Inspection Report — Jul 23, 2024
Routine
Date: Jul 23, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
2 state licensure deficiencies related to fire safety: missing/expired annual fire alarm inspection/certification and inadequate hazardous-area separation due to a non-self-closing sliding mechanical room door.
Deficiencies (2)
19 CSR 30-86.022(9)(D) Fire Alarm System Inspections/Certifications: Based on record review and interview during the fire safety inspection process, the facility failed to have annual inspections and written certification of the complete fire alarm system; the last certification was noted as February 2023 and staff were unable to produce a current report.
19 CSR 30-86.022(10)(A) Hazardous Area Requirements Protection from Hazards: Based on observation and interview during the fire safety inspection process, the sprinklered facility failed to provide required separation of a hazardous mechanical room from the resident corridor with self-closing, smoke-resistant doors; the door observed was a sliding wood door less than 1-3/4 inches thick, not self-closing and had gaps.