Inspection Reports for
Canton Nursing Center
321 HOSPITAL ROAD, CANTON, GA, 30114
Back to Facility Profile6 Reports
Inspection Report — Apr 5, 2021
Date: Apr 5, 2021
Visit Reason
The document is a statement of deficiencies and plan of correction for Canton Nursing Center following a survey completed on April 5, 2021.
Findings
The report contains initial comments and a summary statement of deficiencies, but no specific deficiencies or findings are detailed in the provided page.
Inspection Report — Feb 3, 2021
Abbreviated Survey
Date: Feb 3, 2021
Visit Reason
A COVID-19 Focused Infection Control Survey was conducted in conjunction with an Abbreviated/Partial Extended Survey investigating complaint number GA00210577.
Complaint Details
Complaint number GA00210577 was substantiated, but no State Licensure deficiencies were cited.
Findings
The facility was found to be in compliance with infection control regulations and CMS/CDC recommended practices for COVID-19. The complaint was substantiated; however, no State Licensure deficiencies were cited.
Inspection Report — Nov 17, 2020
Abbreviated Survey
Date: Nov 17, 2020
Visit Reason
An Abbreviated/Partial Extended Survey was conducted to investigate multiple complaints against the facility.
Complaint Details
Complaints #GA00206034 and #GA00205997 were substantiated with no regulatory violations. Complaints #GA00205424, #GA00205227, #GA00204962, and #GA00202772 were unsubstantiated with no regulatory violations.
Findings
Complaints #GA00206034 and #GA00205997 were substantiated with no regulatory violations, while complaints #GA00205424, #GA00205227, #GA00204962, and #GA00202772 were unsubstantiated with no regulatory violations.
Inspection Report — Dec 20, 2018
Routine
Date: Dec 20, 2018
Visit Reason
The inspection was conducted as a routine survey of Canton Nursing Center to assess compliance with dietary service regulations, nutritional adequacy, medical record maintenance, and physical plant standards including kitchen sanitation and food service.
Findings
The facility was found deficient in multiple areas including failure to serve pureed diets as prescribed, significant unaddressed weight loss in a resident, incomplete nutritional assessments, missing audiology consults in medical records, and kitchen sanitation issues such as lack of hot water at handwashing sink, unlabeled food containers, improper storage, and broken/missing thermometers.
Deficiencies (6)
Resident #83 was served pureed foods that were too thin and runny, and was served regular diet items and straws contrary to physician's orders.
Resident #82 experienced significant weight loss with no documented nutritional assessment or interventions, and was served improperly prepared pureed foods.
Resident #2's audiology consults were not maintained in the medical record and follow-up was not documented.
Kitchen handwashing sink lacked hot water intermittently and paper towel dispenser was initially empty; garbage can lid was difficult to operate.
Bulk food bins were unlabeled or had scoops stored improperly; bananas stored on floor; unlabeled nutritional supplement cartons; broken or missing thermometers in refrigerators.
Frozen chicken thawed in water at 79.5°F, exceeding recommended temperature.
Report Facts
Weight loss percentage: 5
Temperature: 79.5
Temperature: 10
Temperature: 43
Employees mentioned
| Name | Title | Context |
|---|---|---|
| CC | Licensed Practical Nurse (LPN) | Notified about resident #83 being served wrong diet consistency. |
| DD | Certified Nurse Assistant (CNA) | Interviewed regarding resident #83 and #82 feeding and eating assistance. |
| EE | Licensed Practical Nurse (LPN) | Interviewed regarding resident #83 choking or coughing incidents. |
| BB | Cook | Observed preparing pureed foods in kitchen. |
| FSM | Food Service Manager | Provided information on dietary services, kitchen sanitation, and nutritional assessments. |
| ADON | Assistant Director of Nursing | Interviewed about dietary orders, audiology consults, and nursing follow-up. |
| DON | Director of Nursing | Verified resident diet orders and discussed weight monitoring. |
| SSD | Social Services Director | Responsible for setting up audiology appointments for resident #2. |
| AA | Dietary Aide | Observed washing hands in kitchen. |
| Plant Manager | Repaired kitchen handwashing sink faucet to restore hot water. |
Inspection Report — Nov 9, 2017
Routine
Date: Nov 9, 2017
Visit Reason
State of GA Healthcare Facility Regulation Division inspection of Canton Nursing Center.
