Inspection Report — Jan 12, 2026

Life Safety
Date: Jan 12, 2026

Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire and life safety code inspection at Wesley Homes Lea Hill to determine compliance with applicable codes.

Findings
All violations noted during previous related inspections have been corrected. The facility was approved following this inspection.

Inspection Report — Jul 28, 2025

Life Safety
Date: Jul 28, 2025

Visit Reason
On 07/28/2025, the Office of the State Fire Marshal conducted an unannounced Fire and Life Safety Code inspection at Wesley Homes Lea Hill to determine compliance with applicable codes.

Findings
Multiple fire and life safety code violations were observed throughout the facility, including uncovered electrical junction boxes, improperly tethered gas appliances, missing grease caps on sprinkler heads, and lack of documentation for required inspections and maintenance. The facility was disapproved due to these deficiencies.

Deficiencies (18)
IFC 603.2.2 (2021) - The patio area had an uncovered electrical junction box, which is prohibited.
IFC 603.4 (2021) - The electrical closet had multiple items in front of electrical panels impeding the required 36-inch clearance.
IFC 606.4 (2021) - Gas fired wheeled appliances in the kitchen were not tethered to the wall as required.
IFC 701.5 (2018) - Electrical closet had penetrations in walls without fire resistance rated material installed.
IFC 705.2 (2021) - The facility was unable to provide documentation that the annual fire door inspection had been performed.
IFC 705.2.4 (2021) - The fire door near the dining area did not latch from a fully open position.
IFC 903.5 (2021) - The facility was unable to provide documentation for required sprinkler system testing and maintenance, and multiple sprinkler heads were loaded with dust or grease.
IFC 904.13.5.2 (2021) - The facility was unable to provide documentation for semi-annual kitchen suppression servicing, and sprinkler heads were missing grease caps or improperly oriented.
IFC 906.2 (2021) - The facility was unable to provide documentation for annual and monthly fire extinguisher servicing and inspections.
IFC 906.6 (2021) - The fire extinguisher near room 155 was obstructed from view.
IFC 907.10 (2021) - The facility was unable to provide documentation for monthly smoke detector testing and reports.
IFC 907.8.1 (2021) - The smoke detector near cooking appliances in the kitchen was heavily covered in grease.
IFC 907.8.3 (2021) - The facility was unable to provide documentation for smoke detector sensitivity testing and nuisance log maintenance.
IFC 915.6 (2021) WAC - The facility was unable to provide documentation for monthly carbon monoxide alarm and detector testing.
IFC 1032.10.1 (2021) - The facility was unable to provide documentation for monthly 30-second emergency lighting activation tests.
IFC 1031.10.2 (2021) - The facility was unable to provide documentation for annual 90-minute emergency lighting power tests.
IFC 1203.4 (2021) - The facility was unable to provide documentation for annual servicing, weekly inspections, and monthly 30-minute load tests of emergency and standby power systems.
WAC 212-12-044 - The facility was unable to provide documentation that fire drills were performed one per shift, per quarter, over the last 12 months.
Report Facts
Next inspection scheduled date: Aug 27, 2025

Inspection Report — Mar 17, 2025

Follow-Up
Date: Mar 17, 2025

Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility to verify correction of previously cited deficiencies and compliance with licensing requirements.

Findings
The follow-up inspection found no deficiencies and confirmed that the facility meets the Assisted Living Facility licensing requirements. All previously cited deficiencies were corrected.

Inspection Report — Jun 26, 2023

Life Safety
Date: Jun 26, 2023

Visit Reason
The Office of the State Fire Marshal conducted a scheduled fire and life safety code inspection at the facility on 06/26/2023.

Findings
All violations noted during previous related inspections have been corrected. The facility was approved following this inspection.