Inspection Reports for
St Agnes Home
10341 MANCHESTER RD, KIRKWOOD, MO, 63122-1520
Back to Facility Profile3 Reports
Inspection Report — Jun 12, 2025
Routine
Date: Jun 12, 2025
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Six state deficiencies were cited addressing hazardous/storage areas lacking self-closing doors, fire extinguisher signage/placement in a kitchen area, locked exit door/electronic keypad without proper egress signage, smoke barrier doors not closing on alarm, missing required fire drills on night/third shifts, and a medication order/administration discrepancy for one sampled resident.
Deficiencies (6)
19 CSR 30-85.022(4) Hazardous Areas: Based on observation and interview the facility failed to maintain hazardous areas with smoke-resistant doors equipped with self-closing devices; multiple storage/utility/activity rooms were observed without self-closures or with vented/modified doors.
19 CSR 30-85.022(8)(B) Fire Extinguishers-ABC/K Rated: Based on observation and interview the facility failed to ensure portable fire extinguishers were maintained and properly identified; a K-class extinguisher in the main kitchen lacked a placard/signage instructing staff to actuate the range suppression system prior to using the extinguisher.
19 CSR 30-85.022(16) Door Locks: Based on observation and interview the facility failed to maintain exit doors without locks requiring special knowledge; the second floor rotunda door was locked with an electronic keypad with no posted code or delayed egress mechanism.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Based on observation and interview the facility failed to ensure smoke barrier doors closed upon activation of the fire alarm; several smoke barrier doors released from magnets but remained partially or completely open.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Based on interview and record review the facility failed to conduct required fire drills on each shift for two of four quarters reviewed, with missing third-shift and night-shift drills for the periods reviewed.
19 CSR 30-85.042(45) Written Orders; Restraints: Based on observation, interview and record review the facility failed to follow physician medication orders for one of seven sampled residents, resulting in a medication order/discrepancy for Resident #3.
Report Facts
residents sampled: 7
Inspection Report — Apr 30, 2024
Routine
Date: Apr 30, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Fifteen state deficiencies were cited, primarily related to fire and life-safety systems and infection control. Main topics included combustible storage under stairways, unsealed penetrations and smoke barrier breaches, hazardous storage areas without self-closing doors, improper oxygen storage and excess tanks, fire extinguisher mounting/inspection issues, incomplete fire alarm testing/documentation and out-of-service procedures, missing sprinkler coverage, inadequate fire drill documentation, noncompliant wastebaskets, portable heaters present, and deficiencies in infection control/wound care.
Deficiencies (15)
19 CSR 30-85.022(2)(D) Combustibles Not Stores Under Stairways: Based on observation and interview, staff failed to prohibit storage under a stairway exit, with combustible materials stored beneath an exit stairwell.
19 CSR 30-85.022(3) Noncombustible Material Between Floors: Based on observation and interview, the facility failed to maintain required noncombustible fire-stopping/sealing for openings between floors, leaving multiple pipe and conduit penetrations unsealed.
19 CSR 30-85.022(4) Hazardous Areas: Based on observation and interview, hazardous storage rooms lacked self-closing doors and contained combustible supplies and multiple cans of paint in rooms larger than allowed for unsecured storage.
19 CSR 30-85.022(6) Oxygen Storage: Based on observation and interview, unused oxygen cylinders were stored improperly in closets and on shelves rather than in designated, secured storage racks.
19 CSR 30-85.022(7) Emergency-Use Oxygen, One per Unit: Based on observation, interview and record review, the facility failed to ensure only one emergency-use oxygen tank was readily accessible per nursing unit, with multiple tanks improperly stored in a resident room.
19 CSR 30-85.022(8)(D) Fire Extinguisher UL/FM, Monthly Check: Based on observation and interview, fire extinguishers were not maintained in accordance with NFPA requirements and several were mounted too high above the finished floor.
19 CSR 30-85.022(10)(B) Fire Alarm System-Test/Maintain: Based on observation, interview and record review, the facility lacked complete and verifiable documentation for annual inspection and testing of the fire alarm system and failed to maintain control panel security.
19 CSR 30-85.022(10)(H) Fire Alarm System-Out of Service > than 4hrs: Based on observation, interview, and record review, the facility lacked a complete fire watch policy and procedures for when the fire alarm system is out of service for more than four hours.
19 CSR 30-85.022(11)(B) No Complete Sprinkler System Prior to 8/28/07: Based on observation and interview, the facility failed to provide sprinkler coverage in a closet in the lower level kitchen manager's office.
19 CSR 30-85.022(11)(E) Sprinkler System Out of Service More Than 4hr: Based on observation, interview, and record review, the facility lacked a complete policy/procedures to follow when the sprinkler system is out of service for more than four hours.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Based on observation and interview, smoke barrier walls contained holes and penetrations (including PVC piping and crumbling areas) that compromised the smoke barrier.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Based on interview and record review, required fire drills were not documented as completed on each shift quarterly for multiple quarters.
19 CSR 30-85.022(40)(A) Wastebaskets, Metal/UL/FM: Based on observation and interview, nonmetal/unapproved wastebaskets were in resident rooms instead of only UL- or FM-approved metal wastebaskets.
19 CSR 30-85.032(28) Heating System-No Portable: Based on observation and record review, portable heaters were present and used in resident areas despite facility policy prohibiting portable space heaters.
19 CSR 30-85.042(77) Infection Control/Communicable Disease: Based on observation, interview and record review, staff failed to follow infection control procedures during wound care, including placing supplies on the floor and not performing hand hygiene between glove changes.
Report Facts
smoke_compartments: 23
sample_size_for_oxygen_review: 10
Inspection Report — Jan 4, 2019
Routine
Date: Jan 4, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Four state deficiencies were cited addressing life safety and infection control topics: missing sprinkler coverage in a linen closet, unsealed smoke barrier penetrations, inadequate clearances at energized electrical panels, and incomplete employee tuberculosis screening documentation.
Deficiencies (4)
19 CSR 30-85.022(11)(D) Complete Sprinkler System: Based on observation and interview, the facility failed to provide complete fire sprinkler coverage in a linen storage closet; the closet had no sprinkler and was stacked to the ceiling.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: The facility failed to maintain smoke barriers by properly sealing openings; an approximately 10 inch duct penetrated a smoke barrier wall with about a 1/2 inch unsealed gap.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: The facility failed to maintain required clear working space at energized electrical panels, with items such as a chair, a mechanic cart and pallet stored within the 36 inch clearance.
19 CSR 30-85.042(27) Communicable Disease-Employees: Based on interview and record review, the facility failed to ensure employees working 10 or more hours per week received required TB screening and the two-step PPD documentation was incomplete in multiple employee files.
Report Facts
employee files reviewed: 10
Viewing
Loading inspection reports...