Inspection Report — Apr 17, 2025

Routine
Date: Apr 17, 2025

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Six federal health deficiencies addressing comprehensive care planning, discharge summaries/recapitulation of stay, RN staffing/Director of Nursing hours, infection prevention and control (including TB and water management), antibiotic stewardship, and influenza/pneumococcal immunizations; plus two Missouri state licensure deficiencies related to RN/LPN staffing patterns and infection control/communicable disease.

Deficiencies (2)
19 CSR 30-85.042(35)(B) SNF RN-Day Shift, LPN/RN eve/nights Licensed Nursing Requirements; Skilled Nursing Facility: Refer to F727.
19 CSR 30-85.042(77) Infection Control/Communicable Disease: Infection Control/Communicable Disease: Refer to F880, F881, and F883.
Report Facts
residents sampled: 15 closed records reviewed: 1

Inspection Report — Aug 28, 2023

Life Safety
Date: Aug 28, 2023

Visit Reason
CMS-2567 federal health and Life Safety survey and Missouri Department of Health and Senior Services State Form; Life Safety Code deficiencies (K-tags) and an Emergency Preparedness deficiency (E-tag) were cited. The survey type is not otherwise stated.

Findings
Fifteen deficiencies were cited: eight federal (CMS-2567) deficiencies involving life safety and emergency preparedness and seven Missouri state licensure deficiencies. Main topics include hazardous area enclosures and self-closing doors, range hood operation, fire alarm testing and maintenance, sprinkler system inspection, corridor and smoke barrier doors/placards, smoking area ashtray disposal, and substantial construction/maintenance issues.

Deficiencies (7)
19 CSR 30-85.022(4) Hazardous Areas: Refer to K321.
19 CSR 30-85.022(9) Range Hood Certification: Refer to K324.
19 CSR 30-85.022(10)(B) Fire Alarm System-Test/Maintain: Refer to K345.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Refer to K353.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Refer to K374.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Refer to K741.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Refer to K363.
Report Facts
residents potentially affected: 16 residents potentially affected: 34 residents potentially affected: 38

Inspection Report — Jul 19, 2022

Complaint Investigation
Date: Jul 19, 2022

Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form; complaint investigation MO#202275.

Complaint Details
MO#202275; substantiation not stated in the document.
Findings
Two deficiencies were cited addressing failure to identify and treat a resident's pressure ulcer and the related state rule for pressure sore prevention/treatment (one federal health deficiency and one Missouri state licensure deficiency, Class II).

Deficiencies (1)
19 CSR 30-85.042(74) Pressure Sore Prevention/Treatment: Refer to F 686.
Report Facts
provider_supplier_clia_identification_number: 265535

Inspection Report — Jan 16, 2020

Routine
Date: Jan 16, 2020

Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form; the survey type is not stated.

Findings
Five federal deficiencies were cited involving environment/housekeeping and maintenance, failure to complete significant change assessments (SCSA), baseline and comprehensive care planning, and medication/clinical standards. Five Missouri state deficiencies were cited regarding handrails, floor and wall surfaces, and nursing care per resident condition, each referring to the corresponding federal findings.

Deficiencies (5)
19 CSR 30-85.012(67) Handrails: Please refer to F584.
19 CSR 30-85.012(84) Floor Surfaces: Please refer to F584.
19 CSR 30-85.042(67) Nursing Care per Res Condition: Please refer to F658.
19 CSR 30-87.020(12) Floor Surfaces: Please refer to F584.
19 CSR 30-87.020(17) Wall Surfaces Cleanable: Please refer to F584.
Report Facts
residents sampled: 12 residents affected: 3

Inspection Report — Jan 16, 2020

Life Safety
Date: Jan 16, 2020

Visit Reason
Federal Life Safety (CMS-2567) survey and Missouri Department of Health and Senior Services State Form licensure survey; Life Safety Code survey.

Findings
Four deficiencies were cited: two federal Life Safety deficiencies addressing unsealed ceiling penetrations/compromised fire barriers and deficiencies with the kitchen range hood/grease drip and filter arrangement, and two Missouri state licensure deficiencies referring to noncombustible material between floors and range hood certification. No Emergency Preparedness deficiencies were cited.

