Inspection Reports for
Advance Assisted Living

252 PAYTON PLACE, ADVANCE, MO, 63730-7251

Back to Facility Profile

5 Reports

2019–2025

Inspection Report — Aug 20, 2025

Routine
Date: Aug 20, 2025

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
One state deficiency was cited concerning resident fund bond requirements and an insufficient surety/bond amount.

Deficiencies (1)
19 CSR 30-88.020(14) Resident Fund Bond Requirements: The facility failed to maintain the required surety (bond) in an amount equal to at least one and one-half times the average monthly balance of residents' personal funds for the 12 months reviewed. Review showed the facility's approved bond equaled $35,000 while the calculated required bond amount was at least $36,000.
Report Facts
facility approved bond amount: 35000 average monthly balance for residents' personal funds: 23690.37 calculated required bond amount: 36000

Inspection Report — Jul 1, 2024

Routine
Date: Jul 1, 2024

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
1 state deficiency concerning oxygen storage: portable oxygen cylinders were not stored in accordance with NFPA 99, with an observed unsecured cylinder in a resident room affecting all residents.

Deficiencies (1)
19 CSR 30-86.022(17) Oxygen Storage Requirements: The facility failed to store portable oxygen cylinders in accordance with NFPA 99; an observed oxygen cylinder was standing upright and unsecured in a resident room, affecting all residents.
Report Facts
residents affected: 34

Inspection Report — Nov 2, 2023

Routine
Date: Nov 2, 2023

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Two state licensure deficiencies were cited related to fire alarm maintenance and improper oxygen cylinder storage.

Deficiencies (2)
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: The smoke detector in the main dining room was hanging from the ceiling by the fire alarm wiring and not mounted properly, compromising its ability to function. The facility failed to maintain the complete fire alarm system in accordance with NFPA 72, affecting 34 of 34 residents.
19 CSR 30-86.022(17) Oxygen Storage Requirements: An unsecured portable oxygen cylinder was observed standing upright in resident room 115 and was not stored in an approved rack or secured, indicating improper oxygen storage. The facility failed to store portable oxygen cylinders in accordance with NFPA 99, affecting 34 of 34 residents.
Report Facts
residents affected: 34

Inspection Report — Apr 20, 2022

Routine
Date: Apr 20, 2022

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Three state licensure deficiencies were cited related to exit sign illumination, sprinkler system inspection/recalibration, and use of non‑compliant wastebaskets.

Deficiencies (3)
19 CSR 30-86.022(8)(C) Exit Sign-Illumination: The facility failed to maintain the building's emergency exit signs in good repair; emergency exit lights in the employee break area and on the west side of the fire separation doors failed to function when the test button was depressed.
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: The facility failed to inspect and/or maintain the sprinkler system in accordance with NFPA 25; sprinkler gauges lacked current recalibration markings and records did not show the gauges were recalibrated within the required five-year period.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: The facility failed to ensure only metal, UL or FM fire-resistant rated wastebaskets were used for trash; unapproved plastic and metal mesh wastebaskets were observed in resident rooms and were removed during the inspection.
Report Facts
residents affected: 31 residents affected: 31 residents affected: 31

Inspection Report — May 7, 2019

Routine
Date: May 7, 2019

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Four Missouri state licensure deficiencies were cited related to fire drill/evacuation requirements, sprinkler system inspections/maintenance, use of nonapproved wastebaskets, and use of a portable heater.

Deficiencies (4)
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Based on record review and interview during the fire safety inspection process on May 7, 2019 the facility failed to conduct a minimum of twelve (12) fire drills per year with at least one drill every three (3) months on each shift. Record review and interview showed fewer drills on each shift and the owner was not aware the performed drills were not correct.
19 CSR 30-86.022(11)(F) Sprinkler Systems-Inspections, Cert.: Based on record review, observation and interview during the fire safety inspection process on May 7, 2019 the facility failed to inspect and maintain the sprinkler system in accordance with NFPA 25, 1998 edition. Observation showed no current date stamping, manufacture date or inspector markings on the sprinkler system pressure gauges and record review showed no documentation the gauges had been replaced or recalibrated as required within the last five years.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements Trash and Rubbish Disposal.: Based on observation and interview during the fire safety inspection process on May 7, 2019 the facility failed to ensure only metal or UL- or FM-fire-resistant rated wastebaskets were being used. Observation on May 7, 2019 showed an unapproved plastic wastebasket in use in resident room 411-A which was removed during the inspection.
19 CSR 30-86.032(10) Heaters-Approved Label, Venting, No Portable: Based on observation and interview during the fire safety inspection process the facility failed to ensure only approved heating sources were used. Observation on May 7, 2019 showed a portable fireplace-style heater being used as a television stand in resident room 402 and the owner said she would have it removed.
Report Facts
residents affected: 35