Failed to implement emergency power system inspection, testing, and maintenance requirements including missing documentation of a three-year 4 hour test.
Failed to ensure means of egress doors were readily accessible and properly locked with only one latching mechanism; exit door codes were posted incorrectly or missing.
Failed to install exit signage in the courtyard exit.
Failed to ensure hazardous area doors had properly working self-closing devices.
Failed to maintain fire alarm system with accurate time and date information.
Failed to ensure sprinkler heads in laundry area were free of foreign material and loading.
Failed to ensure spaces open to corridor had electrically supervised automatic smoke detection for pass-through windows greater than 20 square inches.
Failed to ensure corridor doors had means suitable for keeping door closed, no impediment to closing, latching, and smoke resistance; some doors were propped open.
Failed to ensure fuel fired water heaters and boilers had current inspection certificates.
Failed to secure electrical panels in corridors from unauthorized access.
Failed to provide ground fault circuit interrupter (GFCI) protection for one wet location receptacle in laundry area.
Failed to ensure egress corridors were not used as a portion of a return air system serving adjoining rooms.
Failed to ensure resident rooms did not use multi-plug adaptors as a substitute for fixed wiring.
Failed to properly secure oxygen cylinders from falling; one cylinder was freestanding without proper restraint.
Failed to post signs indicating when oxygen transfilling is occurring and prohibiting smoking in the immediate area.
Failed to provide a complete facility specific written fire safety plan addressing all required components including activation of interconnected fire alarm system upon battery powered isolated smoke alarm activation.
Failed to ensure combustible decorations on corridor doors did not exceed 30% coverage and were fire retardant or treated.
Failed to ensure annual inspection and testing of fire door assembly at Oxygen Transfilling room.