Deficiencies (2)
19 CSR 30-85.022(3) Noncombustible Material Between Floors: Class II* Refer to K161.
19 CSR 30-85.022(9) Range Hood Certification: Class II* Refer to K324.
Report Facts
residents potentially affected: 17

Inspection Report — Apr 24, 2019

Routine
Date: Apr 24, 2019

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Eleven deficiencies were cited: six federal health deficiencies addressing resident self-determination/wake times, environmental cleanliness (ventilation/vents), comprehensive care planning and nutrition/weight loss, pressure ulcer prevention/treatment, medication administration/insulin practices, and immunizations; and five state licensure deficiencies addressing medication system, pressure sore prevention/treatment, infection control, air duct maintenance, and resident personal lives/meal schedules.

Deficiencies (5)
19 CSR 30-85.042(47) Safe/Effective Medication System: Refer to F760.
19 CSR 30-85.042(75) Pressure Sore Prevention/Treatment: Refer to F686.
19 CSR 30-85.042(78) Infection Control/Communicable Disease: Refer to F883.
19 CSR 30-87.020(9) Air Ducts-Maintain: Refer to F584.
19 CSR 30-88.010(41) Resident Lives Not Regulated/Controlled: Refer to F561.
Report Facts
residents sampled: 12

Inspection Report — Apr 24, 2019

Life Safety
Date: Apr 24, 2019

Visit Reason
Federal Life Safety (CMS-2567 K-tag) survey and Missouri Department of Health and Senior Services State Form; the survey is a Life Safety Code survey.

Findings
Eight deficiencies were cited: four federal Life Safety deficiencies addressing building construction/ceiling penetrations, emergency lighting, hazardous-area doors, and smoke barriers, and four Missouri state deficiencies addressing noncombustible material between floors, hazardous areas, emergency lighting, and smoke section walls/doors.

Deficiencies (4)
19 CSR 30-85.022(3) Noncombustible Material Between Floors: The facility failed to maintain the barrier between the first floor and the attic space with a fire resistance rating of at least one hour and left multiple unsealed openings and missing ceiling tiles.
19 CSR 30-85.022(4) Hazardous Areas: The facility failed to ensure hazardous areas were separated by required construction and failed to ensure a door to a hazardous area was self-closing or automatic closing.
19 CSR 30-85.022(25) Emergency Lighting: The facility failed to provide emergency lighting of sufficient intensity for safety in the medication area and failed to document required annual testing of battery-operated emergency lighting.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: The facility failed to ensure smoke sections/walls and doors were continuous and sealed in attic spaces, with observed unsealed penetrations and inappropriate sealant.
Report Facts
residents potentially affected: 36 residents potentially affected: 17

Inspection Report — Jan 9, 2018

Life Safety
Date: Jan 9, 2018

Visit Reason
Federal CMS-2567 Life Safety Code survey (K-tag deficiencies) accompanied by Missouri Department of Health and Senior Services State Form pages; the survey is a Life Safety Code inspection.

Findings
Eight deficiencies were cited: three federal life-safety deficiencies for hazardous areas, smoke barrier construction, and electrical/power strip use, and five Missouri State Form deficiencies addressing night-lights, hazardous areas, smoke section walls/doors, fire drill/simulated evacuation, and electrical wiring/equipment maintenance.

Deficiencies (5)
19 CSR 30-85.012(125) Night-lights-Required Locations: Based on observation and interview, the facility failed to ensure resident rooms had functioning night-lights, with multiple occupied resident rooms noted to have nonfunctional night lights.
19 CSR 30-85.022(4) Hazardous Areas: Refer to K321.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Refer to K372.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Based on record review and interview, the facility failed to ensure an annual simulated resident evacuation involving the local fire department was completed; this deficient practice affected all occupants in four of four smoke compartments.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Refer to K920.
Report Facts
residents potentially affected: 15 residents potentially affected: 6 residents potentially affected: 26

Inspection Report — Jan 9, 2018

Routine
Date: Jan 9, 2018

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is routine.

Findings
Four deficiencies were cited: two federal health deficiencies involving inadequate catheter care/UTI prevention and infection control including blood glucose monitoring and medication administration practices, and two Missouri state licensure deficiencies (19 CSR) referencing those federal findings.

