11 Reports
Inspection Report — May 20, 2026
Routine
Date: May 20, 2026
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
1 state licensure deficiency regarding improper food storage. The deficiency concerns unlabeled, undated, and exposed food items found in the memory care unit kitchen refrigeration and freezer.
Deficiencies (1)
19 CSR 30-87.030(13) Food-Protected, Temp, Need to Contact DHSS: Based on observation, interview and record review, facility staff failed to store food to prevent potential contamination and outdated use. Numerous unlabeled, undated, and exposed food items were observed in the memory care unit kitchen refrigeration and freezer.
Inspection Report — Oct 22, 2025
Routine
Date: Oct 22, 2025
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
2 state deficiencies: one concerned operator/administrator responsibilities related to an expired DHSS exception and a kitchen pass‑thru that did not self/automatically close, and the other concerned food protection including expired, undated, and opened food items not discarded or properly labeled.
Deficiencies (2)
19 CSR 30-86.047(6) Operator/Administrator Responsibilities: Based on observation, interview, and record review, facility staff failed to maintain active DHSS exception approval for the kitchen pass‑thru; the approval had expired and was not posted, and the kitchen pass‑thru window did not self or automatically close and was being used to pass food.
19 CSR 30-87.030(13) Food-Protected, Temp, Need to Contact DHSS: Based on observation and interview, facility staff failed to protect food from potential contamination and failed to discard or properly label and date expired, undated, and opened prepackaged food items found in refrigerators, freezer, and dry storage.
Inspection Report — Oct 3, 2024
Routine
Date: Oct 3, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Three state licensure deficiencies were cited related to missing Employee Disqualification List (EDL) documentation for staff, missing/insufficient tuberculosis (TB) screening/testing documentation for residents and staff, and unsigned or missing physician order signatures on physician order sheets.
Deficiencies (3)
19 CSR 30-86.047(12) EDL Requirements: Based on interview and record review, facility staff failed to maintain documentation showing Employee Disqualification List (EDL) reviews were completed prior to contact with residents for four employees.
19 CSR 30-86.047(19) TB Screen Residents & Staff: Based on interview and record review, facility staff failed to ensure required two-step TB testing and documentation for multiple residents and one employee.
19 CSR 30-86.047(47)(B) Physicians Orders Requirements: Based on interview and record review, facility staff failed to ensure physician order sheets were signed by a physician every three months for five of six sampled residents.
Report Facts
employees with missing EDL reviews: 4
residents missing two-step TB test documentation: 3
employees missing TB test documentation: 1
sampled residents with unsigned physician order sheets: 5
Inspection Report — Jan 30, 2024
Routine
Date: Jan 30, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One Missouri State Form deficiency was cited for failure to perform required electrical wiring inspections and to maintain electrical wiring, creating a potential safety/fire hazard. The deficiency is Class III.
Deficiencies (1)
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: The facility failed to have the building's electrical wiring inspected every two years and did not properly maintain wiring, creating a safety/fire hazard. Document review showed the last electrical inspection was done on November 30, 2021.
Report Facts
residents affected: 24
Inspection Report — Jan 3, 2023
Routine
Date: Jan 3, 2023
Visit Reason
Missouri Department of Health and Senior Services state licensure survey (State Form); the survey type is not stated.
Findings
Nine state deficiencies were cited addressing fire and life-safety topics, including fire hazards and detector maintenance, portable fire extinguishers and range hood extinguishing certification, fire drill and evacuation planning, fire alarm inspections, emergency lighting, flame-resistant curtains/drapes, and building construction/maintenance (sprinkler/ceiling openings).
Deficiencies (9)
19 CSR 30-86.022(2)(D) Inspection Rights, No Fire Hazard: Observations found a smashed/kinked dryer vent hose, expired carbon monoxide detectors, and fire door magnets that did not release, creating a fire hazard affecting residents.
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: The facility failed to ensure all portable fire extinguishers were installed and maintained per NFPA 10; the K-class extinguisher in the kitchen had a loose mounting bracket and was not securely mounted.
