Inspection Reports for
Brookdale West Seattle
4611 35th Ave SW, Seattle, WA 98126, Seattle, WA
Back to Facility Profile7 Reports
Inspection Report — Mar 27, 2026
Life Safety
Date: Mar 27, 2026
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the Brookdale West Seattle residential care facility.
Findings
The inspection found multiple deficiencies related to fire safety systems, documentation, and maintenance. Many items lacked required documentation for inspections and testing, and some physical deficiencies were noted. All deficiencies remain uncorrected, resulting in a disapproved status.
Deficiencies (23)
IFC 603.2.2 (2021) Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
IFC 0603.5.1 (2021) Relocatable power taps shall be listed and labeled in accordance with UL 498A.
IFC 603.5.2 (2021) Relocatable power taps and current taps shall be directly connected to a permanently installed receptacle with specified exceptions.
IFC 603.6 (2021) Extension cords shall not substitute for permanent wiring and shall be used only with portable appliances, not affixed or exposed to damage.
IFC 606.3.3.1 (2021) Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at specified intervals by qualified individuals.
IFC 606.3.3.2 (2021) Components with grease accumulation shall be cleaned in accordance with ANSI/IKECA C10.
IFC 610.1.2 (2021) Clothes dryer exhaust systems shall be maintained per manufacturer instructions to prevent lint or debris accumulation.
IFC 701.3 (2021) Fire-resistance rating and smoke-resistant characteristics of smoke barriers shall be maintained.
IFC 701.6 (2021) Owner shall maintain an inventory and visually inspect fire-resistance-rated construction annually with records maintained.
IFC 703.1 (2021) Materials and firestop systems protecting penetrations shall be maintained with no visible openings.
IFC 705.2 (2021) Opening protectives in fire-resistance-rated assemblies and smoke barriers shall be inspected and maintained per NFPA 80 and NFPA 105.
IFC 705.2.4 (2021) Swinging fire doors shall close from full-open position and latch automatically.
IFC 706.1 (2018) Dampers protecting ducts and air transfer openings shall be inspected and maintained per NFPA 80 and NFPA 105.
IFC 903.5 (2021) Sprinkler systems shall be tested and maintained per Section 901.
IFC 904.13.5.2 (2021) Automatic fire-extinguishing systems shall be serviced at least every six months and after activation.
IFC 906.2 (2021) Portable fire extinguishers shall be selected, installed, and maintained per NFPA 10 with specified exceptions.
IFC 907.8 (2021) Fire alarm and detection systems shall be maintained with records of inspection, testing, and maintenance.
IFC 915.6 (2021 WAC) Carbon monoxide alarms and detectors shall be maintained and replaced if inoperable or end-of-life signals occur.
IFC 1008.1 (2021) Means of egress illumination shall be provided and comply with emergency power requirements.
IFC 1032.10.1 (2021) Emergency lighting equipment shall be tested monthly for at least 30 seconds with visual inspection for trouble indicators.
IFC 1031.10.2 (2021) Battery-powered emergency lighting equipment shall be tested annually for not less than 90 minutes.
IFC 1203.1.3 (2021) Emergency power and standby power systems shall be installed per applicable codes with a remote emergency stop switch outside the enclosure.
WAC 212-12-044 Fire drills shall be held at least twelve times annually with quarterly drills on each shift and detailed records maintained.
Inspection Report — Oct 14, 2025
Follow-Up
Date: Oct 14, 2025
Visit Reason
Follow-up inspection to verify correction of previously cited deficiencies in an Assisted Living Facility license.
Complaint Details
The inspection included a complaint investigation referenced by complaint number 186144. Multiple deficiencies were substantiated including failure to report a flood, incomplete tuberculosis screening of staff, and failure to maintain updated Personal Service Plans.
Findings
The follow-up inspection found no deficiencies and confirmed that previously cited deficiencies were corrected, meeting Assisted Living Facility licensing requirements.
Deficiencies (6)
WAC 388-78A-2620 Pets. The facility failed to ensure that 3 pets maintained certification from a veterinarian confirming they were free of diseases transmittable to humans, placing residents at risk of zoonotic disease exposure.
