Inspection Reports for
White River Assisted Living

2229 JENSEN ST, ENUMCLAW, WA, 98022

Back to Facility Profile

7 Reports

2024–2026

Inspection Report — May 14, 2026

Re-Inspection
Date: May 14, 2026

Visit Reason
This is an unannounced fire and life safety re-inspection and re-certification survey conducted to determine compliance with applicable codes at White River Assisted Living.

Findings
The facility was found not in compliance at the time of inspection with multiple deficiencies cited related to electrical terminations, sprinkler system testing and maintenance, fire extinguishing system service, emergency power for illumination, and exit signage. Documentation for required testing and servicing was not provided, and some emergency lighting and exit signs were missing or not illuminated.

Deficiencies (6)
IFC 603.2.2 (2021) - Open junction boxes and open-wiring splices are prohibited. Approved covers must be provided for all switch and electrical outlet boxes. The kitchen's office has a missing receptacle cover.
IFC 903.5 (2021) - Sprinkler systems must be tested and maintained per Section 901. Documentation including annual sprinkler system report, annual forward flow test, and 5-year hydro testing was not provided.
IFC 904.13.5.2 (2021) - Automatic fire-extinguishing systems must be serviced at least every six months with certificates forwarded to the fire code official. First and second semi-annual servicing reports were not provided.
IFC 907.8 (2021) - Maintenance and testing schedules for fire alarm and detection systems must be maintained with records. Annual, semi-annual, and smoke detector sensitivity reports were not provided.
IFC 1008.3 (2021) - Power supply for means of egress illumination must be provided by the premises' electrical supply. Emergency lighting in the new building's southeast stairwell and stairwell by room 208 needs testing.
IFC 1013.1 (2021) - Exit and exit access doors must be marked by approved exit signs visible from any direction of egress travel. Two exit signs on the 2nd floor in the old building are not illuminated, and an exit sign is missing on the 1st floor by room 116.

Inspection Report — Apr 13, 2026

Complaint Investigation
Date: Apr 13, 2026

Visit Reason
The inspection was conducted in response to a complaint (#219910) regarding the facility's air compressor and fire suppression system.

Complaint Details
Complaint #219910 involved a concern about the air compressor affecting the fire suppression system. The complaint was investigated and found to be unsubstantiated as no violations were observed and the system was in normal status after repairs.
Findings
The fire suppression system was found to be on a 30-minute fire watch due to a low air compressor. Repairs were underway and the fire watch was removed after verification. No IFC violations were observed during the inspection.

Inspection Report — Mar 4, 2026

Follow-Up
Date: Mar 4, 2026

Visit Reason
The Department completed a follow-up inspection of the Assisted Living Facility to verify correction of previously cited deficiencies.

Findings
The follow-up inspection on 03/04/2026 found no deficiencies and confirmed that the facility meets Assisted Living Facility licensing requirements. Previously cited deficiencies were corrected as listed.

Report Facts
Sampled residents: 7 Former residents: 0 Staff training deficiency: 1 Rooms with approval deficiency: 1 Non-functioning paper towel dispensers: 2 Handwashing sink deficiencies: 1

Inspection Report — Aug 19, 2025

Complaint Investigation
Date: Aug 19, 2025

Visit Reason
The inspection was conducted in response to complaint #189610 regarding trouble with the fire alarm panel at White River Assisted Living.

Complaint Details
Complaint #189610 alleged trouble with the fire alarm panel. The investigation confirmed issues with the fire alarm panel and fire watch policy noncompliance. Violations were cited and remain uncorrected.
Findings
The fire alarm panel was found to be in trouble status and the communication radio network was causing false trouble signals. The facility did not follow its fire watch policy correctly, performing 30-minute intervals instead of the required 15-minute intervals. The fire alarm panel network remains in trouble and may not communicate properly.