19 CSR 30-86.022(4)(C) Range Hood Certification: The facility failed to ensure the range hood extinguishing systems had been certified at least twice annually as required; current certification tags showed the most recent date of August 2022 and supporting semiannual inspection documentation was not on file.
19 CSR 30-86.022(5)(A) Fire Drill/Evacuation Plan, Consultation: The facility failed to provide documentation of annual consultation from the local fire department for review of fire and evacuation plans.
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: The facility failed to conduct the required twelve fire drills annually with at least one every three months on each shift, with records missing for certain months.
19 CSR 30-86.022(9)(D) Fire Alarm System Inspections/Certifications: The facility failed to ensure the complete fire alarm system was inspected and certified annually as required; review showed no annual inspection and the last documented inspection was in August 2001.
19 CSR 30-86.022(12)(C) Emergency Lighting -Battery Powered, 1.5 hrs: The facility failed to provide battery-powered emergency lighting capable of operating for at least one and one-half hours; observations and testing showed emergency lights that would not illuminate as required.
19 CSR 30-86.022(13)(D) Curtains/Drapes, Flame Resistant: The facility failed to ensure curtains and drapes were certified or treated to be flame-resistant as defined in NFPA 101; multiple resident and non-resident rooms had drapes or curtains without documentation of flame-retardant treatment.
19 CSR 30-86.032(2) Substantially Constructed & Maintained: The facility failed to maintain building 3104 in good repair; observations found gaps in sheetrock around sprinkler heads and a 3" x 4" hole in an attic access panel that could allow smoke and flame spread and impede sprinkler activation.
Report Facts
residents affected: 13
residents affected: 10
residents affected: 23
residents affected: 13
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Carolyn Becker | Administrator | Interviewed on January 3, 2023; she stated she would have maintenance or request inspections/repairs to address the noted deficiencies. |
Inspection Report — Jul 6, 2022
Complaint Investigation
Date: Jul 6, 2022
Visit Reason
Missouri state licensure survey (State Form); complaint investigation. Complaint numbers M000203308 and M000202978 are cited in the file.
Complaint Details
Complaint numbers M000203308 and M000202978; substantiation not stated.
Findings
Two Missouri state deficiencies were cited concerning Protective Oversight and Proper Care per Individual Service Plan. One involved failure to provide 24-hour visual checks resulting in a resident found on the floor with blood and feces, and the other involved failure to document and verify a resident's code status which led to the resident being intubated and receiving blood products.
Deficiencies (2)
19 CSR 30-86.047(35) Protective Oversight: The facility failed to provide 24-hour protective oversight for one sampled resident when staff did not conduct visual checks throughout the night. The resident was later found on the bathroom floor and the room contained blood and feces on walls, carpet, bedding and bathroom surfaces.
19 CSR 30-86.047(36) Proper Care Per Individual Service Plan: The facility failed to document and follow-up on an accurate code status for one resident, listing the resident as Full Code instead of Do Not Resuscitate and not verifying the DNR paperwork. As a result, hospital staff intubated the resident and administered blood products against the resident's wishes.
Report Facts
residents sampled: 1
Inspection Report — Nov 15, 2021
Routine
Date: Nov 15, 2021
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Three Missouri state licensure deficiencies were cited concerning fire drill frequency/evacuation, semi-annual fire alarm inspection documentation, and electrical wiring inspection frequency. Two deficiencies were Class III and one was Class II.
Deficiencies (3)
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Based on interview and record review on November 15, 2021, the facility failed to perform required fire drills on each shift every three months and did not perform twelve fire drills annually, affecting all 22 residents.
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: Based on record review and interview on November 15, 2021, the facility failed to provide documentation of required semi-annual fire alarm inspections for the Arbors, with the most recent inspection dated 12/10/2020, affecting all 22 residents.
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on interview and record review, the facility failed to have electrical wiring inspected every two years, with the most recent report dated December 27, 2018, affecting all 22 residents.
