Inspection Report
Life Safety
Deficiencies: 12
Jan 23, 2025
Visit Reason
An unannounced Fire and Life Safety Code inspection was conducted at Normandy Park Assisted Living by a representative of the Washington State Patrol, State Fire Marshal's Office to determine compliance with all applicable codes.
Findings
Multiple fire and life safety code deficiencies were cited including open electrical junction boxes, extension cord misuse, inadequate cleaning documentation, failure to maintain fire-resistant construction, door operation issues, sprinkler system deficiencies, fire alarm system deficiencies, missing exit signs, and lack of documentation for emergency generator servicing.
Deficiencies (12)
| Description |
|---|
| Housekeeping closet by room 266b in memory care has exposed wiring on 2nd floor |
| Marketing office by room 203 has an extension cord in use on 2nd floor |
| Facility unable to provide documentation for semi-annual hood cleaning |
| Facility unable to provide record of annual fire wall inspection and/or repairs |
| Penetrations found in housekeeping closet by 102 and housekeeping door by laundry room - north side - 1st floor |
| Several fire doors did not close or latch properly when tested |
| Two loaded sprinkler heads in kitchen and walk-in cooler has tray rack obstructing sprinkler head |
| Facility unable to provide first quarter sprinkler report |
| Facility unable to provide service report for current kitchen suppression service |
| Fire alarm report showed 5 deficiencies; 3 corrected, 2 remain uncorrected with no correction report provided |
| Exit outside of memory care does not have an exit sign indicating which way is the exit |
| Facility unable to provide documentation showing annual servicing of emergency generator in last 12 months and fuel test for generator |
Report Facts
Deficiencies cited: 5
Next inspection scheduled: Scheduled on or after 2025-02-22
Employees Mentioned
| Name | Title | Context |
|---|---|---|
| Elliot Liebowitz | Maintenance Director | Named as Maintenance Director on report signature page |
| Cozetta Christian | Deputy State Fire Marshal | Conducted the inspection and signed the report |