Deficiencies (2)
19 CSR 30-85.042(67) Nursing Care per Res Condition: Refer to F690.
19 CSR 30-85.042(78) Infection Control/Communicable Disease: Refer to F880.
Report Facts
residents sampled: 12 residents with indwelling catheters: 5

12 CMS Surveys

Inspection Report — Apr 17, 2025

Routine
Date: Apr 17, 2025

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Six federal health deficiencies addressing comprehensive care planning, discharge summaries/recapitulation of stay, RN staffing/Director of Nursing hours, infection prevention and control (including TB and water management), antibiotic stewardship, and influenza/pneumococcal immunizations; plus two Missouri state licensure deficiencies related to RN/LPN staffing patterns and infection control/communicable disease.

Deficiencies (6)
F656 Develop/Implement Comprehensive Care Plan: The facility failed to develop comprehensive, person-centered care plans with measurable goals and interventions for residents, as evidenced by deficiencies in the plans of two residents during record review and interviews.
F661 Discharge Summary: The facility failed to complete a comprehensive discharge summary and recapitulation of stay for a discharged resident in a review of one closed record.
F727 RN 8 Hrs/7 days/Wk, Full Time DON: The facility failed to provide a registered nurse for at least eight consecutive hours a day, seven days a week, and the Director of Nursing was the only full-time RN, leaving days without RN coverage.
F880 Infection Prevention & Control: The facility failed to maintain required infection prevention and control documentation and processes, including incomplete TB screening/two-step testing and gaps in the water management program and monitoring of water temperatures.
F881 Antibiotic Stewardship Program: The facility failed to fully implement its antibiotic stewardship policy, including timely reporting and tracking of infections and incomplete antibiotic monitoring/documentation for residents.
F883 Influenza and Pneumococcal Immunizations: The facility failed to provide pneumococcal vaccinations or documentation consistent with CDC guidelines for several residents reviewed and did not ensure immunization records/consents were complete.
Report Facts
residents sampled: 15 closed records reviewed: 1

Inspection Report — Aug 28, 2023

Life Safety
Date: Aug 28, 2023

Visit Reason
CMS-2567 federal health and Life Safety survey and Missouri Department of Health and Senior Services State Form; Life Safety Code deficiencies (K-tags) and an Emergency Preparedness deficiency (E-tag) were cited. The survey type is not otherwise stated.

Findings
Fifteen deficiencies were cited: eight federal (CMS-2567) deficiencies involving life safety and emergency preparedness and seven Missouri state licensure deficiencies. Main topics include hazardous area enclosures and self-closing doors, range hood operation, fire alarm testing and maintenance, sprinkler system inspection, corridor and smoke barrier doors/placards, smoking area ashtray disposal, and substantial construction/maintenance issues.

Deficiencies (8)
E020 Policies for Evac. and Primary/Alt. Comm.: Based on interview and record review, the facility failed to develop a policy and procedure which addressed the facility's response to a resident who refused to leave the facility in the event of an emergency evacuation.
K321 Hazardous Areas - Enclosure: Based on observation and interview, the facility failed to ensure the door to a combustible storage room larger than 50 square feet was self-closing to separate the area from other spaces in the facility; the practice had the potential to affect residents.
K324 Cooking Facilities: Based on observation, interview, and record review, the facility failed to ensure proper operation of the range hood by allowing gaps between the baffle filters.
K345 Fire Alarm System - Testing and Maintenance: Based on record review and interview, the facility failed to ensure a deficiency identified on the annual fire alarm system inspection was addressed, which could result in improper operation or equipment failure in an emergency.
K353 Sprinkler System - Maintenance and Testing: Based on observation, interview, and record review, the facility failed to maintain the sprinkler system in accordance with NFPA 25 by not ensuring the five-year internal pipe inspection of the facility's sprinkler system was completed.
K363 Corridor - Doors: Based on observation and interview, the facility failed to maintain corridor doors to resist the passage of smoke and to ensure corridor doors were positive-latching, with multiple corridor door deficiencies observed.
K374 Subdivision of Building Spaces - Smoke Barrie: Based on observation, interview, and record review, the facility failed to maintain smoke barrier doors and associated features to resist the passage of smoke, including missing placards to indicate fire-resistance ratings.
K741 Smoking Regulations: Based on observation, interview, and record review, the facility failed to ensure smoking areas were equipped with self-closing containers for disposal of smoking materials; ashtrays and cigarette debris were observed in outside areas.
Report Facts
residents potentially affected: 16 residents potentially affected: 34 residents potentially affected: 38

Inspection Report — Aug 23, 2023

Annual Inspection
Date: Aug 23, 2023

Visit Reason
Federal health survey (CMS-2567) recertification survey.

