5 Reports
Inspection Report — Dec 21, 2023
Routine
Date: Dec 21, 2023
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Two state licensure deficiencies were cited concerning fire alarm testing/maintenance and electrical wiring inspection/maintenance. Both deficiencies involved failure to provide required testing/inspection documentation and affected all residents.
Deficiencies (2)
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: Based on record review and interview, the facility failed to test and maintain the complete fire alarm system in accordance with NFPA 72, 1999 edition when it did not complete or document the required semi-annual fire alarm inspection; the facility census was 40 and this affected 40 residents.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on record review and interview, the facility failed to provide documentation of electrical wiring inspections every two years by a qualified electrician; the facility census was 40 and this affected 40 residents.
Report Facts
residents affected: 40
Inspection Report — Dec 6, 2021
Routine
Date: Dec 6, 2021
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One state licensure deficiency was cited for failure to have the complete fire alarm system inspected annually, affecting all residents.
Deficiencies (1)
19 CSR 30-86.022(9)(D) Fire Alarm System Inspections/Certifications: Based on record review and interview, the facility failed to have the complete fire alarm system inspected annually by an approved qualified service representative. The deficiency affected all 27 residents.
Report Facts
residents affected: 27
Inspection Report — Feb 5, 2019
Routine
Date: Feb 5, 2019
Visit Reason
Missouri Department of Health and Senior Services state licensure survey (State Form); the survey type is not stated.
Findings
Six state deficiencies involving fire alarm testing and records, hazardous area self-closing doors, sprinkler system escutcheon rings and storage clearance, use of non-approved wastebaskets, and electrical wiring/extension cord/outlet hazards.
Deficiencies (6)
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: The facility failed to test and maintain the complete fire alarm system in accordance with NFPA 72 and did not have the required semi-annual fire alarm system inspection documented. Record review and interview showed no semi-annual inspection had been completed.
19 CSR 30-86.022(10)(A) Hazardous Area Requirements: The facility failed to ensure hazardous areas were separated from other spaces by self-closing smoke-resistant doors. Observations showed the furnace room door would not close due to the bottom door seal dragging and the laundry room doors did not have self-closing devices attached.
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing: The facility had missing and loose escutcheon rings and gaps between escutcheon rings and the ceiling, and stored items too close to a sprinkler deflector, which could impair sprinkler function. A missing escutcheon ring and a one-half inch gap were observed in Resident Room E11.
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Non–UL/FM–fire-resistant rated wastebaskets were being used for trash in facility areas. Observations documented wastebaskets in the activity room and resident rooms that were not UL- or FM-rated.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: The facility failed to maintain the electrical system in good repair and free from safety hazards. Observations included heat tape and extension cords permanently attached to walls and other wiring practices that presented a hazard.
19 CSR 30-86.032(18) Extension Cords/Duplex Receptacles: Extension cords and three-way plugs were being used improperly to power multiple electrical items (an extension cord with a three-way plug powering three items was observed). The administrator indicated the item would be replaced with a power strip.
Report Facts
residents_affected: 38
Inspection Report — Jan 23, 2018
Routine
Date: Jan 23, 2018
Visit Reason
Missouri Department of Health and Senior Services State Form (licensure survey); the survey type is not stated.
Findings
3 state deficiencies: two Class II deficiencies related to fire alarm testing/maintenance and emergency battery-powered lighting, and one Class III deficiency related to electrical wiring maintenance and inspection.
Deficiencies (3)
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: Based on record review and interview during the fire safety portion of the licensure inspection on January 23, 2018, the facility failed to test and maintain the complete fire alarm system in accordance with NFPA 72; record review showed the facility failed to provide documentation of the semi-annual fire alarm inspection.
19 CSR 30-86.022(12)(C) Emergency Lighting -Battery Powered, 1.5 hrs: Based on observation and interview during the fire safety portion of the licensure inspection on January 23, 2018, the facility failed to maintain emergency lighting capable of operating for at least one and one-half hours; observations included emergency lights that would not illuminate in the hallway by resident room #15 and by resident room #27.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected.: Based on observation and interview during the fire safety portion of the licensure inspection on January 23, 2018, the facility failed to maintain electrical wiring in good repair and not present a safety hazard; observations included five power strips daisy chained together with 24 items plugged into them, a missing outlet cover, and a loose light switch cover in the water heater closet.
Report Facts
power strips observed: 5
items plugged into power strips: 24
Inspection Report — Jan 10, 2018
Complaint Investigation
Date: Jan 10, 2018
Visit Reason
Missouri state licensure survey (State Form); complaint investigation for complaint number MO00137479.
Complaint Details
Complaint number MO00137479; determination (substantiated/unsubstantiated) not stated in the form.
Findings
1 state deficiency (Class II*) for failure to inform a resident and/or the resident's Durable Power of Attorney in writing of charges for services not covered by the facility's basic per diem, lack of documentation of outside agency service costs and failure to provide a 30-day written notice of changes; related billing issues including charges totaling over $10,000 for outside one-on-one services.
Deficiencies (1)
19 CSR 30-88.010(8) Informed Services/Charges/Alz Disclosure: Based on observation, interview and record review, the facility failed to fully inform, in writing, one resident (Resident #1) or the resident's Durable Power of Attorney of charges for services not covered by the facility's basic per diem rate and did not document outside agency service costs or provide a 30 day written notice prior to changes in fees. The record review showed billing for outside one-on-one services totaling over $10,000.
Report Facts
Total cost of Home Care/Private Duty services: 10475.94
Viewing
Loading inspection reports...