Inspection Reports for
La Bonne Maison Senior Living

226 Plaza Dr, Sikeston, MO 63801, United States, MO, 63801

Back to Facility Profile

6 Reports

2018–2024

Inspection Report — Jul 30, 2024

Routine
Date: Jul 30, 2024

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Two state deficiencies were cited concerning annual resident rights/annual review and advance directive requirements; the surveyor found the facility failed to ensure annual reviews for the three sampled residents.

Deficiencies (2)
19 CSR 30-88.010(4) Resident Rights-Admission/Annual Review: Based on interview and record review, the facility staff failed to ensure that three of three sampled residents (Resident #1, #2 and #3) or their legal representative had their residents' rights reviewed annually. The facility did not provide a written policy for the annual updates of the Resident Rights.
19 CSR 30-88.010(10) Advance Directive Requirements: Based on interview and record review, the facility failed to ensure that three of three sampled residents had their Advance Directive reviewed annually. The facility did not provide a written policy for the annual updates of the Advance Directives.
Report Facts
residents_sampled: 3

Inspection Report — Jun 11, 2024

Routine
Date: Jun 11, 2024

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
2 state deficiencies were cited concerning oxygen storage practices and building maintenance (a loose light fixture/ceiling hole creating an exposure and hazard). Both deficiencies are Class III.

Deficiencies (2)
19 CSR 30-86.022(17) Oxygen Storage Requirements: The facility failed to store portable oxygen cylinders in accordance with NFPA 99, 1999 Edition; observation showed two portable oxygen cylinders standing upright and not secured in an approved rack in the east hall oxygen storage room.
19 CSR 30-86.032(2) Substantially Constructed & Maintained: The building was not maintained in good repair; observation showed a light fixture in resident room D2 hanging from electrical wiring leaving a three-inch hole in the ceiling that exposed the attic and created a fire and shock hazard.
Report Facts
residents affected by deficiency: 25

Inspection Report — Apr 5, 2023

Routine
Date: Apr 5, 2023

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Four state licensure deficiencies were cited addressing sprinkler system maintenance, use of unapproved plastic wastebaskets, improper oxygen cylinder storage, and unapproved electrical extension cord use.

Deficiencies (4)
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: Based on observation and interview, the facility failed to ensure the complete sprinkler system was tested and maintained in accordance with NFPA 13. A ceiling-mounted sprinkler head in resident room E6 had fallen below ceiling level, leaving the sprinkler head displaced and a hole around the sprinkler piping.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Based on observation and interview, the facility failed to ensure only metal or UL/FM-fire-resistant rated wastebaskets were being used. Unapproved plastic wastebaskets were observed in multiple resident rooms and the activity director's office.
19 CSR 30-86.022(17) Oxygen Storage Requirements: Based on observation and interview, the facility failed to store portable oxygen cylinders in accordance with NFPA 99. Observation on April 5, 2023 at 12:35 P.M. showed five (5) oxygen cylinders standing upright and not stored in an approved rack, or secured by a chain or band in the facilities storage closet in the E hallway.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on observation and interview, the facility failed to properly maintain the electrical wiring system so as not to cause a safety and/or fire hazard. An unapproved electrical extension cord was observed in use in resident room E4.
Report Facts
residents affected: 19 oxygen cylinders observed: 5

Inspection Report — Apr 26, 2022

Routine
Date: Apr 26, 2022

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Five state deficiencies were cited related to range hood certification, fire drill/evacuation planning and consultation, fire drill requirements, sprinkler system maintenance/testing, and electrical wiring maintenance and inspection.

Deficiencies (5)
19 CSR 30-86.022(4)(C) Range Hood Certification: Based on record review and interview on April 26, 2022 the facility failed to inspect and/or maintain the kitchen hood suppression system in accordance with NFPA 96; record review showed no current kitchen hood system inspection on file and the last record was dated 08/05/2021.
19 CSR 30-86.022(5)(A) Fire Drill/Evacuation Plan, Consultation: Based on record review and interview on April 26, 2022 the facility failed to request the required annual consultation from the local fire authority and had no current fire department consultation on file; the last consultation paperwork on file was dated 03/04/2021.
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Based on record review and interview on April 26, 2022 the facility failed to conduct the required minimum number of fire drills annually with required unannounced drills on each shift; record review showed no record of a fire drill being conducted in March 2022 and the last recorded drill was 02/28/2022.
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing: Based on record review, observation and interview on April 26, 2022 the facility failed to inspect and maintain the sprinkler system in accordance with NFPA 25; observation showed no hydraulic calculation plate affixed or posted near the sprinkler riser and the annual sprinkler inspection noted the plate was not affixed.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on observation and interview on April 26, 2022 the facility failed to properly maintain the electrical wiring system and observations showed an unapproved electrical extension cord and two unapproved multiplug adapters in use in resident room B4.
Report Facts
residents affected: 20

Inspection Report — May 2, 2019

Routine
Date: May 2, 2019

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Three Missouri State Form deficiencies were cited involving sprinkler system inspections and gauge recalibration, use of an unapproved portable heater, and electrical wiring/unapproved multiple adapter; two were Class II and one was Class III.

Deficiencies (3)
19 CSR 30-86.022(11)(F) Sprinkler Systems-Inspections, Cert.: The facility failed to ensure required inspections and recalibration of sprinkler system pressure gauges and records lacked documentation of required recalibration and internal inspection.
19 CSR 30-86.032(10) Heaters-Approved Label, Venting, No Portable: A portable heater was observed installed in a resident room closet and the facility failed to ensure only approved heating sources were used.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: An unapproved multiple electrical adapter was observed in a resident room allowing multiple devices to be powered; the adapter was removed during the inspection.
Report Facts
residents affected: 23 residents affected: 23 residents affected: 23

Inspection Report — May 14, 2018

Routine
Date: May 14, 2018

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
One Missouri state deficiency was cited regarding failure to perform and document required fire drills and evacuation practices across all shifts.

Deficiencies (1)
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: The facility failed to perform and/or document fire drills showing at least one drill was performed every three months on each shift for the past twelve months; records showed drills were not conducted on all shifts as required and several drills occurred on the same shift.
Report Facts
fire drills documented: 12

Viewing