kitchen suppression system servicing, quarterly sprinkler system inspections, monthly smoke and carbon monoxide alarm testing, and annual emergency generator servicing. Several fire safety equipment issues were corrected, but some violations remain, such as improper use of power strips and extension cords, and fire extinguishers mounted too high or lacking required maintenance.
Deficiencies (10)
| Description |
|---|
| Facility is unable to provide documentation for the 12 months of semi-annual hood cleanings. |
| Facility is unable to provide documentation for the annual kitchen suppression system servicing. |
| Facility is unable to provide documentation for the quarterly sprinkler system inspections. |
| Facility is unable to provide documentation for the monthly single station smoke alarm testing. |
| Facility is unable to provide documentation for the monthly carbon monoxide detector testing. |
| Facility is unable to provide documentation for the annual servicing of the emergency generator. |
| There is a power strip plugged into another power strip in the nurses station. |
| There was an extension cord utilized as permanent wiring near room 234. |
| The required monthly maintenance for the portable fire extinguisher in the elevator equipment room has not been completed. |
| Fire extinguisher in main laundry was mounted with the top of the extinguisher over five feet above the finished floor. |
Report Facts
Months of semi-annual hood cleanings documentation missing: 12
Frequency of fire-extinguishing system servicing: 6
Maximum number of relocatable power taps connected together: 5
Maximum height for fire extinguishers weighing 40 pounds or less: 5