Inspection Reports for
Village Concepts of Auburn – Brannan Park
2901 I St NE, Auburn, WA 98002, United States, WA, 98002
Back to Facility Profile6 Reports
Inspection Report — Apr 30, 2026
Re-Inspection
Date: Apr 30, 2026
Visit Reason
The Office of the State Fire Marshal conducted a fire and life safety inspection at Village Concepts of Auburn to determine compliance with applicable codes.
Findings
All violations noted during previous related inspections have been corrected. The current inspection found no open violations and the facility was approved.
Deficiencies (9)
IFC 315.2.3 (2021) - Combustible material shall not be stored in boiler rooms, mechanical rooms, electrical equipment rooms or in fire command centers.
IFC 606.3.3 (2021) - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at required intervals.
IFC 606.4 (2021) - Gas-fired commercial cooking appliances on casters shall be connected with listed appliance connectors and movement limited by restraining devices.
IFC 701.6 (2021) - Owner shall maintain inventory and visually inspect fire-resistance-rated construction annually and repair as needed.
IFC 705.2 (2021) - Opening protectives in fire-resistance-rated assemblies shall be inspected and maintained per NFPA 80 and NFPA 105.
IFC 903.5 (2021) - Sprinkler systems shall be tested and maintained in accordance with Section 901.
IFC 1103.4.9.5 (2021) - Chute discharges shall have self-closing or automatic-closing opening protectives with at least 1-hour fire rating.
IFC 1203.4 (2021) - Emergency and standby power systems shall be maintained to supply service within required time.
NFPA 80 Fire/Smoke Dampers Inspection and Testing - Dampers shall be inspected and tested periodically as required.
Inspection Report — Apr 28, 2026
Enforcement
Date: Apr 28, 2026
Visit Reason
The Department of Social and Health Services conducted a follow-up visit to the assisted living facility to assess compliance and imposed a civil fine based on unresolved deficiencies.
Findings
The facility failed to document care, services, and interventions in four residents' Negotiated Service Agreements, placing residents at risk. This deficiency was uncorrected from a prior citation and resulted in a $400 civil fine.
Deficiencies (1)
WAC 388-78A-2140 (1)(a)(ii)(iii) Negotiated Service Agreement Contents. The licensee failed to document in four residents’ Negotiated Service Agreements the care, services, and interventions to meet the resident’s needs, placing residents at risk for unmet care needs and worsening conditions.
Report Facts
Civil fine amount: 400
Number of residents affected: 4
Inspection Report — Apr 21, 2026
Follow-Up
Date: Apr 21, 2026
Visit Reason
Unannounced on-site follow-up inspection to verify correction of previously cited deficiencies.
Findings
The facility was found not in compliance with licensing laws due to failure to document negotiated service agreements for four sampled residents regarding care, services, and interventions related to their medications and health needs. This deficiency was previously cited and remains uncorrected.
Deficiencies (1)
WAC 388-78A-2140 Negotiated service agreement contents. The facility failed to document in 4 of 12 sampled residents' negotiated service agreements the care, services, and interventions to meet their needs, placing them at risk for unmet care and worsening conditions.
Report Facts
Sampled residents: 7
Current residents: 79
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Staff J | Resident Care Director | Interviewed regarding lack of documented instructions and guidance in residents' negotiated service agreements. |
Inspection Report — Apr 9, 2026
Complaint Investigation
Date: Apr 9, 2026
Visit Reason
The inspection was conducted in response to a complaint about a fire in a rag bin at Village Concepts of Auburn.
Complaint Details
Complaint #217519 alleged a fire in a rag bin. The investigation confirmed the fire occurred but found no violations. The complaint was not substantiated with any code violations.
Findings
The investigation found that the fire was caused by rags that were improperly dried and stored. The fire was extinguished promptly with no injuries or building maintenance issues. No IFC violations were observed and the facility is implementing longer cool-down times for rags.
Inspection Report — Feb 25, 2026
Complaint Investigation
Date: Feb 25, 2026
Visit Reason
The inspection was conducted to investigate complaint #213421 regarding a sprinkler issue at Village Concepts of Auburn.
Complaint Details
Complaint #213421 alleged a sprinkler issue. The contractor repaired the sprinkler and no violations were found during the inspection, indicating the complaint was unsubstantiated.
Findings
The contractor repaired the cited sprinkler by cutting the pipe and gluing it. The sprinkler head was fixed and the system was operational with no violations found at the time of inspection.
Report Facts
Cure time: 24
Inspection Report — Jan 22, 2026
Re-Inspection
Date: Jan 22, 2026
Visit Reason
This report is the result of an unannounced fire and life safety re-certification survey conducted to determine compliance with applicable codes at Village Concepts of Auburn.
Findings
The facility was found not in compliance at the time of inspection with multiple deficiencies cited across fire and life safety areas including combustible material storage, cleaning documentation, appliance connections, fire door maintenance, sprinkler system testing, chute discharge protection, emergency power system maintenance, and fire/smoke damper inspection documentation.
Deficiencies (9)
IFC 315.2.3 (2021) - Combustible material was stored in stairwells on the 3rd floor stair 5, 1st floor stair 4, and 1st floor stair 1.
IFC 606.3.3 (2021) - Documentation for first and second semi-annual hood cleaning was not provided at the time of inspection.
IFC 606.4 (2021) - Facility must verify that cooking appliances on casters have required restraining devices and are connected to the wall.
IFC 701.6 (2021) - Documentation for detailed maps of fire-rated construction locations and annual inspection reports was not provided.
IFC 705.2 (2021) - Stairwell doors on 3rd floor stair 3, 3rd floor stair 5, 2nd floor stair 5, and 1st floor stair 2 were missing gasketing, edge seals, or would not latch.
IFC 903.5 (2021) - Documentation for 5-year internal pipe testing, annual forward flow test, and 5-year FDC Hydro testing was not provided; loaded sprinkler head observed in 2nd floor resident laundry room.
IFC 1103.4.9.5 (2021) - Trash chute will need to be tested along with all chute doors by an outside vendor.
IFC 1203.4 (2021) - Documentation for diesel fuel testing for the diesel generator was not provided.
NFPA 80 - Fire/smoke dampers inspection and testing documentation was not provided and must be performed and documented.
Report Facts
Next inspection date: Feb 19, 2026