Inspection Report — May 14, 2026
Citations: 7
Date: May 14, 2026
Visit Reason
State-compiled facility profile showing 7 citations from a comprehensive inspection on 2026-05-14 with deficiency history including prior inspections.
Findings
The facility had 7 life safety code citations from a prior inspection dated 2019-05-21, all corrected, and no health code violations or enforcement actions were found.
Citations (7)
The facility failed to comply with Chapter 19 of NFPA 101.
The facility failed to ensure interior walls and/or ceilings were constructed with a material having at least a 20-minute fire rating, or at least 3/8 gypsum board.
The facility failed to provide a written contract with a fire alarm firm to perform inspections, testing, and system maintenance at least every six months.
The facility failed to ensure the required sprinkler system was inspected, tested, and maintained in compliance with NFPA 25.
The facility failed to provide the required sprinkler system to meet NFPA 13.
The facility failed to ensure the building was kept in good repair.
The facility failed to provide and/or maintain a commercial range hood and exhaust system in compliance with NFPA 96.
Report Facts
Inspections on page: 1
Citations: 7