Inspection Report — May 26, 2026

Life Safety
Date: May 26, 2026

Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the Brookdale Everett residential care facility.

Findings
All violations noted during previous related inspections have been corrected. The facility was approved following this inspection.

Inspection Report — Apr 28, 2025

Follow-Up
Date: Apr 28, 2025

Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility to verify correction of previously cited deficiencies.

Findings
The follow-up inspection found no deficiencies and confirmed that all previously cited deficiencies were corrected.

Deficiencies (2)
WAC 388-78A-3090 Maintenance and housekeeping. The facility failed to provide a safe, sanitary, and well-maintained environment in three locations including first floor, second floor, and outside grounds, placing all residents at risk. Observations included black marks on doors, dried liquids on walls, missing drawer knobs, cobwebs, broken ceiling tiles, dust buildup, disorganized storage, and unsafe outdoor conditions.
WAC 388-78A-2466 Background checks. The facility failed to ensure 2 of 6 staff had valid Washington State background checks renewed every two years, placing resident safety at risk. Staff E and F had background checks renewed late by 16 and 110 days respectively.
Report Facts
Residents in the facility: 61 Sampled residents: 9 Staff with invalid background checks: 2

Employees mentioned
NameTitleContext
Staff EMedication TechnicianNamed in background check deficiency for late renewal
Staff FMedication TechnicianNamed in background check deficiency for late renewal

Inspection Report — Apr 2, 2025

Complaint Investigation
Date: Apr 2, 2025

Visit Reason
The inspection on 04/02/2025 was conducted as a follow-up to verify that all violations noted during previous related inspections had been corrected.

Complaint Details
The complaint investigation related to a fire incident on 03/17/2025 at Brookdale Everett involved a resident who was injured. The cause of the fire was unknown and under investigation. No sprinkler activation occurred, no other residents were evacuated, and one resident was injured. The complaint number was 171133.
Findings
All violations from prior inspections have been corrected, resulting in an Approved status for this inspection.

Report Facts
Residents injured: 1 Staff injured: 0

Inspection Report — May 7, 2024

Life Safety
Date: May 7, 2024

Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the residential care facility Brookdale Everett.

Findings
The inspection identified multiple fire safety violations including combustible materials stored improperly, penetrations in fire-resistance-rated construction, and issues with smoke detector placement. Some violations were corrected on site, but the overall approval status was Disapproved.

Deficiencies (8)
IFC 315.2.3 (2021) - Combustible material shall not be stored in boiler rooms, mechanical rooms, electrical equipment rooms or in fire command centers. There was combustible storage within the mechanical furnace room near 227.
IFC 703.1 (2021) - Materials and firestop systems used to protect membrane and through penetrations in fire-resistance-rated construction shall be maintained with no openings visible through or into the cavity of the construction. There was a through penetration of the ceiling assembly next to the smoke detector near 110.
IFC 903.5 (2021) - Sprinkler systems shall be tested and maintained in accordance with Section 901. The walk-in type cooler and freezer has ordinary temperature heads installed.
IFC 907.8 (2021) - The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be maintained. The smoke detector head located near 217 has not been installed within 36 inches of an air supply diffuser or return air opening.
IFC 907.8 (2021) - The smoke detector head located near 119 has not been installed within 36 inches of an air supply diffuser or return air opening.
IFC 907.8 (2021) - The smoke detector head located near 121 has not been installed within 36 inches of an air supply diffuser or return air opening.
IFC 1008.3.3 (2021) - In the event of power supply failure, emergency electrical system shall automatically illuminate specified areas. Electrical equipment rooms, fire command centers, fire pump rooms, generator rooms, and public restrooms with area greater than 300 square feet shall be illuminated.
IFC 1203.4 (2021) - Emergency and standby power systems shall be maintained to supply service within the time specified. The system was maintained in accordance with NFPA 110 and NFPA 111.
Report Facts
Next inspection scheduled: Jun 6, 2024

Inspection Report — May 10, 2023

Complaint Investigation
Date: May 10, 2023

Visit Reason
The inspection was conducted as an unannounced complaint investigation based on allegations regarding food service quality, bathing frequency, housekeeping, and cleanliness issues at the Assisted Living Facility.

Complaint Details
The complaint investigation involved allegations about inadequate food service, missed meals, insufficient bathing, and poor housekeeping. The investigation substantiated the housekeeping and maintenance issues with citations issued, while food service and bathing concerns were found to be addressed satisfactorily.
Findings
The investigation found that the facility provided fresh fruits and vegetables, timely meal delivery, and increased bathing frequency for the named resident. However, housekeeping and maintenance deficiencies were identified, including cluttered rooms, unwashed dishes, full laundry bins, and safety hazards, resulting in a failed provider practice citation for noncompliance with WAC 388-78A-3090 Maintenance and housekeeping.

Deficiencies (1)
WAC 388-78A-3090 Maintenance and housekeeping. The assisted living facility failed to provide basic housekeeping and maintenance services to keep resident living quarters safe and sanitary, resulting in unsanitary safety risks and diminished quality of life for residents.
Report Facts
Total residents: 65 Resident sample size: 3 Closed records sample size: 1

Inspection Report — Apr 10, 2023

Life Safety
Date: Apr 10, 2023

Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the facility on 04/10/2023.

Findings
All violations noted during previous related inspections have been corrected and the facility was approved at this inspection.