Findings
The facility was cited on federal tags F0156, F0160 and F0279 and on state tag N1018. Findings included failure to provide the Advance Beneficiary Notice of Noncoverage to seven residents discharged off Medicare Part A, failure to convey resident trust fund balances within 30 days of death for four residents, and failure to develop an individualized dental care plan for Resident #39.
Deficiencies (1)
N 1018 - Medical, Dental and Nursing Care: the facility failed to develop an individualized care plan related to dental care for Resident #39 who had missing and broken teeth.
Inspection Report — Jan 19, 2017
Complaint Investigation
Date: Jan 19, 2017
Visit Reason
Complaint investigation of the nursing home.
Complaint Details
Complaint GA00163721 was investigated.
Findings
The facility was cited for two state rule violations for nonfunctioning patio doorbells that prevented reentry and for failure to perform background and reference checks for employees.
Deficiencies (2)
N 1300 - Safety: the facility failed to ensure the doorbells for both patios were functioning, resulting in residents and visitors being unable to reenter the facility (census 83).
N 2600 - Background screening: the facility failed to conduct background and reference checks prior to employment for staff, including no background/reference check for the Nursing Home Administrator and lack of reference checks for sampled employees.
22 CMS Surveys
Inspection Report — Apr 7, 2021
Complaint Investigation
Date: Apr 7, 2021
Visit Reason
An Abbreviated/Partial Extended Survey investigating complaint #GA00213260 was initiated and concluded on 04/07/2021.
Complaint Details
Complaint #GA00213260 was substantiated with no deficiencies cited.
Findings
Complaint #GA00213260 was substantiated with no deficiencies cited.
Inspection Report — Apr 5, 2021
Follow-Up
Date: Apr 5, 2021
Visit Reason
A revisit survey was conducted to verify correction of deficiencies cited on 02/03/2021.
Findings
All deficiencies cited as a result of the 02/03/2021 survey were found to be corrected as of 03/20/2021.
Report Facts
:
Inspection Report — Feb 3, 2021
Routine
Date: Feb 3, 2021
Visit Reason
Abbreviated/Partial Extended Survey conducted in conjunction with a COVID-19 Focused Infection Control Survey, including an investigation of complaint GA00210577.
Complaint Details
Complaint GA00210577 was substantiated with the following deficiency cited.
Findings
The complaint (GA00210577) was substantiated and the facility was cited for one deficiency for failing to protect one resident (R#1) from physical abuse.
Deficiencies (1)
F 0600 - Free from Abuse and Neglect: based on resident and staff interviews and record review the facility failed to protect one of three sampled residents (R#1) from physical abuse when CNA AA allegedly yanked a call light from R#1's hand causing injury to R#1's right fifth finger; CNA AA was suspended pending investigation and was terminated.
Inspection Report — Oct 21, 2020
Complaint Investigation
Date: Oct 21, 2020
Visit Reason
An Abbreviated/Partial Extended Survey investigating GA00208717 was initiated in conjunction with an Infection Control Survey.
Complaint Details
Complaint GA00208717 was substantiated with no deficiencies cited.
Findings
Complaint GA00208717 was substantiated with no deficiencies cited.
Inspection Report — Jul 7, 2020
Life Safety
Date: Jul 7, 2020
Visit Reason
A COVID-19 Focused Emergency Preparedness and Infection Control Survey.
Findings
The facility was found to be in compliance with 42 CFR §483.73 (emergency preparedness) and 42 CFR §483.80 (infection control) related to COVID-19. Total census 66.
Inspection Report — Feb 11, 2019
Follow-Up
Date: Feb 11, 2019
Visit Reason
A revisit survey was conducted to determine if deficiencies cited during the December 20, 2018 recertification survey had been corrected.
