Inspection Reports for
Foxberry Terrace Senior Living

MO, 64870

Back to Facility Profile

1 Report

2025

Inspection Report — Mar 25, 2025

Routine
Date: Mar 25, 2025

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Seven state deficiencies were cited, all related to fire/life safety and building maintenance: obstructing/sticking exits and doors, improperly illuminated/misleading exit signs and an inoperative exit/emergency light, a fire alarm panel in trouble, missing self-closing smoke partition door, non–flame-resistant curtains, and an electrical cord placed across a walkway.

Deficiencies (7)
19 CSR 30-86.022(7)(A) Exits-2 per Floor-Remote/Unobstructed: Based on observation and interview during the fire safety inspection, the facility failed to maintain unobstructed exits; the exit door on C Hall was sticking requiring excessive force to open and the E Hall exit did not close properly.
19 CSR 30-86.022(8)(B) Exit-Directional Indicators Exit Signs: Based on observation and interview during the fire safety inspection, an exit sign next to the laundry had illuminated directional arrows indicating turns that were not present.
19 CSR 30-86.022(8)(C) Exit Sign-Illumination Exit Signs: Based on observation and interview during the fire safety inspection, an exit sign/emergency light combination in B Hall failed to illuminate when tested and not all emergency lighting/exit signs were operational.
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain Complete Fire Alarm Systems: Based on record review and interview during the fire safety inspection, the facility failed to ensure the complete fire alarm system was tested and maintained; the fire alarm panel at the Arbors building was in trouble mode.
19 CSR 30-86.022(10)(A) Hazardous Area Requirements Protection from Hazards: Based on observation and interview during the fire safety inspection, the facility failed to install and maintain self-closing smoke partition doors; the laundry room smoke partition door was not self-closing.
19 CSR 30-86.022(13)(D) Curtains/Drapes, Flame Resistant Interior Finish and Furnishings: Based on observation and interview during the fire safety inspection, the facility failed to ensure curtains were certified or treated to be flame-resistant; a curtain in the administrative assistant's office had no documentation of treatment.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on observation, record review and interview during the fire safety inspection, the facility failed to ensure flexible power cords were properly maintained and not placed where subject to damage; a flexible power cord was taped to a rug across a walkway in room C-9.
Report Facts
residents affected: 43