WAC 388-78A-2650 Reporting fires and incidents. The facility failed to notify the Department after a flood occurred in a resident's apartment, placing the resident at risk of living in an unsafe environment.
WAC 388-78A-2480 Tuberculosis Testing Required. The facility failed to ensure 2 of 5 sampled staff were screened for tuberculosis within three days of employment, risking resident exposure to communicable diseases.
WAC 388-78A-2140 Negotiated service agreement contents. The facility failed to update Personal Service Plans for 5 residents on anticoagulant medications to include safety instructions, increasing risk of health complications.
WAC 388-78A-2450 Staff. The facility failed to retain a prior background check for one staff member, preventing confirmation of compliance with background check renewal requirements.
WAC 388-78A-2700 Emergency and disaster preparedness. The facility failed to maintain the premises free of fire hazards by storing combustible materials in electrical and mechanical rooms, placing residents at risk of injury or death during a fire.
Report Facts
Residents present during inspection: 33
Sampled residents: 7
Sampled staff: 5
Pets without certification: 3
Residents on anticoagulant medications without updated PSP: 5
Inspection Report — Sep 25, 2025
Enforcement
Date: Sep 25, 2025
Visit Reason
This document is a follow-up visit resulting in the imposition of a civil fine due to an uncorrected deficiency related to pet certification at the assisted living facility.
Findings
The licensee failed to ensure that two pets maintained veterinarian certification to confirm they did not carry zoonotic diseases, placing 33 residents at risk. This deficiency was previously cited and remains uncorrected, resulting in a $200 civil fine.
Deficiencies (1)
WAC 388-78A-2620 (2)(b) Pets. The licensee failed to ensure that two pets maintained certification from a veterinarian to ensure they did not carry zoonotic diseases that could infect residents. This deficiency remains uncorrected.
Report Facts
Civil fine amount: 200
Residents at risk: 33
Inspection Report — Feb 12, 2025
Life Safety
Date: Feb 12, 2025
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the residential care facility.
Findings
All violations noted during previous related inspections have been corrected. The current inspection found some deficiencies, but the overall approval status is Approved.
Deficiencies (10)
IFC 603.5.2 (2021) - Relocatable power taps and current taps must be directly connected to a permanently installed receptacle. One power strip was plugged into another and one had an open plug with burnt marks.
IFC 703.1 (2021) - Materials and firestop systems must maintain fire-resistance and resist smoke passage. New IT cabling left holes open through fire walls and the 3rd floor utility room fire wall needs re-installation of the fire door frame.
IFC 705.2 (2021) - Opening protectives in fire-resistance-rated assemblies must be inspected and maintained. Door wedges were used to hold fire doors open in five locations.
IFC 705.2.4 (2021) - Swinging fire doors must close and latch automatically. Five doors on the 4th floor and main floor kitchen will not close and latch properly.
IFC 903.5.2 (2021) - Sprinkler systems must be tested and maintained. Annual forward flow test paperwork was not provided; some sprinkler heads were painted, rusted, or loaded improperly.
IFC 0915.1 (2021) WAC 51-54A - Carbon monoxide detectors must be installed. Missing CO detectors were found on the 3rd floor by room 303, lobby area, and library.
IFC 1032.10 (2021) - Emergency lighting must be maintained and tested. Emergency lights were found not working throughout the facility.
IFC 1203.4 (2021) - Emergency and standby power systems must be maintained and tested. Annual service report paperwork was not provided.
IFC 5303.5 (2021) - Compressed gas containers must be secured. Room 517 had a loose oxygen tank needing placement in a holder.
NFPA 80 - Fire door inspection and testing must be performed annually and documented. Facility must establish a schedule for inspection of fire doors and complete annual inspections.
Inspection Report — Mar 12, 2024
Follow-Up
Date: Mar 12, 2024
Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility to verify correction of previously cited deficiencies.
Findings
The follow-up inspection found no deficiencies and the facility meets the Assisted Living Facility licensing requirements. Previously cited deficiencies were corrected as listed.