Findings
All deficiencies cited during the December 20, 2018 recertification survey were found to be corrected as of 2019-02-03.
Inspection Report — Feb 4, 2019
Follow-Up
Date: Feb 4, 2019
Visit Reason
Follow-up survey to verify that previously cited deficiencies were corrected.
Findings
A follow-up survey on 2019-02-04 found that all previously cited survey tags had been corrected.
Inspection Report — Dec 20, 2018
Annual Inspection
Date: Dec 20, 2018
Visit Reason
Standard survey conducted December 17–20, 2018 to assess compliance with Medicare/Medicaid requirements.
Findings
The facility was cited for four deficiencies involving nutrition and hydration assessment/weight monitoring, failure to serve therapeutic diets as prescribed, unsanitary food storage and preparation practices in the kitchen, and missing audiology consults in a resident's medical record.
Deficiencies (4)
F 0692 - Nutrition/Hydration Status: one resident (R#82) experienced a significant 5% weight loss from 150 to 142.5 pounds between 11/27/18 and 12/5/18 and was not reweighed or assessed, there were no nutritional assessments or progress notes and a low albumin (2.5) was not addressed with interventions.
F 0808 - Therapeutic Diet Prescribed by Physician: two residents (R#82 and R#83) of three reviewed were served foods inconsistent with physician orders or therapeutic menu extensions, including pureed foods that were too thin/runny, wrong portions, use of straws despite 'no straws' orders, and one instance of a regular diet served instead of pureed.
F 0812 - Food Procurement,Store/Prepare/Serve-Sanitary: the kitchen was not maintained or sanitary, creating potential for foodborne illness for all 85 residents, with findings including lack of paper towels at the handwashing sink, unlabeled bulk bins, food stored on the floor, undated thawed nutritional shakes, broken/missing thermometers, thawing chicken in 79.5°F water, and intermittent lack of hot water.
F 0842 - Resident Records - Identifiable Information: one resident (R#2) had audiology consults from 5/25/18, 6/4/18 and 7/9/18 that were not on file and the facility was unable to obtain or have the consults faxed/scanned into the medical record prior to survey exit.
Inspection Report — Dec 17, 2018
Life Safety
Date: Dec 17, 2018
Visit Reason
During a Life Safety Code Survey conducted on 12/17/2018, Canton Nursing was found not in substantial compliance with the requirements for participation in Medicare/Medicaid at 42 CFR Subpart 483.70(a), Life Safety from Fire, and the related National Fire Protection Association (NFPA) standard NFPA 101 Life Safety Code 2012 edition.
Findings
The facility was cited for multiple Life Safety Code deficiencies including missing fire alarm strobes in public restrooms and improperly installed pull stations, missing sensitivity testing for smoke devices, inadequate sprinkler coverage and missing sprinkler components, non-smoke-tight or non-latching doors, unsealed penetrations with flammable foam, combustible crepe paper decorations in the activity room, improper cigarette containers in smoking areas, and lack of an annual rated door inspection.
Deficiencies (10)
K 0341 - NFPA 101 Fire Alarm System - Installation: the Men and Women's public restrooms did not have fire alarm strobes and multiple fire alarm pull stations were installed at 54 in. to pull handle from finished floor (not the code-specified 42-48 in.).
K 0345 - NFPA 101 Fire Alarm System - Testing and Maintenance: the facility did not have a copy of a sensitivity test/inspection for the smoke devices.
K 0351 - NFPA 101 Sprinkler System - Installation: the basement stair well exit area and elevator equipment room did not have proper fire sprinkler coverage.
K 0352 - NFPA 101 Sprinkler System - Supervisory Signals: the facility did not have electronic tamper devices on the back-flow preventer.
K 0353 - NFPA 101 Sprinkler System - Maintenance and Testing: fire sprinkler trim rings were missing throughout the facility.
K 0363 - NFPA 101 Corridor - Doors: the door in patient room 306 was not smoke tight, the door in patient room 206 was not smoke tight and did not latch, and the entry door to the basement stair well was not latching causing a lack of a smoke resistant seal.