Findings
Five federal health survey deficiencies were cited covering comprehensive assessments after significant change, care plan timing and revision, quality of care related to wound assessment and documentation, bed rail assessments and consent, and failure to perform regular inspections of beds/bed rails.

Deficiencies (5)
F637 Comprehensive Assessment After Significant Chg: The facility failed to complete a significant change Minimum Data Set (MDS) assessment as required for 2 of 19 sampled residents (Resident #26 and Resident #8); significant change assessments were not completed when residents had declines or were admitted to hospice.
F657 Care Plan Timing and Revision: The facility failed to revise a resident's (Resident #24) care plan appropriately when the resident's diet status changed and omitted removal of care plan portions no longer pertinent.
F684 Quality of Care: The facility failed to assess and document an open wound for 1 of 13 sampled residents after hospice staff identified superficial areas to the resident's buttocks, and wound assessments lacked description of size, color, and drainage and weekly documentation.
F700 Bedrails: The facility failed to perform assessments and obtain consents for bed rails for residents who used bed rails and the issue affected numerous residents; bed rail processes and documentation were not completed as required.
F909 Resident Bed: The facility failed to conduct regular inspections of all bed frames, mattresses, and bed rails as part of a maintenance program, resulting in missing inspections for 36 of 59 beds with bed rails and lack of maintenance logs.
Report Facts
sampled residents: 19 residents affected with bed rails: 27 beds with missing inspections: 36

Inspection Report — Jul 19, 2022

Complaint Investigation
Date: Jul 19, 2022

Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form; complaint investigation MO#202275.

Complaint Details
MO#202275; substantiation not stated in the document.
Findings
Two deficiencies were cited addressing failure to identify and treat a resident's pressure ulcer and the related state rule for pressure sore prevention/treatment (one federal health deficiency and one Missouri state licensure deficiency, Class II).

Deficiencies (1)
F686 Treatment/Svcs to Prevent/Heal Pressure Ulcer: Based on interview and record review the facility failed to identify and provide treatment and monitoring for a resident's pressure ulcer, resulting in an open, draining left ischial wound and related complications.
Report Facts
provider_supplier_clia_identification_number: 265535

Inspection Report — Jun 3, 2020

Routine
Date: Jun 3, 2020

Visit Reason
CMS-2567 federal health and emergency preparedness survey; a COVID-19 Focused Emergency Preparedness and Infection Control Survey was conducted on June 3, 2020.

Findings
No deficiencies were cited; the facility was found to be in compliance with CMS and CDC recommended practices related to COVID-19.

Inspection Report — Jan 16, 2020

Routine
Date: Jan 16, 2020

Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form; the survey type is not stated.

Findings
Five federal deficiencies were cited involving environment/housekeeping and maintenance, failure to complete significant change assessments (SCSA), baseline and comprehensive care planning, and medication/clinical standards. Five Missouri state deficiencies were cited regarding handrails, floor and wall surfaces, and nursing care per resident condition, each referring to the corresponding federal findings.

