Inspection Reports for
Rockhill Manor Assisted Living
4235 LOCUST ST, KANSAS CITY, MO, 64110-1016
Back to Facility Profile6 Reports
Inspection Report — Jun 11, 2025
Routine
Date: Jun 11, 2025
Visit Reason
Missouri Department of Health and Senior Services state licensure surveys (State Form) contained in this file; survey type is not stated (forms completed 2025-06-11 and 2025-09-23 are included).
Findings
Eleven Missouri state licensure deficiencies were cited, covering exit signage, fire alarm testing/maintenance, hazardous area separation and smoke partitions, sprinkler system maintenance/testing, emergency lighting, building repair and maintenance, prohibited portable heaters, electrical wiring and outlet/junction box issues, improper use of extension cords/power strips, and rooms not kept neat and orderly. One smoke-partition finding was noted as previously uncorrected on a later state form page.
Deficiencies (11)
19 CSR 30-86.022(8)(A) Exit Sign Requirements: The facility failed to have exit signs bearing the word EXIT in required locations; multiple exit signs were missing, incorrectly labeled, or had letters smaller than the required six inches.
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: The facility failed to maintain the complete fire alarm system in accordance with NFPA 72; junction boxes and wiring were observed with no cover plates in attic and other locations.
19 CSR 30-86.022(10)(A) Hazardous Area Requirements: The facility failed to ensure hazardous areas were separated by the required one-hour fire-resistive construction; doors to hazardous areas lacked required self-closing devices.
19 CSR 30-86.022(10)(I) Smoke Section Partitions > than 20 beds: Smoke partitions were not continuous from outside wall-to-outside wall and from floor-to-floor or floor-to-roof deck; attic separation walls did not extend to the roof deck.
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing: Sprinkler system components showed corrosion, paint, missing or damaged escutcheon rings and other issues, and some sprinklers lacked required clearance and were obstructed.
19 CSR 30-86.022(12)(A) Emergency Lighting - locations: The facility failed to provide and maintain emergency lighting of sufficient intensity for required locations; lights were missing at specified stairwell/egress locations.
19 CSR 30-86.032(2) Substantially Constructed & Maintained: The building was not maintained in good repair with multiple holes, penetrations, missing ceiling tiles, gaps around pipes and sprinkler heads, and other damage allowing smoke and fire to travel.
19 CSR 30-86.032(10) Heaters-Approved Label, Venting, No Portable: The facility failed to prohibit portable space heaters; portable electric heaters were observed in the laundry and maintenance areas.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: The facility failed to maintain electrical wiring and fixtures properly; live wires not enclosed in junction boxes, unsecured closet lights, outlet boxes not flush, missing cover plates, and exposed wiring were observed.
19 CSR 30-86.032(18) Extension Cords/Duplex Receptacles: The facility allowed improper use of extension cords and power strips, including daisy-chaining and multiple adapters, and extension cords serving as permanent wiring.
19 CSR 30-86.032(23) Rooms Neat, Orderly, Cleaned Daily: The facility failed to keep resident rooms neat and orderly; excessive clutter and items on floors were observed creating tripping hazards and added fire load.
Report Facts
Inspection Report — Dec 30, 2024
Routine
Date: Dec 30, 2024
Visit Reason
Missouri state licensure surveys (State Form); the survey type is not stated.
Findings
One state deficiency cited concerning locked exit doors and failure to maintain exits unlocked; the survey notes the deficiency was previously cited (past noncompliance).
Deficiencies (1)
19 CSR 30-86.022(7)(E) Locked Exit Doors: Based on observation, interview and record review, the facility failed to maintain the south exit doors on the 2nd and 3rd floors unlocked so special knowledge would not be needed to open them, and failed to place information with the code to open the exit doors.
Report Facts
residents potentially affected: 121
Inspection Report — Apr 3, 2024
Routine
Date: Apr 3, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One state licensure deficiency for lack of required electrical wiring inspection documentation and an expired electrical inspection; cited as Class III.
Deficiencies (1)
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: The facility failed to show documentation that the electrical wiring had been inspected within the last two years; the last electrical inspection had expired and this potentially affected 116 of 116 residents.
Report Facts
residents potentially affected: 116
Inspection Report — Aug 31, 2022
Routine
Date: Aug 31, 2022
Visit Reason
Missouri State Form (Missouri Department of Health and Senior Services); the survey type is not stated.
Findings
Two state deficiencies were cited: one involving failure to ensure Individualized Service Plans addressed residents' care needs related to sexual activity, privacy and rights, and one involving failure to provide an appropriate emergency discharge notice. Both findings were based on observation, interview and record review.
Deficiencies (2)
19 CSR 30-86.047(28)(J) Plan to Safeguard Residents: Based on observation, interview and record review, the facility failed to ensure that residents' Individualized Service Plans (ISPs) addressed their care needs surrounding involvement in a sexual relationship and did not ensure the residents' privacy and rights were protected for two sampled residents.
19 CSR 30-88.010(18) Emergency Discharges: Based on observation, interview and record review, the facility failed to ensure that a resident was issued an appropriate emergency discharge letter that included all required information for one sampled resident.
Report Facts
residents affected: 2
residents sampled: 4
residents affected: 1
Inspection Report — Feb 7, 2020
Routine
Date: Feb 7, 2020
Visit Reason
Missouri Department of Health and Senior Services State Form (licensure survey); the survey type is not stated.
Findings
One Missouri State Form deficiency was cited concerning sprinkler system maintenance/testing, specifically missing monthly pressure gauge and valve position records and a missing sprinkler riser room log.
Deficiencies (1)
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing Sprinkler Systems: The facility failed to maintain records of monthly sprinkler pressure gauge readings and valve position checks; the sprinkler riser room log binder was missing and staff could not locate the records. The administrator stated a new log would be set up.
Report Facts
residents affected: 120
Inspection Report — Feb 13, 2019
Routine
Date: Feb 13, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One state licensure deficiency was cited regarding missing documentation of monthly activation/testing of the facility fire alarm system.
Deficiencies (1)
19 CSR 30-86.022(9)(E) Fire Alarm System Monthly Test: Based on record review and an interview, the facility failed to provide documentation that the fire alarm system was activated at least once a month. Record review showed missing alarm activations and monitoring reports.
Report Facts
residents affected: 122
Viewing
Loading inspection reports...