Inspection Reports for
Brookdale at Home® Wornall Place

MO, 64114

Back to Facility Profile

12 Reports

2018–2026

Inspection Report — Apr 8, 2026

Complaint Investigation
Date: Apr 8, 2026

Visit Reason
Missouri Department of Health and Senior Services State Form; complaint investigation cited (MO00260976).

Complaint Details
Complaint MO00260976; substantiation not stated.
Findings
Two Missouri state licensure deficiencies were cited. They concern failures in protective oversight including delayed call light response and lack of individualized fall planning, and failures in the medication system including missing narcotic medication, unsecured storage, and lack of monitoring for residents who self-administer medications.

Deficiencies (2)
19 CSR 30-86.047(35) Protective Oversight: Based on interview and record review, the facility failed to provide protective oversight for one sampled resident by not ensuring call lights were answered in a timely manner. The facility also did not complete an individualized fall care plan after the resident was assessed as at heightened risk for falls.
19 CSR 30-86.047(46) Safe & Effective Medication System: Based on interview and record review, the facility failed to ensure a system to monitor medications for one resident who self-administered medications and failed to secure narcotic medications. The investigation documented missing narcotic pills, medications not locked, and no method to track residents' self-administered medications daily.
Report Facts
residents sampled: 9

Inspection Report — Oct 15, 2024

Routine
Date: Oct 15, 2024

Visit Reason
Missouri Department of Health and Senior Services State Form (Missouri state licensure survey); the survey type is not stated.

Findings
12 state deficiencies were cited, primarily involving fire safety and emergency preparedness: fire extinguisher maintenance, fire drill and evacuation planning and execution, areas of refuge, fire alarm and sprinkler system testing/maintenance, emergency lighting, flame-resistant curtains, approved wastebaskets, oxygen storage, and boiler inspection documentation.

Deficiencies (12)
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: The facility failed to document monthly checks and annual maintenance of all fire extinguishers and an extinguisher in the 5th floor life enrichment area had not been inspected for an extended period.
19 CSR 30-86.022(5)(A) Fire Drill/Evacuation Plan, Consultation: The facility failed to provide documentation that a request for consultation and assistance was made annually from a local fire unit for review of the facility's fire and evacuation plan.
19 CSR 30-86.022(5)(B)(1 - 10) Fire Drill/Evacuation Plan Requirements: The facility failed to produce a written plan or demonstrate knowledge for proper use of and response to areas of refuge and other required plan elements.
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: The facility failed to produce documentation showing required distribution of fire drills (including required drills on each shift) as specified by the regulation.
19 CSR 30-86.022(7)(D)(1 - 8) Area of Refuge Requirements: The facility was housing residents on floors without accessible exits to grade and failed to have areas of refuge that met requirements, including lack of required signage and an area-of-refuge communication device that had been obstructed.
19 CSR 30-86.022(9)(E) Fire Alarm System Monthly Test: The facility failed to show proof the complete fire alarm system was activated at least once each month and documentation showed the system had been activated fewer than required monthly times in the past year.
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing: The facility failed to perform and document monthly pressure gauge readings and valve position checks for all sections of the sprinkler system and had no check sheets in the main riser room.
19 CSR 30-86.022(12)(C) Emergency Lighting - Battery Powered, 1.5 hrs: The facility failed to provide sufficient emergency lighting at attendants' stations and an emergency light in the 5th floor nurses station was inoperable.
19 CSR 30-86.022(13)(D) Curtains/Drapes, Flame Resistant: The facility failed to ensure curtains were certified or treated as flame-resistant; curtains observed in a resident room lacked identifying tags.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: The facility failed to ensure wastebaskets were the approved type for trash and numerous resident rooms were found with non-approved wastebaskets.
19 CSR 30-86.022(17) Oxygen Storage Requirements: The facility failed to provide oxygen storage in accordance with requirements and had resident rooms with multiple portable oxygen bottles stored at the bedside.
State Statute: Boiler inspection certifications (Section 11 CSR 40-2.022) and related documentation: The facility failed to maintain current approved boiler inspection certifications and record review showed two-year certificates for boilers were nearing expiration.
Report Facts
residents potentially affected: 41 fire drills documented on first shift: 7 fire drills documented on second shift: 2 fire drills documented on third shift: 3 portable oxygen bottles observed in a resident room: 3

Inspection Report — Jul 15, 2024

Complaint Investigation
Date: Jul 15, 2024

Visit Reason
Missouri state licensure survey (State Form); complaint investigation (MO00238919).

