Inspection Reports for Crista Shores

WA, 98383

Back to Facility Profile
Document Deficiencies: 0 Jul 11, 2024
Visit Reason
This document appears to be informational or directory-related, not an inspection or regulatory report.
Findings
No inspection findings or regulatory content present.
Document Deficiencies: 0 Dec 19, 2023
Visit Reason
This document serves as an informational resource for the Locator website and is not an inspection or regulatory report.
Findings
No inspection findings or regulatory content present in the document.
Inspection Report Life Safety Deficiencies: 13 Sep 29, 2022
Visit Reason
The Office of the State Fire Marshal conducted a fire safety inspection at the Courtyard at Christa Shores facility to assess compliance with fire protection and safety codes.
Findings
The facility was found to be noncompliant with multiple fire safety requirements, including failure to provide emergency plan binder, documentation of fire drills, kitchen hood cleaning, annual fire wall inspection, sprinkler system maintenance, certification of service personnel, servicing of kitchen suppression system, smoke detector inspections, nuisance logs, and generator maintenance documentation.
Deficiencies (13)
Description
Facility failed to provide emergency plan binder.
Facility failed to provide documentation showing fire drills are being conducted once per shift per quarter for the 2nd and 3rd quarter of 2022.
Facility failed to provide documentation showing first and second semi-annual kitchen hood cleaning.
Facility failed to provide documentation showing annual fire wall inspection.
Facility failed to maintain fire wall in housekeeping storage room on beach level by elevator, penetration found.
Facility failed to provide documentation showing annual backflow report for the automatic sprinkler system.
Facility failed to maintain sprinkler heads in mechanical room #1 at beach level (2 heads rusted), dairy cooler in kitchen (1 head rusted), and dish pit in kitchen area (3 heads rusted).
Facility failed to provide documentation showing technician for kitchen suppression system holds NAFED certification.
Facility failed to provide documentation showing first and second semi-annual servicing of kitchen suppression system.
Facility failed to provide documentation showing annual replacement of fusible links for kitchen suppression system.
Facility failed to provide documentation showing monthly inspection of single and/or multiple station smoke detectors.
Facility failed to provide documentation showing nuisance log for smoke detectors.
Facility failed to provide documentation for generator annual servicing report, log of weekly inspections, and monthly 30-minute full load test.
Report Facts
Inspection date: Sep 29, 2022 Next inspection scheduled: Oct 31, 2022 Sprinkler heads rusted: 6
Employees Mentioned
NameTitleContext
Raul MurciaDeputy State Fire MarshalConducted the fire safety inspection
Document Deficiencies: 0 R COURTYARD AT CRISTA SHORES 58380 63075 SI
Visit Reason
This document was prepared to provide information for the Locator website by Residential Care Services.
Findings
No inspection or regulatory findings are present in this document.