Inspection Report — Apr 2, 2026
Annual Inspection
Date: Apr 2, 2026
Visit Reason
The Department completed a full inspection of the Assisted Living Facility on 04/02/2026 to determine compliance status.
Findings
The inspection found no deficiencies at the facility.
Inspection Report — Oct 8, 2025
Life Safety
Date: Oct 8, 2025
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire protection inspection at the facility.
Findings
The inspection found missing quarterly fire sprinkler inspection report for Q2 of 2024 and a dry sprinkler system past due for a 3-year full flow trip test requiring scheduling. Additionally, the facility was unable to produce a service report for the first semi-annual hood suppression system in 2024.
Deficiencies (2)
IFC 903.5 (2021) - Sprinkler systems shall be tested and maintained in accordance with Section 901. No quarterly fire sprinkler inspection report for Q2 of 2024 was found and the dry sprinkler system was past due for a 3-year full flow trip test requiring scheduling.
IFC 904.13.5.2 (2021) - Automatic fire-extinguishing systems shall be serviced at least every six months and after activation. The facility was unable to produce a service report for the first semi-annual hood suppression system in 2024.
Report Facts
Next inspection scheduled: Jan 31, 2026
Employees mentioned
| Name | Title | Context |
|---|---|---|
| William L. Husman | Maint Sup | Named as Owner or Authorized Representative signing the report |
Inspection Report — Aug 11, 2025
Life Safety
Date: Aug 11, 2025
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire protection inspection at the facility.
Findings
The inspection identified multiple fire safety violations, including missing floor tape clearance marks, overdue sprinkler system testing, and dim exit signs. Several violations were corrected on site, but some remain uncorrected, resulting in a disapproved status.
Deficiencies (9)
IFC 603.2 2021 - The facility did not place floor tape indicating the required 36-inch clearance mark in the kitchen mop closet as noted in the previous report.
IFC 603.4 2021 - Working space and clearance around electrical equipment were provided in accordance with code requirements.
IFC 606.3.3 2021 - Hoods, grease-removal devices, fans, ducts, and other appurtenances were cleaned at required intervals.
IFC 701.6 2021 - The owner maintained an inventory of all required fire-resistance-rated construction and inspected concealed spaces as required.
IFC 703.1 2021 - Materials and firestop systems used to protect membrane and through penetrations in fire-resistance-rated construction were maintained and inspected as required.
IFC 904.13.5.2 2021 - Unable to produce service report for first semi-annual hood suppression system in 2024.
IFC 903.5 2021 - No quarterly fire sprinkler inspection report for Q2 of 2024; dry sprinkler system past due for 3-year full flow trip test scheduling.
IFC 1013.5 2021 - Exit signs throughout the building's exit corridors and stairwells were significantly dim and failed to be fully illuminated on normal power; bulb replacements recommended every couple years. No records of light bulb replacement were available.
NFPA 72 10.6.5.2 - Circuit identification and accessibility requirements were met, including permanent identification of branch circuit disconnecting means and protection against physical damage.
Inspection Report — Dec 15, 2023
Annual Inspection
Date: Dec 15, 2023
Visit Reason
The Department of Social and Health Services conducted a full inspection of the Assisted Living Facility on 12/15/2023.
Findings
The inspection found no deficiencies in the facility.
Inspection Report — May 8, 2023
Life Safety
Date: May 8, 2023
Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire safety inspection at the facility on 05/08/2023.
Findings
All violations noted during previous related inspections have been corrected. The facility was approved following this inspection.