Complaint Details
MO00238919; determination of substantiation not stated.
Findings
One Missouri state licensure deficiency cited for failure to promptly investigate and report an allegation of resident-to-resident abuse.

Deficiencies (1)
19 CSR 30-88.010(25) Report A/N to DHSS/DMH When Needed: Based on interview and record review, the facility failed to immediately investigate and report to the state agency an allegation of possible resident-to-resident abuse for two sampled residents (Resident #1 and Resident #2).
Report Facts
residents affected: 2

Inspection Report — Oct 24, 2023

Complaint Investigation
Date: Oct 24, 2023

Visit Reason
Missouri state licensure survey (State Form); complaint investigation. Complaint number MO00224217 is cited in the file.

Complaint Details
MO00224217; substantiation not stated in the document.
Findings
1 state deficiency for protective oversight concerning failure to ensure resident call lights were answered in a timely manner, with multiple alerts unanswered or delayed and lack of adequate tracking and response processes.

Deficiencies (1)
19 CSR 30-86.047(35) Protective Oversight: Based on observation, interview and record review, the facility failed to ensure call lights were answered in a timely manner for sampled residents, with multiple call light alerts unanswered or delayed and inadequate tracking of alerts and responses.
Report Facts
residents sampled: 3

Inspection Report — Aug 8, 2023

Routine
Date: Aug 8, 2023

Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure survey); the survey type is not stated.

Findings
11 state deficiencies were cited covering fire extinguisher maintenance and monthly checks, fire drill documentation, monthly fire alarm testing, self/auto-closing door devices, smoke section partitions, sprinkler system monthly checks, approved wastebaskets, oxygen storage, building exits/maintenance, electrical wiring inspection, and extension cord use.

Deficiencies (11)
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: Based on observation and interview the facility failed to document monthly fire extinguisher checks and extinguishers were not being checked monthly.
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Based on record review and interview the facility failed to produce documentation of at least twelve fire drills within the last year and failed to show required drills on each shift every three months.
19 CSR 30-86.022(9)(E) Fire Alarm System Monthly Test: Based on record review and interview the facility failed to show proof the complete fire alarm system was activated at least once each month.
19 CSR 30-86.022(10)(G) Door Devices - Self/Auto closing: Based on observation and interview the facility failed to ensure doors providing separation between floors closed properly; door closers were not functioning and some doors would not latch.
19 CSR 30-86.022(10)(J) Smoke Section Partitions < than 20 beds: Based on observation and interview the facility failed to ensure smoke partition doors would properly close during fire alarm activation, including a fire door found sticking and not fully closing.
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: Based on observations and interview the facility failed to perform and/or document monthly sprinkler riser pressure gauge readings and valve position checks as required.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Based on observation and interview the facility had non-approved wastebaskets in numerous resident rooms instead of the required metal or UL/FM fire-resistant types.
19 CSR 30-86.022(17) Oxygen Storage Requirements: Based on observation and interview the facility failed to provide oxygen storage in accordance with NFPA 99; multiple oxygen cylinders and equipment were present in a resident room.
19 CSR 30-86.032(2) Substantially Constructed & Maintained: Based on observation and interview the facility failed to properly maintain an exit door, with panic hardware loose and about to fall off the exit door by Room 474.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on record review and interview the facility failed to show documentation that electrical wiring had been inspected within the last two years; the last documented inspection was 2018.
19 CSR 30-86.032(18) Extension Cords/Duplex Receptacles: Based on observation and interview the facility failed to prevent extension cords from being used with more than one electrical item; an observed utility-type extension cord had multiple items plugged into it.
Report Facts
required annual fire drills: 12 large oxygen bottles observed in resident room 444: 7 medium oxygen bottles observed in resident room 444: 6 oxygen bottles in use observed in resident room 444: 1

Inspection Report — May 9, 2023

Routine
Date: May 9, 2023

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Two state licensure deficiencies were cited related to staffing and fall response and to resident dignity/privacy.

