Inspection Report

Life Safety
Deficiencies: 3 Date: May 13, 2022

Visit Reason
The inspection was conducted as a fire life safety and sanitation licensure survey to assess compliance with relevant safety codes and regulations.

Findings
The facility was found to have deficiencies including lack of documentation for emergency generator inspections and testing, improper storage of medical oxygen in a non-ventilated area with combustible materials, and fire drills that did not demonstrate evacuation to the designated assembly point as required.

Deficiencies (3)
No documentation for inspections and testing of the emergency generator system including weekly inspections, monthly load testing, load bank tests, and annual fuel test.
Oxygen storage of 312 cubic feet in a linen/storage closet without ventilation and housing combustible materials.
Fire drills did not demonstrate evacuation to the designated point of assembly outlined in the emergency action plan.
Report Facts
Oxygen storage volume: 312 Generator capacity: 250