K 0372 - NFPA 101 Subdivision of Building Spaces - Smoke Barrier: penetrations in the basement stair well area and attic fire-rated walls were not sealed properly and flammable spray foam was used to seal a penetration in the washer room ceiling.
K 0741 - NFPA 101 Smoking Regulations: plastic cigarette containers were observed at the facility entrance and in designated smoking areas instead of required metal containers and these areas lacked metal ash trays and fire extinguishers.
K 0753 - NFPA 101 Combustible Decorations: the activity room was decorated with flammable crepe paper.
K 0761 - NFPA 101 Maintenance, Inspection & Testing - Doors: the facility did not have a copy of the annual rated door inspection conducted by a competent/designated individual.
Inspection Report — Oct 24, 2018
Complaint Investigation
Date: Oct 24, 2018
Visit Reason
Abbreviated/Partial Extended Survey investigating complaint GA00190500.
Complaint Details
Complaint GA00190500 was unsubstantiated.
Findings
The abbreviated/partial extended survey investigated complaint GA00190500 and found the complaint unsubstantiated; no deficiencies were cited.
Inspection Report — Jul 10, 2018
Complaint Investigation
Date: Jul 10, 2018
Visit Reason
A complaint survey was conducted on 7/9/2018 - 7/10/2018 to investigate complaints GA00189658, GA00189813, GA00189190.
Complaint Details
Complaints GA00189658, GA00189813, GA00189190 were investigated; no deficiencies were cited.
Findings
The complaint survey investigated the listed complaints and no deficiencies were cited.
Inspection Report — May 31, 2018
Complaint Investigation
Date: May 31, 2018
Visit Reason
Complaint survey to investigate complaint GA00188537 and determine compliance with Federal and State long term care requirements.
Complaint Details
Complaint GA00188537 was investigated and no deficiencies were cited.
Findings
A complaint survey conducted on 2018-05-31 to investigate complaint GA00188537 found no deficiencies were cited.
Inspection Report — Jan 4, 2018
Follow-Up
Date: Jan 4, 2018
Visit Reason
Follow up to the Recertification survey of November 9, 2017.
Findings
A follow up to the Recertification survey of November 9, 2017 was conducted on January 4, 2018 and revealed that all deficiencies had been corrected.
Inspection Report — Jan 2, 2018
Follow-Up
Date: Jan 2, 2018
Visit Reason
Follow-Up Survey conducted by the FSCO to determine whether previously cited deficiencies had been corrected.
Findings
A follow-up survey on 2018-01-02 found that all previously cited survey tags had been corrected.
Inspection Report — Nov 9, 2017
Routine
Date: Nov 9, 2017
Visit Reason
State of GA Healthcare Facility Regulation Division inspection of Canton Nursing Center.
Findings
The facility was cited on federal tags F0156, F0160 and F0279 and on state tag N1018. Findings included failure to provide the Advance Beneficiary Notice of Noncoverage to seven residents discharged off Medicare Part A, failure to convey resident trust fund balances within 30 days of death for four residents, and failure to develop an individualized dental care plan for Resident #39.
Deficiencies (3)
F 0156 - Notice of Medicare noncoverage (ABN): the facility failed to provide the Advance Beneficiary Notice of Noncoverage to seven residents reviewed (#4, #18, #49, #156, #95, #137, #87) who were discharged off Medicare Part A services and remained in the facility.
F 0160 - Conveyance of personal funds upon death: the facility failed to convey the ending trust fund balances within 30 days of death for residents #47, #72, #185, and #186.
F 0279 - Comprehensive care plans: the facility failed to develop an individualized dental care plan for Resident #39 who had missing and broken teeth.
Inspection Report — Nov 7, 2017
Life Safety
Date: Nov 7, 2017
Visit Reason
Life Safety Code survey conducted on 2017-11-07 to determine compliance with NFPA 101 Life Safety Code 2012 edition and 42 CFR Subpart 483.70(a).
Findings
The facility was found not in substantial compliance and cited for 4 Life Safety Code violations involving fire alarm pull station placement, unapproved gas line to cooking equipment, lack of emergency lighting in a medication prep room, and use of unapproved multi-tab power strips.