Deficiencies (2)
19 CSR 30-86.045(4)(A) Staffing Ratio, Resident Care & Fire Safety: Based on observation, interview and record review, the facility failed to ensure that the appropriate type of staff was on duty to meet the care needs of one sampled resident who was assessed as a fall risk, had a fall with an injury and was not appropriately assessed before being moved.
19 CSR 30-88.010(29) Dignity/Privacy: Based on interview and record review, the facility failed to ensure one sampled resident was treated with consideration and respect when a Level One Medication Aide was rude and disrespectful and assisted the resident after a fall in a manner that caused pain.
Report Facts
residents affected: 1 residents sampled: 3

Inspection Report — Nov 8, 2022

Complaint Investigation
Date: Nov 8, 2022

Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure survey); file contains complaint investigation identifiers MO00209448 and MO 00208330.

Complaint Details
Complaint investigation identifiers found in the file: MO00209448 and MO 00208330; the document does not state whether the allegations were substantiated.
Findings
Two state licensure deficiencies were cited addressing lack of individualized service plan guidance for a resident with alcohol use/aggressive behaviors and failure to promptly report/investigate an allegation of employee-to-resident abuse; both deficiencies are classified Class II.

Deficiencies (2)
19 CSR 30-86.047(36) Proper Care Per Individual Service Plan: Based on interview and record review, the facility failed to ensure that one resident (Resident #1) out of five sampled residents had goals or trackable outcomes outlining guidance related to management of the resident's alcohol use and/or aggressive behaviors; staff interviews noted the resident frequently drank alcohol, was verbally aggressive when drinking, and staff had received no training or ISP direction on how to interact with the resident in those circumstances.
19 CSR 30-88.010(25) Report A/N to DHSS/DMH When Needed: Based on interview and record review, facility staff failed to immediately report and investigate an allegation of employee-to-resident abuse when one sampled resident (Resident #5) reported that a Level 1 Medication Aide (L1MA A) was rough with him/her and left bruises; the record and interviews documented prior reports not being forwarded to the Director and issues with the facility's reporting/investigation of the allegation.
Report Facts
residents sampled: 5

Inspection Report — Jul 13, 2022

Routine
Date: Jul 13, 2022

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
7 Missouri state deficiencies covering fire extinguishers, sprinkler system monthly checks, emergency lighting, non-approved wastebaskets, electrical wiring inspection, elevator certification, and boiler inspection/statute. The electrical wiring finding included past noncompliance (last documented inspection 2018).

Deficiencies (7)
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: Based on observation and an interview on 7/13/22 the facility failed to document and date all of the fire extinguishers being checked annually and monthly; an extinguisher in the 5th floor exercise room had not been inspected since 2020.
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: Based on observations, interview and record review on 7/13/22 the facility failed to perform and/or record monthly pressure gauge readings and valve position checks for the sprinkler system at the risers and stairwell sub risers.
19 CSR 30-86.022(12)(C) Emergency Lighting -Battery Powered, 1.5 hrs: Based on observations and interview on 7/13/22 the facility failed to maintain emergency lights in good repair; emergency lights in the 4th floor dining area had weak batteries and/or were not lighting.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Based on observations and an interview on 7/13/22 the facility failed to ensure all wastebaskets were the approved metal or UL/FM-fire-resistant types; non-approved wastebaskets were observed in multiple resident rooms.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on record review and an interview on 7/13/22 the facility failed to show documentation that electrical wiring had been inspected within the last two years by a qualified electrician; record review showed the last inspection was 2018.
19 CSR 30-86.032(19) Elevator Requirements: Based on observation, record review, and interview on 7/13/22 the facility failed to have current approved elevator inspection certifications under state statute; one record located was expired (dated 3/15/03) and no current state inspection or certificate records were found.
State Statute: Based on observation, record review, and interview on 7/13/22 the facility failed to have current approved boiler inspection certifications under 11CSR40-2.022; no boiler certificates were posted for any of the five boilers.
Report Facts
residents potentially affected: 46 boilers without certificates observed: 5

Inspection Report — Mar 29, 2022

Routine
Date: Mar 29, 2022

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
One state licensure deficiency was cited concerning protective oversight and failure to ensure accurate side rail assessments and staff training on entrapment risks when side rails were used with a low-air-loss mattress.

