13 Reports
Inspection Report — Jun 10, 2026
Complaint Investigation
Date: Jun 10, 2026
Visit Reason
The inspection was conducted in response to a complaint (#224713) regarding a fire alarm and a water line break in the dining room hallway at Sunnyside Care Assisted Living.
Complaint Details
Complaint #224713 involved a fire alarm triggered by a sprinkler line leak caused by a vendor puncturing the line. The inspection confirmed the incident and found no violations.
Findings
The inspection found no violations. The sprinkler line leak was repaired, and the facility staff discussed the incident with the inspector. The facility went into fire watch during the event and the fire alarm was activated.
Inspection Report — May 12, 2026
Complaint Investigation
Date: May 12, 2026
Visit Reason
The inspection was conducted in response to complaint #223250 regarding the fire alarm system at Sunnyside Care Assisted Living.
Complaint Details
Complaint #223250 was regarding the fire alarm system being in trouble status due to water damage from flooding. The complaint was substantiated as violations were found but all were corrected by the inspection date.
Findings
The fire alarm system was found to be in trouble status due to water damage from a flooding incident. The facility failed to notify the licensing agency immediately when the system went out of service but corrected the issue with a fire watch and subsequent repairs. All violations were corrected by the time of inspection.
Deficiencies (2)
IFC 901.7 (2021) - The facility failed to notify the licensing agency and appropriate fire code officials that the fire alarm system was out of service on May 5, 2026, at approximately 1700 hours. A fire watch was issued on May 7, 2026, for the out of service fire alarm system.
IFC 907.8.1 (2021) - The facility failed to provide documentation of the fire alarm system repair conducted on May 7, 2026, for the smoke alarm in Room 151, which failed due to flooding on April 5, 2026.
Report Facts
Complaint number: 223250
Time of fire alarm trouble status start: 1700
Time of fire watch issuance: 1230
Duration of resident relocation: 2
Inspection Report — Mar 23, 2026
Complaint Investigation
Date: Mar 23, 2026
Visit Reason
The inspection was conducted in response to a complaint (#216894) regarding a broken water pipe at Sunnyside Care Assisted Living located at 907 Ida Belle Street, Sunnyside, Washington.
Complaint Details
Complaint #216894 alleged a broken water pipe. The investigation confirmed the leak was utility related with no fire or safety violations. No fire department response was required and no violations were found.
Findings
The inspection found that the water leak was utility related and not part of any fire or life safety systems. No fire or life safety systems were activated, no injuries or evacuations occurred, and no violations were observed. The issue was discussed with facility staff and no citations were issued.
Inspection Report — Mar 3, 2026
Life Safety
Date: Mar 3, 2026
Visit Reason
The Office of the State Fire Marshal conducted a fire safety inspection at the facility to assess compliance with fire safety codes and regulations.
Findings
The inspection identified multiple fire safety violations related to documentation, maintenance, and equipment. All violations cited in this report were corrected on site, resulting in an Approved status.
Deficiencies (6)
IFC 404.2 (2021) Fire safety, evacuation and lockdown plan contents shall be in accordance with Sections 404.2.1 through 404.2.3.2. Facility was unable to provide fire drill documentation for the 3rd and 4th quarter NOC shift, and 2nd quarter swing shift. The drill conducted on June 26, 2025 was simulated and must be completed with fire alarm activation during the hours of 6:00am to 9:00pm.
IFC 606.3.3 (2021) Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals as required. The facility was unable to provide documentation of both semi-annual commercial hood cleanings within the past twelve months; documentation was reviewed from a cleaning on March 3, 2025 but was missing the name of the service company.
IFC 705.2 (2021) Opening protectives in fire-resistance-rated assemblies shall be inspected and maintained in accordance with NFPA 80. The annual fire door inspection completed on April 10, 2025 is missing resident doors for inspection. All fire-resistant and smoke barrier doors are required to be inspected annually. An assessment shall be done with the fire and life safety plans to assure all fire and smoke rated door assemblies are being assessed annually.
IFC 903.5 (2021) Sprinkler systems shall be tested and maintained in accordance with Section 901. The facility was unable to provide documentation of the annual fire sprinkler system deficiencies noted on the report from May 13, 2025 were corrected; North building dry system #2/#4 paint on sprinkler heads, South Building wet systems #3/#1, quick response sprinkler heads on wet system are dated 2002 and require testing.
IFC 907.8 (2021) The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with Sections 907.8.1 through 907.8.5 and NFPA 72. Records of inspection, testing and maintenance shall be maintained. The facility was unable to provide documentation of the annual inspection, testing, and maintenance of the fire alarm system within the past twelve months.
