2 Reports
Inspection Report — May 23, 2022
Routine
Date: May 23, 2022
Visit Reason
Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
2 state licensure deficiencies were cited related to sprinkler system maintenance and electrical wiring/unauthorized electrical devices. Both deficiencies affected all nineteen residents.
Deficiencies (2)
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13: The facility failed to inspect and maintain the sprinkler system in accordance with the applicable standard. A sprinkler head in the closet of a resident room was displaced from the ceiling leaving an opening and the hydraulic calculation plate was not affixed or posted near the sprinkler riser.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: The facility failed to properly maintain the electrical wiring system so as not to cause a safety or fire hazard. Observations included an unapproved electrical adapter used to power a resident room refrigerator and a power strip piggybacked onto another power strip.
Report Facts
residents affected by deficiency (sprinkler): 19
residents affected by deficiency (electrical): 19
Inspection Report — Jun 19, 2019
Routine
Date: Jun 19, 2019
Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure survey); the survey type is not stated.
Findings
5 state licensure deficiencies were cited involving fire/smoke door closure, missing sprinkler escutcheon rings, improper oxygen cylinder storage, use of an unapproved portable heater, and unapproved electrical cords/outlet adapters. Four deficiencies were Class II and one was Class III.
Deficiencies (5)
19 CSR 30-86.022(10)(1) Smoke Section Partitions > than 20 beds Protection from Hazards.: The required smoke doors separating the dining room from the C hallway failed to fully close when released from their magnetic holding devices, leaving approximately a 1 3/4 inch opening and failing to completely close on multiple attempts; the facility census was 24 and the deficiency affected all residents.
19 CSR 30-86.022(11)(B) Sprinkler System Maintenance/Testing Sprinkler Systems.: Escutcheon rings were missing leaving open holes around sprinkler heads located in the closet of resident room E Seven (E7) and in the E hallway in front of room E7.
19 CSR 30-86.022(17) Oxygen Storage Requirements: Four portable oxygen cylinders were observed standing upright and not stored in an approved rack or secured by chain or band inside the oxygen storage room of hallway B.
19 CSR 30-86.032(10) Heaters-Approved Label, Venting, No Portable: A portable heater was observed located in the Wellness Office and was determined not to meet fire safety standards.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: An unapproved electrical extension cord was in use in resident room C-1 and an unapproved multiple outlet adapter was in use in resident room F-2.
Report Facts
residents affected: 24