Deficiencies (1)
19 CSR 30-86.047(35) Protective Oversight: Based on observation, interview and record review, the facility failed to ensure that side rail assessments were accurate and updated for one sampled resident and that staff were trained on the increased risk of entrapment when using side rails with a low air loss mattress.
Report Facts
residents affected: 1 residents sampled: 7

Inspection Report — Oct 5, 2021

Routine
Date: Oct 5, 2021

Visit Reason
Missouri state licensure survey (State Form) dated 2021-10-05 with an additional revisit State Form dated 2022-05-18; the survey types are not stated.

Findings
Seven state licensure deficiencies were cited covering fire hazards/oxygen storage, fire extinguisher maintenance, fire drill documentation, sprinkler system monthly checks, use of non-approved wastebaskets, building maintenance (fire door/panic bar), and lack of required electrical inspection; the electrical inspection deficiency was noted as uncorrected on a 2022 revisit.

Deficiencies (7)
19 CSR 30-86.022(2)(D) Inspection Rights, No Fire Hazard: Surveyor found multiple areas storing more than the allowed number of oxygen bottles and improper oxygen storage, with oxygen bottles observed in resident rooms and the storage cabinet being used for trash instead of oxygen bottle storage.
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: Surveyor found incomplete documentation of monthly pressure checks for fire extinguishers on the tags, with the last documented monthly checks recorded as July 2021.
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Surveyor found the facility failed to produce documentation of at least 12 fire drills conducted within the last year, with records showing July 29, 2021 as the last fire drill.
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: Surveyor found the facility failed to ensure monthly pressure gauge readings and valve position checks of the sprinkler system were performed as required, with the last recorded monthly check noted in November 2019 and no other documentation found.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Surveyor observed non-approved type wastebaskets in numerous resident rooms during walkthrough, rather than only metal or UL/FM-rated wastebaskets as required.
19 CSR 30-86.032(2) Substantially Constructed & Maintained: Surveyor found the facility failed to maintain a fire door in good repair, noting a panic bar pulled loose from one of the fire doors between the living and dining room on the fourth floor.
19 CSR 30-86.032(14) Lighting-Electric Only: Surveyor found the facility failed to provide documentation that electrical wiring/lighting had been inspected within the last two years by a qualified electrician; records showed the last electrical inspection on 8/15/18 and the deficiency was noted as uncorrected on a 2022 revisit.
Report Facts
oxygen bottles observed: 11 oxygen bottles observed: 7

Inspection Report — Jul 12, 2019

Routine
Date: Jul 12, 2019

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
3 state licensure deficiencies (Class II) for area of refuge doors not properly sealed or latching, exit doors locked or with missing delayed-egress signage preventing egress, and stairways obstructed by stair lifts reducing egress width.

Deficiencies (3)
19 CSR 30-86.022(7)(D)(1 - 8) Area of Refuge Requirements: The area of refuge doors did not provide protection from fire as several doors lacked a smoke seal, were rubbing preventing positive latching, or were hitting each other preventing full closure and latching.
19 CSR 30-86.022(7)(E) Locked Exit Doors: Exit doors were locked against egress or lacked required delayed-egress signage and required use of a code to unlock, preventing proper egress.
19 CSR 30-86.022(7)(G) Stairways/Corridors Free of Obstructions: Stairways were obstructed by two stair lifts that reduced the stairwell width to approximately 26 inches and would hinder evacuation of wheelchair-bound residents.
Report Facts
residents affected: 44

Inspection Report — Sep 13, 2018

Routine
Date: Sep 13, 2018

Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure survey); the survey type is not stated.

Findings
Four Missouri state licensure deficiencies were cited, involving area of refuge doors not closing properly, missing/untimely monthly sprinkler pressure and valve checks, improper oxygen storage in resident rooms, and an exit sign hanging by electrical wires indicating inadequate electrical maintenance.

Deficiencies (4)
19 CSR 30-86.022(7)(D)(1 - 8) Area of Refuge Requirements: The wooden doors to the area of refuge by room 568 would not close properly and were hitting each other; the facility failed to ensure a properly working entrance/exit door for the area of refuge.
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: Monthly pressure gauge readings and valve position checks for sprinkler risers were not consistently performed or recorded, with checklists showing months-old entries and no other monthly records found.
19 CSR 30-86.022(17) Oxygen Storage Requirements: Oxygen bottles were stored and supported improperly with multiple spare cylinders in resident rooms exceeding NFPA 99 allowances.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: An exit sign outside room 470 was hanging by its electrical wires and was not properly secured.
Report Facts
residents affected: 42

Viewing