IFC 1013.5 (2021) Electrically powered, self-luminous and photoluminescent exit signs shall be listed and labeled in accordance with UL 924 and shall be installed in accordance with the manufacturer's instructions and Section 1203. Exit signs shall be illuminated at all times. The emergency exit lighting near Room 220 is not illuminated.
Inspection Report — Mar 3, 2026
Follow-Up
Date: Mar 3, 2026
Visit Reason
The inspection was conducted by the Office of the State Fire Marshal as a follow-up to verify correction of deficiencies related to a fire alarm system outage complaint.
Complaint Details
The inspection was triggered by complaint #201394 regarding a fire alarm system outage occurring on November 7, 2025. The complaint investigation found that the fire alarm system activated, no evacuation or injuries occurred, but documentation of repairs and retesting was missing initially. The follow-up inspection confirmed correction.
Findings
The facility failed to provide documentation showing the deficiencies to the fire alarm system were repaired and retested after the system failure during the initial complaint inspection. This violation was corrected on site during the follow-up inspection, resulting in an Approved status.
Deficiencies (1)
IFC 0901.7.6 (2021) - The facility failed to provide documentation showing the deficiencies to the fire alarm system were repaired and retested after the system failure.
Inspection Report — Jan 21, 2026
Follow-Up
Date: Jan 21, 2026
Visit Reason
The visit was a follow-up inspection triggered by a complaint and related to the facility's failure of the Fire Marshal reinspection.
Complaint Details
The complaint investigation found that the facility failed the Fire Marshal reinspection and follow-up reinspection. Multiple fire safety violations were identified and citations were written. The facility acknowledged the uncorrected violations and stated they hired a maintenance assistant to help make corrections.
Findings
The facility failed the Fire Marshal reinspection and follow-up reinspection due to multiple fire safety deficiencies including lack of fire drill documentation, missing commercial hood cleaning documentation, incomplete fire door inspection reports, and missing documentation for fire sprinkler and alarm system maintenance. The facility acknowledged the violations and hired a maintenance assistant to address the issues.
Deficiencies (1)
WAC 388-78A-2040 Other requirements. The assisted living facility must have its building approved by the Washington state fire marshal to be licensed. The facility failed to maintain compliance with the Washington State Patrol Fire Protection Bureau during the Deputy State Fire Marshal reinspection, placing residents, staff, and visitors at risk of harm in the event of a fire.
Report Facts
Total residents: 68
Resident sample size: 9
Inspection Report — Jan 5, 2026
Life Safety
Date: Jan 5, 2026
Visit Reason
The Office of the State Fire Marshal conducted a fire safety inspection at the Sunnyside Care residential care facility on January 5, 2026.
Findings
The inspection identified multiple fire safety violations, including missing documentation for fire drills and inspections, unsecured electrical panels, missing outlet covers, blocked emergency exits, and unsecured oxygen cylinders. Several violations were corrected on site, but some remain open, resulting in a disapproved status.
Deficiencies (18)
IFC 3035.1 2021 - Clearance between ignition sources and combustible items must be maintained. Combustible items were located above the stove cooking operations in the kitchen. (Corrected)
IFC 404.2 2021 - Fire safety, evacuation, and lockdown plan contents must comply with Sections 404.2.1 through 404.2.3.2. Facility was unable to provide fire drill documentation for multiple shifts and a simulated drill must be completed with fire alarm activation during specified hours. Violation remains for night shifts.
IFC 603.1 2021 - Electrical equipment and wiring must be installed and maintained per code. Electrical panels in main building and cottages were unsecured or uncovered. (Corrected)
IFC 603.2 2021 - Electrical hazards must be abated. Missing outlet covers were found in multiple areas including front entrance, activities office, and cottages B storage room. (Corrected)
IFC 603.4 2021 - Working space and clearance around electrical equipment must meet NFPA 70 requirements. An electrical panel was blocked by a cart with dishes in the kitchen. (Corrected)
IFC 603.5 2021 - Use of relocatable power taps must comply with NFPA 70. Unlisted multi plug adapters were in use in several rooms. (Corrected)
IFC 603.5.2 2021 - Relocatable power taps must be connected to permanently installed receptacles except for limited exceptions. A refrigerator was plugged into two power strips connected to an extension cord in the admin office. (Corrected)
IFC 606.3.3 2021 - Hoods and grease-removal devices must be cleaned at required intervals. Facility lacked documentation for semi-annual hood cleanings within past twelve months. Violation remains.
