Inspection Reports for
Villas of Jackson LLC the
670 BROADRIDGE DRIVE, JACKSON, MO, 63755-3044
Back to Facility Profile4 Reports
Inspection Report — Feb 14, 2022
Routine
Date: Feb 14, 2022
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Three state licensure deficiencies were cited regarding lack of annual fire department consultation for fire drills/evacuation plans, missing semi-annual fire alarm system inspections for the memory care building, and sprinkler system deficiencies in the memory care building.
Deficiencies (3)
19 CSR 30-86.022(5)(A) Fire Drill/Evacuation Plan, Consultation: The facility failed to request annual fire department consultation or provide documentation of scheduled consultation for review of fire and evacuation plans; no current annual fire department consultation was on file for the main building or the memory care building.
19 CSR 30-86.022(9)(D) Complete Fire Alarm Systems: The facility failed to ensure the memory care building's complete fire alarm system was tested semi-annually; no semi-annual fire alarm inspection was on file for the memory care building.
19 CSR 30-86.022(11)(A) Sprinkler Systems: The facility failed to maintain the sprinkler system in the memory care building; sprinkler escutcheon rings were dislodged and sprinkler heads had been withdrawn from the ceiling leaving openings that could impair sprinkler operation.
Report Facts
residents affected (main building): 56
residents affected (memory care building): 16
Inspection Report — Jan 9, 2020
Routine
Date: Jan 9, 2020
Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure survey); the survey type is not stated.
Findings
Three state licensure deficiencies were cited relating to fire/safety issues: unapproved wastebasket use, improper oxygen cylinder storage, and unapproved electrical extension cord/wiring hazards. All deficiencies cite impacts to residents and were identified during the January 9, 2020 fire safety inspection.
Deficiencies (3)
19 CSR 30-86.022(15)(A) Wastebaskets, Metal/UL/FM-Requirements: Based on observation and interview during the fire safety inspection on January 9, 2020 the facility had an unapproved plastic wastebasket in use in resident room 202 and failed to ensure only metal or UL- or FM-fire-resistant rated wastebaskets were used.
19 CSR 30-86.022(17) Oxygen Storage Requirements: Based on observation and interview during the fire safety inspection on January 9, 2020 the facility failed to store portable oxygen cylinders in approved racks or secured as observed in multiple resident rooms (including rooms 406, 321, 305 and 210).
19 CSR 30-86.032(13) Electrical Wiring, Maintained, Inspected: Based on observation and interview during the fire safety inspection on January 9, 2020 the facility had an unapproved electrical extension cord in use in resident room 202.
Report Facts
residents affected by cited deficiencies: 56
Inspection Report — Aug 8, 2019
Routine
Date: Aug 8, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
1 state deficiency for resident rights admission/annual review: the facility failed to ensure resident rights were reviewed and signed annually for sampled residents. Records for three of five sampled residents lacked signed resident rights for the current year.
Deficiencies (1)
19 CSR 30-88.010(4). Resident Rights-Admission/Annual Review: Based on interview and record review, the facility staff failed to ensure three out of five sampled residents had their resident rights reviewed annually and the records did not contain signed resident rights for the current year for Residents #1, #2, and #3.
Report Facts
residents sampled: 5
residents affected: 3
Inspection Report — Jan 14, 2019
Routine
Date: Jan 14, 2019
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
1 state licensure deficiency concerning smoke section partitions and a smoke separation door that failed to fully close, compromising smoke containment and affecting all residents.
Deficiencies (1)
19 CSR 30-86.022(10)(l) Smoke Section Partitions > than 20 beds: The smoke separation door in the 300 hallway failed to fully close on multiple releases due to a malfunctioning push bar, leaving approximately a 3/4 inch opening that would allow smoke and hot gases to pass; the deficiency affected all 48 residents.
Report Facts
residents affected: 48
Viewing
Loading inspection reports...