Deficiencies (2)
IFC 901.7 (2021) - The facility failed to provide fire watch patrols at 15-minute intervals during fire alarm system trouble, instead performing them every 30 minutes. The fire department and fire code official were not properly notified as required.
IFC 907.8 (2021) - The fire alarm panel network is in trouble status and may not be communicating with the fire alarm panel properly, indicating a system deficiency.
Report Facts
Complaint number: 189610 Next inspection scheduled: Sep 18, 2025

Inspection Report — Jul 7, 2025

Re-Inspection
Date: Jul 7, 2025

Visit Reason
An unannounced Fire and Life Safety Code re-inspection was conducted on 07/07/2025 at White River Assisted Living to determine compliance with applicable codes following a requested extension.

Findings
Multiple deficiencies were cited during the re-inspection, including issues with fire doors, sprinkler system documentation, and inspection frequency. Some violations were corrected on site, but others remained open as of the inspection date.

Deficiencies (9)
IFC 310.7 2021 - Lighted matches, cigarettes, cigars, or other burning objects shall not be discarded in a manner that could cause ignition of combustible material.
IFC 606.3.3.3 2021 - Records for inspections and cleanings shall be completed and maintained after each inspection or cleaning.
IFC 701.6 2018 WAC 51-54A - The owner shall maintain an inventory of all required fire-resistance-rated construction and ensure proper inspection and repair.
IFC 705.2 2021 - Opening protectives in fire-resistance-rated assemblies shall be inspected and maintained in accordance with NFPA 80 and NFPA 105; fire doors and smoke and draft control doors shall not be blocked or obstructed.
IFC 903.5 2021 - Sprinkler systems shall be tested and maintained in accordance with Section 901.
IFC 904.13.5.2 2021 - Automatic fire-extinguishing systems shall be serviced at least every six months and after activation, with inspection certificates forwarded to the fire code official.
IFC 907.8 2021 - Fire alarm and detection systems shall be maintained with records of inspection, testing, and maintenance.
IFC 907.8.3 2021 - Smoke detector sensitivity shall be checked within one year after installation and every alternate year thereafter, with calibration tests performed as required.
NFPA Standard 10 Section 6.2.1 - Fire extinguishers shall be inspected initially and at approximately 30-day intervals, manually or electronically monitored as needed.
Report Facts
Next inspection scheduled: Aug 6, 2025

Inspection Report — Apr 24, 2025

Complaint Investigation
Date: Apr 24, 2025

Visit Reason
The inspection was conducted in response to a complaint regarding the sprinkler system at White River Assisted Living.

Complaint Details
Complaint #176215 involved a sprinkler system issue caused by an elevator technician cutting the water line. The fire department responded to the fire alarm panel activation. No IFC violations were found, indicating the complaint was unsubstantiated.
Findings
The elevator technician accidentally cut the water line to the east portion of the community, causing a water shutoff for about 4 hours. The facility was on fire watch every 30 minutes until repairs and fire panel reset were completed. No fire code violations were observed.

Report Facts
Duration of water shutoff: 4 Fire watch frequency: 30

Inspection Report — Aug 21, 2024

Life Safety
Date: Aug 21, 2024

Visit Reason
The Office of the State Fire Marshal conducted a fire and life safety inspection at Living Court Assisted Living Community to determine compliance with applicable codes.

Findings
All violations noted during previous related inspections have been corrected. The current inspection found no outstanding violations and the facility was approved.

Deficiencies (3)
IFC 705.2.4 2021 - Swinging fire doors shall close from the full-open position and latch automatically.
IFC 706.1 2018 - Dampers protecting ducts and air transfer openings shall be inspected and maintained; damaged products shall be repaired or replaced. The facility's fire damper report showed one damper failed and documentation was not provided showing correction.
IFC 903.5 2009, 2012, 2015, 2018 - Sprinkler systems shall be tested and maintained in accordance with Section 901. The facility was unable to provide documentation for quarterly sprinkler reports and forward flow test.