Deficiencies (4)
K 0341 - Fire Alarm System - Installation: fire alarm pull station locations exceed the maximum distance on 300 and 200 halls; no pull stations were located on 200 or 300 hall and all pull stations were located at exit doors on 100 Hall and 400 Hall.
K 0511 - Utilities - Gas and Electric: unapproved gas line connecting cooking equipment to the structure gas lines with a yellow corrugated non-protected gas line and coupling being used.
K 0911 - Electrical Systems - Other: medication prep room had no emergency lighting provided.
K 0920 - Electrical Equipment - Power Cords and Extension Cords: unapproved multi-tab plugs were being used in resident treatment areas and residence rooms with medical equipment plugged into them, observed in rooms on all four halls.
Inspection Report — May 2, 2017
Complaint Investigation
Date: May 2, 2017
Visit Reason
Complaint Survey conducted to investigate complaint #GA00174410.
Complaint Details
Complaint GA00174410 was investigated and no deficiencies were cited.
Findings
The complaint survey to investigate complaint #GA00174410 on 2017-05-02 found no deficiencies were cited.
Inspection Report — Mar 17, 2017
Complaint Investigation
Date: Mar 17, 2017
Visit Reason
Complaint survey to investigate complaint GA00172162 to determine compliance with Federal and State Long Term Care regulations.
Complaint Details
Complaint GA00172162: no deficiencies were cited.
Findings
The complaint survey conducted on 2017-03-17 found no deficiencies were cited.
Inspection Report — Mar 7, 2017
Follow-Up
Date: Mar 7, 2017
Visit Reason
A revisit was conducted to the standard survey of January 19, 2017 to determine compliance with the Plan of Correction.
Findings
The March 6, 2017 revisit verified the facility was in compliance with Federal and State long term care requirements as alleged in the Plan of Correction dated March 5, 2017; all deficiencies cited in the January 19, 2017 survey were found to be corrected.
Inspection Report — Mar 6, 2017
Follow-Up
Date: Mar 6, 2017
Visit Reason
Follow-up survey conducted by the FSCO to verify correction of previously cited survey tags.
Findings
All previously cited survey tags were found to be corrected during the follow-up survey conducted on 2017-03-06.
Inspection Report — Jan 19, 2017
Complaint Investigation
Date: Jan 19, 2017
Visit Reason
Complaint investigation of the nursing home.
Complaint Details
Complaint GA00163721 was investigated.
Findings
The facility was cited for two state rule violations for nonfunctioning patio doorbells that prevented reentry and for failure to perform background and reference checks for employees.
Deficiencies (3)
F 0278 - Assessment accuracy: the facility failed to accurately assess Resident #120's dental status (one of 28 sampled residents) on the Significant Change MDS.
F 0371 - Food procure/store/prepare sanitary: staff failed to label and date food items and failed to discard expired foods in the dry storage pantry, walk-in freezer, and a resident snack refrigerator, potentially affecting 82 of 83 residents.
F 0456 - Essential equipment/doorbells: doorbells for both facility patios were not functioning properly, preventing reentry into the patios by residents and visitors (census 83).
Inspection Report — Jan 17, 2017
Life Safety
Date: Jan 17, 2017
Visit Reason
Life Safety Code Survey conducted on 01/17/2017 to determine compliance with Medicare/Medicaid requirements and NFPA 101 Life Safety Code.
Findings
The facility was cited for two Life Safety deficiencies: improperly installed smoke detectors (installed in HVAC airstream) and violations of smoking regulations (smoking debris and combustible material in designated smoking areas).
Deficiencies (2)
K 0342 - NFPA 101 Fire Alarm System - Initiation: two smoke detectors were installed in the direct airstream of the facility's HVAC supply registers, one in the 400 corridor near room #401 and the other in the 200 corridor near the therapy room, and were not installed properly.
K 0741 - NFPA 101 Smoking Regulations: observation revealed smoking debris in the combustible general trash receptacle and combustible debris in the ashtray container in the facility's designated smoking areas.
Viewing