Inspection Reports for Stanton Nursing and Rehabilitation Center

31 DERICKSON LANE, KY, 40380

Back to Facility Profile

Deficiencies (last 1 years)

Deficiencies (over 1 years) 6 deficiencies/year

Deficiencies are regulatory violations found during state inspections.

28% worse than Kentucky average
Kentucky average: 4.7 deficiencies/year

Deficiencies per year

4 3 2 1 0
2025
Inspection Report Life Safety Census: 76 Capacity: 81 Deficiencies: 4 Jun 11, 2025
Visit Reason
An Emergency Preparedness Recertification Survey and a Life Safety Recertification Survey were conducted to assess compliance with federal regulations and life safety code requirements for long term care facilities.
Findings
The facility was found not in compliance with several life safety standards including sprinkler system installation, smoke barrier doors, portable space heaters, and gas equipment for oxygen transilling cylinders. Deficiencies were identified related to sprinkler protection on a combustible wood porch, smoke barrier doors held open by magnetic devices, lack of documentation for a portable space heater, and a non-functioning mechanical fan in the oxygen transilling room.
Severity Breakdown
D: 4
Deficiencies (4)
DescriptionSeverity
Failed to install a complete automatic sprinkler system protecting a combustible wood covered porch area exceeding four feet from the exterior wall.D
Failed to maintain smoke barrier doors that were held open by magnetic devices not tied into the fire alarm system.D
Failed to provide documentation that a heat producing portable space heater did not exceed 212 degrees Fahrenheit.D
Failed to maintain a functioning mechanical fan in the liquid oxygen transilling storage room.D
Report Facts
Facility capacity: 81 Census: 76 Deficiencies cited: 4
Inspection Report Abbreviated Survey Deficiencies: 2 Apr 25, 2025
Visit Reason
An abbreviated survey investigation was initiated due to multiple complaints against Stanton Nursing and Rehabilitation Center, including KY36932, KY38939, KY40676, KY40958, KY41261, KY41794, KY41857, KY43606, KY43675, KY43777, KY45037, and KY45185.
Findings
The facility was found to have substantiated abuse involving one resident (Resident #1) where staff verbally and physically abused the resident by yelling and using a back scratcher to pull on the resident's lip. The facility also failed to timely report the abuse allegation to the State Survey Agency and Adult Protective Services as required. Other complaints were unsubstantiated with no deficient practice identified.
Complaint Details
The abbreviated survey was complaint-driven, investigating multiple complaints. Most complaints were unsubstantiated except for complaint KY45037, which was substantiated with a scope and severity of 'D'.
Severity Breakdown
SS=D: 2
Deficiencies (2)
DescriptionSeverity
Failure to protect resident from verbal and physical abuse by staff, substantiated for one resident.SS=D
Failure to immediately report alleged abuse to the Administrator and State Survey Agency within required timeframes.SS=D
Report Facts
Number of complaints investigated: 12 Number of residents sampled: 22 Compliance date: May 9, 2025
Employees Mentioned
NameTitleContext
CNA4Certified Nursing AssistantNamed in substantiated abuse finding for verbally and physically abusing Resident #1
CNA5Certified Nursing AssistantInvolved in abuse incident and investigation
LPN3Licensed Practical NurseWitnessed abuse incident and involved in investigation
UM1Unit ManagerReceived delayed report of abuse incident via text and communicated with former DON
Director of NursingDirector of NursingInterviewed Resident #1 post-incident and involved in corrective actions
Social Services DirectorSocial Services DirectorConducted resident interviews and skin assessments as part of corrective actions
Education DirectorEducation DirectorProvided staff education on abuse and neglect policy
Former AdministratorAdministratorDelayed receipt and reporting of abuse allegation
Former Director of NursingDirector of NursingCompleted facility investigation of abuse incident

Loading inspection reports...