Deficiencies (7)
WAC 388-78A-2130 Service agreement planning. The facility failed to update the Negotiated Service Agreement to reflect current resident needs for 2 of 8 sampled residents, placing them at risk for improper care and compromised health conditions.
WAC 388-78A-2140 Negotiated service agreement contents. The facility failed to develop and document appropriate behavioral interventions in the service agreements for 5 of 5 sampled residents, placing them at risk.
WAC 388-78A-2060 Preadmission assessment. The facility failed to conduct required preadmission assessments for new residents, risking inadequate care plans.
WAC 388-78A-2474 Training and home care aide certification requirements. The facility failed to ensure all staff received appropriate training and orientation, including required First Aid training, risking inadequate care.
WAC 388-78A-3100 Safe storage of supplies and equipment. The facility failed to secure hazardous supplies and equipment, including an unlocked housekeeping cart with broken lock and unlocked cabinet with hazardous chemicals, placing residents at risk of harm.
WAC 388-78A-2210 Medication services. The facility failed to implement systems to promote safe medication service for one sampled resident, resulting in a medication error and placing the resident at risk for deteriorated health.
WAC 388-78A-2730 Licensee's responsibilities. The facility failed to implement a Respiratory Protection Program including annual mask fit testing for staff, placing residents and staff at increased risk of exposure to COVID-19.
Report Facts
Sampled residents: 8
Current residents: 31
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Staff A | Health and Wellness Director | Interviewed and provided information related to resident care and medication errors |
| Staff F | Administrator | Observed during walkthrough related to hazardous supplies storage |
| Staff I | Maintenance Supervisor | Observed during walkthrough related to hazardous supplies storage |
| Staff J | Housekeeper | Provided information about housekeeping cart lock status |
| Staff G | Resident Care Coordinator | Interviewed regarding respiratory protection program and mask fit testing |
Inspection Report — Jan 9, 2024
Life Safety
Date: Jan 9, 2024
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the facility on 01/09/2024.
Findings
All violations noted during previous related inspections have been corrected as of this inspection. The facility was approved with no outstanding deficiencies.
Inspection Report — Jan 23, 2023
Life Safety
Date: Jan 23, 2023
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the facility.
Findings
Multiple fire safety violations were observed including combustible storage in exit stairwells, missing electrical panel breaker covers, lack of documentation for fire door testing and damper inspections, missing fire extinguisher maintenance, and inadequate emergency lighting and exit signage. The facility was disapproved due to these unresolved deficiencies.
Deficiencies (11)
IFC 315.3.1 2018 - Combustible materials were stored in the exit stair on the 6th floor stairwell A, obstructing means of egress.
IFC 604.1 2018 - Breakers were missing protective coverings in the electrical panel in the 6th floor utility room for breakers 5, 7, and 9.
IFC 705.2.6 2018 - Facility was unable to provide documentation for annual testing of rolling fire doors in Room #314 and Main lobby.
IFC 706.1 2018 - Facility was unable to provide documentation for the 4 year fire and smoke damper inspection.
IFC 904.12 2015, 2018 - Kitchen appliances were not aligned correctly with installed sprinkler nozzles.
IFC 906.2 2015, 2018 - Several fire extinguishers were missing monthly maintenance and the fire extinguisher in the P2 elevator room was not completed per NFPA 10.
IFC 907.8 2018 - Facility was unable to provide documentation for monthly single station smoke alarm testing.
IFC 1008.1 2015, 2018 - No emergency lighting was installed to illuminate the means of egress in the kitchen.
IFC 1008.3.1 2015, 2018 - Emergency egress lights failed to illuminate when tested at multiple locations including the 6th floor near elevator and various stairwells.
IFC 1013.5 2018 - Two exit signs on the 6th floor patio did not illuminate when the activation test button was pushed.
IFC 402.7 (implied by fire drills section) - Facility could not provide documentation for completion of twelve planned and unannounced fire drills in the previous 12 months; multiple shifts missing drills.
Report Facts
Missing breakers: 3
Fire drills missing: 9
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Jose Morales | Maintenance Supervisor | Named as Owner's Representative signing the report |
Viewing
Loading inspection reports...