IFC 701.6 2021 - Owner must maintain inventory and inspection records for fire-resistance-rated construction. Multiple penetrations were found in walls and ceilings in various rooms. (Corrected)
IFC 705.2 2021 - Fire-resistance-rated assemblies must be inspected and maintained. Annual fire door inspection report was missing resident doors for inspection and an assessment is required. Violation remains.
IFC 705.2.3 2021 - Hold-open devices and automatic door closers must be maintained. Several self-closing fire doors were obstructed or propped open in multiple rooms. (Corrected)
IFC 903.5 2021 - Sprinkler systems must be tested and maintained. Facility lacked documentation for annual sprinkler system testing; some deficiencies noted remain. Quarterly inspection documentation was missing but corrected. Several sprinkler heads were loaded with debris or covered with tape. (Corrected)
IFC 904.13.5.2 2021 - Automatic fire-extinguishing systems must be serviced and inspected. Facility failed to provide documentation of kitchen hood system's second semi-annual inspection within last twelve months. (Corrected)
IFC 906.1 2021 - Portable fire extinguishers must be installed where required. No fire extinguishers were installed in several cottages and one extinguisher was not mounted or painted. (Corrected)
IFC 907.8 2021 - Fire alarm and detection systems must be maintained and tested. Facility lacked documentation for annual and semi-annual fire alarm inspections; violations remain. Fire alarm pull station and annunciator were obstructed by chairs; smoke detector covered with tape. (Corrected)
IFC 1003.6 2021 - Means of egress must not be obstructed. Back emergency exit door was blocked by chairs. (Corrected)
IFC 1013.5 2021 - Internally illuminated exit signs must be installed and illuminated. Emergency exit lighting near room 220 was not illuminated. Violation remains.
IFC 5303.5.3 2021 - Compressed gas containers must be secured to prevent hazards. Multiple unsecured oxygen cylinders were found in various cottages and the resident care coordinator's office. (Corrected)
Inspection Report — Jan 5, 2026
Complaint Investigation
Date: Jan 5, 2026
Visit Reason
The inspection was conducted in response to complaint #201394 regarding a fire alarm system outage occurring on November 7, 2025, at Sunnyside Care.
Complaint Details
Complaint #201394 was investigated regarding a fire alarm system outage on November 7, 2025. The fire alarm activated, no evacuations or injuries occurred, but the facility did not provide required documentation of repairs and retesting. The violation remains open.
Findings
The fire alarm system did activate during the outage, no injuries or evacuations occurred, but the facility failed to provide documentation showing that deficiencies were repaired and the system was retested. The violation remains open and the facility was disapproved.
Deficiencies (1)
IFC 0901.7.6 (2021) - The facility failed to provide documentation showing the deficiencies to the fire alarm system were repaired and retested after the system failure.
Inspection Report — Dec 15, 2025
Follow-Up
Date: Dec 15, 2025
Visit Reason
The Department of Social and Health Services conducted a follow-up inspection of the Assisted Living Facility to verify correction of previously cited deficiencies.
Findings
The Department found no deficiencies during the follow-up inspection on 12/15/2025. Previously cited deficiencies related to background checks were corrected.
Deficiencies (7)
WAC 388-78A-2466 Background checks Washington state name and date of birth background check Valid for two years National fingerprint background check Valid indefinitely. The facility failed to ensure a valid Washington state name and date of birth background check was submitted every two years for 5 of 5 staff. This placed residents at risk of being cared for by disqualified staff.
WAC 388-78A-2450 Staff. The facility failed to provide staff orientation for 4 of 4 staff, placing residents at risk of receiving care from untrained staff.
WAC 388-78A-2466 Background checks Washington state name and date of birth background check Valid for two years National fingerprint background check Valid indefinitely. The facility failed to ensure a valid Washington state name and date of birth background check was submitted every two years for staff who had worked more than two years for 2 of 2 staff, placing residents at risk of being cared for by disqualified staff.
WAC 388-78A-2468 Background checks Employment Conditional hire Pending results of Washington state name and date of birth background check. The facility failed to complete a Washington state name and date of birth background check within one day of hire and did not complete references for 1 of 3 staff, placing residents at risk of being cared for by disqualified staff.
WAC 388-112A-0611 Continuing education training requirements. The facility failed to ensure staff met the 12-hour continuing education training requirement for 3 of 3 staff.
WAC 388-78A-3000 Ventilation. The facility failed to provide and maintain intact sixteen mesh screens on operable windows in 2 of 2 cottages, placing residents at risk of having pests and bugs entering their living space.
WAC 388-78A-3090 Maintenance and housekeeping. The facility failed to maintain and provide the facility structure and environment in a sanitary manner and in good repair for 2 of 2 areas impacting 5 of 10 residents, placing residents at risk for decreased quality of life.