Deficiencies (5)
F584 Safe/Clean/Comfortable/Homelike Environment: Based on observation and interview the facility failed to maintain housekeeping and maintenance services, resulting in multiple damaged, scratched, missing or broken fixtures and surfaces in resident rooms, hallways and shower areas.
F637 Comprehensive Assessment After Significant Chg: The facility failed to complete a significant change in status assessment (SCSA) for residents who experienced significant changes as evidenced by record review and observation, including missing SCSAs for identified residents.
F655 Baseline Care Plan: The facility failed to develop and implement baseline care plans consistent with residents' specific conditions and to provide required review/signature or printed copies, as shown in record review for multiple residents.
F656 Develop/Implement Comprehensive Care Plan: The facility failed to develop, implement and revise comprehensive person-centered care plans with measurable objectives and timely updates for residents with changing needs.
F658 Services Provided Meet Professional Standards: The facility failed to follow physician orders and obtain medication timely for a resident, resulting in delays in necessary medication delivery and treatment.
Report Facts
residents sampled: 12 residents affected: 3

Inspection Report — Jan 16, 2020

Life Safety
Date: Jan 16, 2020

Visit Reason
Federal Life Safety (CMS-2567) survey and Missouri Department of Health and Senior Services State Form licensure survey; Life Safety Code survey.

Findings
Four deficiencies were cited: two federal Life Safety deficiencies addressing unsealed ceiling penetrations/compromised fire barriers and deficiencies with the kitchen range hood/grease drip and filter arrangement, and two Missouri state licensure deficiencies referring to noncombustible material between floors and range hood certification. No Emergency Preparedness deficiencies were cited.

Deficiencies (2)
K161 Building Construction Type and Height: Based on observation, interview, and record review, the facility failed to maintain the fire-resistance barrier between the first floor and attic as evidenced by multiple unsealed ceiling penetrations and wiring through ceilings that compromised smoke compartments.
K324 Cooking Facilities: The facility failed to ensure the kitchen range hood was maintained in accordance with NFPA 96, lacking a grease drip tray/metal container and showing gaps between baffle filters that allowed grease drippings and gaps to remain between filters.
Report Facts
residents potentially affected: 17

Inspection Report — Oct 8, 2019

Routine
Date: Oct 8, 2019

Visit Reason
Federal health survey (CMS-2567); the survey type is not stated on the form and is recorded as a routine health survey.

Findings
Two federal health survey deficiencies were cited addressing inadequate discharge planning and failure to provide complete discharge summaries and medication reconciliation for discharged residents.

Deficiencies (2)
F660 Discharge Planning Process: Based on interview and record review, the facility failed to ensure a discharge planning process that addressed residents' discharge goals and needs; review of residents' records showed no overall discharge goals or completed discharge care plans and no referrals to the local contact agency when needed.
F661 Discharge Summary: Based on interview and record review, the facility failed to provide discharge summaries that recapitulated the residents' stay, reconciled medications, and documented a post-discharge plan of care for discharged residents; documentation was absent or incomplete and staff stated they do not provide a recapitulation or reconciliation consistently.
Report Facts
residents' records reviewed: 3

Inspection Report — Apr 24, 2019

Routine
Date: Apr 24, 2019

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Eleven deficiencies were cited: six federal health deficiencies addressing resident self-determination/wake times, environmental cleanliness (ventilation/vents), comprehensive care planning and nutrition/weight loss, pressure ulcer prevention/treatment, medication administration/insulin practices, and immunizations; and five state licensure deficiencies addressing medication system, pressure sore prevention/treatment, infection control, air duct maintenance, and resident personal lives/meal schedules.

Deficiencies (6)
F561 Self-Determination: The facility failed to ensure a system to accommodate resident choice for rising in the morning; staff had a get-up list and were awakening residents early and residents' care plans did not address preferred waking time.
F584 Safe/Clean/Comfortable/Homelike Environment: The facility failed to ensure exhaust ventilation units in resident bathrooms were free of dust and debris; surveyor observed moderate to heavy buildup of dust and debris inside vents in multiple resident bathrooms.
F656 Develop/Implement Comprehensive Care Plan: The facility failed to complete comprehensive care plans to meet the nutritional needs of residents who experienced weight loss; care plans lacked documented interventions for identified residents.
F686 Treatment/Svcs to Prevent/Heal Pressure Ulcer: The facility failed to turn and reposition residents at risk for pressure ulcers according to its pressure ulcer prevention policy, resulting in residents remaining in wheelchairs or without repositioning for extended periods.
F760 Residents are Free of Significant Med Errors: The facility failed to administer insulin according to manufacturer recommendations for residents, including not priming insulin pens prior to administration which had the potential to result in residents not receiving the full dose ordered.
F883 Influenza and Pneumococcal Immunizations: The facility failed to follow policies and procedures for pneumococcal immunization, including documenting vaccine status and offering/reoffering vaccine to eligible residents, and did not document vaccination or offering for several residents.
Report Facts
residents sampled: 12

Inspection Report — Apr 24, 2019

Life Safety
Date: Apr 24, 2019

Visit Reason
Federal Life Safety (CMS-2567 K-tag) survey and Missouri Department of Health and Senior Services State Form; the survey is a Life Safety Code survey.

