Deficiencies per Year
8
6
4
2
0
Severe
High
Moderate
Low
Unclassified
Inspection Report
Life Safety
Deficiencies: 5
Nov 4, 2025
Visit Reason
The Office of the State Fire Marshal conducted an inspection at The Village Senior Living facility to evaluate compliance with fire protection and safety codes.
Findings
The inspection identified multiple violations including lack of proper ventilation for a single deck oven, missing fire sprinkler system documentation, and fire door deficiencies such as missing painted frame labels, failure of doors to self-close and latch, and excessive gaps in door frames.
Deficiencies (5)
| Description |
|---|
| Single deck oven in kitchen is not vented or contained under the facility's kitchen hood and lacks documentation of approval. |
| Unable to provide fire sprinkler system documentation including last annual forward flow test report and hydraulic calculation plate. |
| Fire door frames throughout the facility lack painted frame labels. |
| Fire doors failed to self-close and latch when tested in memory care dining room, memory care janitor room, and door to central stairwell 1st floor. |
| Excessive gaps between fire door frames and doors in memory care dining room, door to central stairwell 1st floor, and memory care janitor room. |
Report Facts
Next inspection scheduled on or after: Dec 4, 2025
Employees Mentioned
| Name | Title | Context |
|---|---|---|
| Dawn Beuamy | Executive Director | Signed as Owner or Authorized Representative |
| Arthur Jesse Ward | Deputy State Fire Marshal | Conducted the inspection |