Inspection Report

Complaint Investigation
Deficiencies: 2 Date: Aug 19, 2025

Visit Reason
The inspection was conducted in response to complaint #189610 regarding trouble with the fire alarm panel at White River Assisted Living.

Complaint Details
Complaint #189610 regarding fire alarm trouble status. The complaint was investigated by CDSFM Christian and DSFM Harlan. The facility started fire watch but did not follow the 15-minute interval policy. The fire alarm panel network was still in trouble status at the time of inspection.
Findings
The fire alarm panel went into trouble status on 08/01/25 and was corrected on 08/05/25, but the communication radio network was causing issues notifying the facility. The facility's fire watch policy was not followed correctly, with 30-minute intervals instead of the required 15-minute intervals. The fire alarm panel network remained in trouble status at the time of inspection.

Deficiencies (2)
Fire alarm panel network is still in trouble status and may not be communicating with fire alarm panel.
Fire watch was conducted in 30 minute intervals instead of the required 15 minute intervals per policy.
Report Facts
Complaint number: 189610 Fire watch interval: 30 Fire watch required interval: 15

Employees mentioned
NameTitleContext
Cozetta ChristianDeputy State Fire MarshalConducted complaint investigation
Alan HarlanDeputy State Fire MarshalConducted complaint investigation
Michael WeihenmannEDTFacility representative during inspection

Inspection Report

Re-Inspection
Deficiencies: 10 Date: Jul 7, 2025

Visit Reason
An unannounced Fire and Life Safety Code re-inspection was conducted at White River Assisted Living by a representative of the Washington State Patrol, State Fire Marshal's Office to determine compliance with all applicable codes.

Findings
Multiple deficiencies were cited during the re-inspection, including issues with fire door latches, missing documentation for sprinkler system maintenance, and other fire safety violations. Many deficiencies from previous inspections were noted as corrected.

Deficiencies (10)
Cross corridor FD 17 did not close / latch properly when tested.
The 5 year internal pipe has been rescheduled for the week of 7/7/2025.
The facility was unable to provide documentation for their current hood cleaning.
The facility was unable to provide record of their annual fire wall inspection and/or repairs for all fire-resistant-rated construction.
The facility's fire door inspection showed a deficiency; several doors did not close/latch when tested.
The facility was unable to provide documentation for first and second quarter sprinkler reports and 5 year internal pipe inspection.
The tags in the kitchen have been marked yellow - deficient.
The facility was unable to provide record of their annual inspection for their fire alarm system.
The facility was unable to provide documentation for their last smoke detector sensitivity test report and is not currently filling out a nuisance log.
The facility missed fire extinguisher monthly sign offs on the smoking area and activity room - office extinguishers.
Report Facts
Next inspection scheduled on or after: Aug 6, 2025 Next inspection scheduled on or after: Jun 20, 2025

Employees mentioned
NameTitleContext
Cozetta ChristianDeputy State Fire MarshalSigned as Deputy State Fire Marshal conducting the inspection
Robina GainesExecutive DirectorSigned as Owner or Authorized Representative

Inspection Report

Complaint Investigation
Deficiencies: 0 Date: Apr 24, 2025

Visit Reason
The inspection was conducted to investigate a complaint regarding the sprinkler system at White River Assisted Living.

Complaint Details
Complaint #176215 regarding the sprinkler system. The complaint was investigated and found no violations. No evacuation or injuries occurred. Fire Department responded due to fire alarm panel activation.
Findings
The elevator technician mistakenly cut the water line to the east portion of the community, causing water to be shut off for about 4 hours. No residents were harmed or evacuated, no fire occurred, and no IFC violations were observed.

Report Facts
Complaint number: 176215 Water shut off duration (hours): 4 Evacuated residents: 0 Injuries: 0 Fire watch interval (minutes): 30

Employees mentioned
NameTitleContext
Michael WeilemannExecutive Director in TrainingInterviewed during complaint investigation
Cozetta ChristianDeputy State Fire MarshalConducted the inspection and signed the report

Inspection Report

Re-Inspection
Deficiencies: 3 Date: Jul 9, 2024

Visit Reason
On 07/09/2024 an unannounced Fire and Life Safety Code re-inspection was conducted at Living Court Assisted Living Community by a representative of the Washington State Patrol, State Fire Marshal's Office to determine compliance with all applicable codes.

Findings
The inspection found deficiencies related to door operation, duct and air transfer openings, and testing and maintenance of sprinkler systems. Some violations were corrected, while others required further action or documentation.

Deficiencies (3)
Swinging fire doors shall close from the full-open position and latch automatically.
The facility's fire damper report shows that 1 damper failed. The facility was unable to provide documentation showing it was corrected. The facility has all of their dampers inspected due to not knowing which damper failed. Four of the dampers failed and the contractor is working on correcting them.
The facility was unable to provide documentation for quarterly sprinkler reports and forward flow test; the facility indicated they are wanting to switch contractors and have not scheduled these tests yet.
Report Facts
Number of dampers failed: 4 Date of inspection: Jul 9, 2024

Employees mentioned
NameTitleContext
Saul MoraMaintenance DirectorNamed as Owner or Authorized Facility Representative signing the inspection report
Cozetta ChristianDeputy State Fire MarshalConducted the inspection and signed the report