Report Facts
residents affected: 22
Inspection Report — Dec 3, 2019
Routine
Date: Dec 3, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One Missouri state licensure deficiency was cited relating to hazardous area/fire separation between the kitchen and the dining area in the Arbors. The finding concerns a pass-through window with manual bi-fold doors that could allow smoke and toxic gases to pass into the dining room.
Deficiencies (1)
19 CSR 30-86.022(10)(A) Hazardous Area Requirements: The facility failed to ensure the kitchen was separated from the remainder of the facility by smoke-stop partitions in the Arbors. A pass-through window between the kitchen and the dining room had manual bi-fold doors with an approximate one-inch gap and were not automatic closing or connected to the fire alarm system, which could allow smoke and toxic gases to pass into the dining area.
Report Facts
residents affected: 37
Inspection Report — Oct 2, 2019
Routine
Date: Oct 2, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Two Missouri state deficiencies were cited related to failure to conduct required unannounced fire drills and failure to properly date, label, and store opened/prepackaged foods in kitchen storage areas.
Deficiencies (2)
19 CSR 30-86.022(5)(D) Fire Drill Requirements, Evacuation: Based on interview and record review, facility staff failed to conduct required unannounced fire drills at various times and on each shift quarterly between October 2018 and September 2019, which could delay response procedures.
19 CSR 30-87.030(13) Food-Protected, Temp, Need to Contact DHSS: Based on observation and interview, facility staff failed to date and label opened and prepackaged foods and failed to store food properly in multiple kitchen storage areas, including upright freezers, refrigerators and dry storage.
Inspection Report — Dec 4, 2018
Routine
Date: Dec 4, 2018
Visit Reason
Missouri Department of Health and Senior Services State Form (statement of deficiencies and plan of correction); the survey type is not stated.
Findings
Three Missouri state licensure deficiencies were cited involving fire extinguisher maintenance, hazardous area self-closing doors, and emergency lighting; the surveyor found these issues during the fire safety portion of the licensure inspection and they affected all 38 residents.
Deficiencies (3)
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: The surveyor found the facility failed to ensure monthly checks of fire extinguishers; extinguisher tags were not dated and there was no documentation showing they were checked in November, affecting thirty-eight residents.
19 CSR 30-86.022(10)(A) Hazardous Area Requirements Protection from Hazards: The surveyor found the facility failed to maintain self-closing devices on doors to hazardous areas; the laundry room door self-closing hinges were broken and would not close, allowing smoke and poisonous gases to enter the hallway, affecting thirty-eight residents.
19 CSR 30-86.022(12)(C) Emergency Lighting -Battery Powered, 1.5 hrs: The surveyor found the facility failed to ensure emergency lighting operated on battery power for the required time; an emergency light in the west hall did not illuminate when the test button was pressed, affecting thirty-eight residents.
Report Facts
residents affected: 38
Inspection Report — Sep 19, 2018
Routine
Date: Sep 19, 2018
Visit Reason
Missouri Department of Health and Senior Services state licensure survey (State Form); the survey type is not stated.
Findings
4 state deficiencies were cited addressing tuberculosis screening for employees, the facility's safe and effective medication system including medication administration technique, documentation of medication administration on MARs, and food service utensil storage/dispensing.
Deficiencies (4)
19 CSR 30-86.047(19) TB Screen Residents & Staff: The surveyor found employee TB screening documentation was missing or incomplete and specific staff (CMA F and Cook J) did not have documented TB screening in their personnel files.
19 CSR 30-86.047(46) Safe & Effective Medication System: The surveyor found facility staff failed to ensure a safe and effective medication system, including failure to use proper hand washing and proper utensil storage/handling during medication administration.
19 CSR 30-86.047(47)(G) Medication Administration, Documented Medication Orders: The surveyor found facility staff failed to record administration of medications on the Medication Administration Record (MAR) for numerous sampled residents and multiple medication administrations were not documented.
19 CSR 30-87.030(41) Food Service-Dispensing Utensils Use/Storage: The surveyor found dispensing utensils were stored in a manner that allowed food debris contamination and staff stored scoops inside containers rather than preventing contamination.
Report Facts
residents affected: 5
Viewing