Findings
Eight deficiencies were cited: four federal Life Safety deficiencies addressing building construction/ceiling penetrations, emergency lighting, hazardous-area doors, and smoke barriers, and four Missouri state deficiencies addressing noncombustible material between floors, hazardous areas, emergency lighting, and smoke section walls/doors.

Deficiencies (4)
K161 Building Construction Type and Height: The facility failed to maintain the barrier between the first floor and the attic space with a one-hour fire resistance rating; multiple unsealed openings and missing ceiling tiles were observed allowing penetrations through the barrier.
K291 Emergency Lighting: The facility failed to provide adequate emergency task lighting inside one medication room and failed to document annual 90-minute testing of emergency battery-operated lights for required areas.
K321 Hazardous Areas - Enclosure: The facility failed to ensure a door to a hazardous area was self-closing or automatic closing and observed a clean laundry room door that would not completely close.
K372 Subdivision of Building Spaces - Smoke Barrier Construction: The facility failed to ensure smoke barriers in attic spaces were continuous and had unsealed penetrations and questionable sealant, allowing passage of wiring through the barrier.
Report Facts
residents potentially affected: 36 residents potentially affected: 17

Inspection Report — Jan 9, 2018

Life Safety
Date: Jan 9, 2018

Visit Reason
Federal CMS-2567 Life Safety Code survey (K-tag deficiencies) accompanied by Missouri Department of Health and Senior Services State Form pages; the survey is a Life Safety Code inspection.

Findings
Eight deficiencies were cited: three federal life-safety deficiencies for hazardous areas, smoke barrier construction, and electrical/power strip use, and five Missouri State Form deficiencies addressing night-lights, hazardous areas, smoke section walls/doors, fire drill/simulated evacuation, and electrical wiring/equipment maintenance.

Deficiencies (3)
K321 Hazardous Areas - Enclosure: Based on observation and interview, the facility failed to ensure the door to a combustible storage room larger than 50 square feet was self-closing, which had the potential to affect approximately 15 residents in one of four smoke compartments.
K372 Subdivision of Building Spaces - Smoke Barrier Construction: Based on observation and interview, the facility failed to ensure smoke barrier walls were complete from floor to roof deck, leaving unsealed penetrations that compromised the smoke barrier and had the potential to affect six residents and others in two of four smoke compartments.
K920 Electrical Equipment - Power Cords and Extens(ion) Cords: Based on observation and interview, the facility failed to prohibit use of power strips and extension cords as substitutes for fixed wiring, with multiple power strips/extension cords observed in resident rooms and the staff break room; this had the potential to affect 26 residents in two of four smoke compartments.
Report Facts
residents potentially affected: 15 residents potentially affected: 6 residents potentially affected: 26

Inspection Report — Jan 9, 2018

Routine
Date: Jan 9, 2018

Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is routine.

Findings
Four deficiencies were cited: two federal health deficiencies involving inadequate catheter care/UTI prevention and infection control including blood glucose monitoring and medication administration practices, and two Missouri state licensure deficiencies (19 CSR) referencing those federal findings.

Deficiencies (2)
F 690 Bowel/Bladder Incontinence, Catheter, UTI: The facility failed to provide appropriate catheter care and UTI prevention practices, including observations of catheter tubing and dignity bags touching the floor, failure to secure tubing during care and transfers, and inadequate catheter handling for Resident #7 and others.
F 880 Infection Prevention & Control: The facility failed to follow professional standards of practice for infection control when providing catheter care, blood glucose monitoring, and medication preparation/administration, including observed failures to clean glucometers between residents, incomplete hand hygiene, and unsafe handling of contaminated supplies.
Report Facts
residents sampled: 12 residents with indwelling catheters: 5