Report Facts
Sampled residents: 0
Sampled residents: 10
Current residents: 58
Staff missing background checks: 5
Staff missing orientation: 4
Staff missing background checks over 2 years: 2
Staff missing background check within one day of hire: 1
Staff missing continuing education: 3
Cottages missing screens: 2
Resident apartments with carpet stains: 5
Inspection Report — Oct 28, 2025
Enforcement
Date: Oct 28, 2025
Visit Reason
The Department of Social and Health Services conducted a follow-up visit to Sunnyside Care to enforce compliance related to previously cited deficiencies, resulting in the imposition of a civil fine.
Findings
The facility was fined $800 for failing to ensure valid Washington state background checks were submitted every two years for five staff members. This deficiency was uncorrected from a prior citation dated August 14, 2025.
Deficiencies (1)
WAC 388-78A-2466 (1)(a)(b) Background checks—Washington state name and date of birth background check—Valid for two years—National fingerprint background check—Valid indefinitely. The licensee failed to ensure a valid Washington state name and date of birth background check was submitted every two years for five staff members.
Report Facts
Civil fine amount: 800
Number of staff with missing background checks: 5
Inspection Report — Sep 29, 2025
Complaint Investigation
Date: Sep 29, 2025
Visit Reason
The inspection was conducted in response to a complaint alleging that residents were being told they were not allowed to eat in the main dining room for meals.
Complaint Details
The complaint alleged that residents were told they could not eat in the dining room. The investigation confirmed that residents in cottages were restricted from dining in the main dining room and required to sign agreements to dine separately. Multiple residents and staff interviews supported these findings. The complaint was substantiated with citations issued.
Findings
The investigation found that residents living in cottages outside the main building were restricted from eating in the main dining room and were required to sign an agreement to dine in their cottages. The facility failed to provide a 30-day notice for this rule change. Observations showed empty tables in the dining room, contradicting the facility's claim of no space. Citations were written for these deficiencies.
Deficiencies (3)
WAC 388-78A-2660 (1) - The assisted living facility failed to comply with resident rights by not providing a 30-day notice of changes to facility rules and restricting residents from dining in the main dining room.
RCW 70.129.030 - The facility did not inform residents in writing about services, items, and activities as required before admission and upon changes, violating residents' rights.
RCW 70.129.140 - The facility failed to protect residents' quality of life rights by restricting dining choices and socialization opportunities without proper notice.
Report Facts
Total residents: 64
Resident sample size: 4
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Melissa Milanez | Community Complaint Investigator | Conducted the on-site verification and investigation |
Inspection Report — Sep 24, 2025
Complaint Investigation
Date: Sep 24, 2025
Visit Reason
The inspection was conducted as a complaint investigation regarding allegations that a resident was financially and personally exploited by another resident, and that the same resident had fall incidents requiring more supervision.
Complaint Details
The complaint investigation (Complaint #193329) addressed two allegations: financial and personal exploitation of a resident by another resident, and fall incidents requiring more supervision. The first allegation was substantiated with a citation issued due to failure in care planning. The second allegation was unsubstantiated as safety measures were in place and families were satisfied.
Findings
The investigation found that the facility failed to document interventions to protect the exploited resident, who had advanced dementia, resulting in a citation. Safety measures for fall risks were in place and families were satisfied, with no failed practice identified in that regard.
Deficiencies (1)
WAC 388-78A-2140 Negotiated service agreement contents. The assisted living facility failed to ensure the negotiated service agreement contained necessary content to meet the needs of one resident, resulting in financial exploitation and risk to the resident's quality of life.
Report Facts
Total residents: 64
Resident sample size: 3
Inspection Report — Sep 9, 2025
Follow-Up
Date: Sep 9, 2025
Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility on 09/09/2025 to verify correction of previously cited deficiencies related to service agreement planning.
Complaint Details
The complaint investigation concerned an identified resident who had a fall with injury. The investigation found that the resident was admitted without an initial resident service plan, resulting in staff being unaware of the resident's care needs and fall risk. The complaint number referenced is 183247.
Findings
The Department found no deficiencies during the follow-up inspection and confirmed that the previously cited deficiencies related to service agreement planning were corrected.
Deficiencies (1)
WAC 388-78A-2130 Service agreement planning. The assisted living facility must develop an initial resident service plan based on discussions with the resident and their representative, integrating assessment information and identifying immediate needs. The facility failed to ensure an initial service plan was developed for one resident, contributing to a fall with injury.
Report Facts
Total residents: 57
Resident sample size: 3
Closed records sample size: 1
Viewing
Loading inspection reports...



