Inspection Reports for
Grandview Healthcare Center
201 GRAND AVE, WASHINGTON, MO, 63090-1209
Back to Facility Profile10 Reports
Inspection Report — Jul 11, 2024
Life Safety
Date: Jul 11, 2024
Visit Reason
CMS-2567 Life Safety Code survey with accompanying Missouri Department of Health and Senior Services State Form licensure survey; the survey is a life safety survey.
Findings
Twenty deficiencies were cited: eleven federal Life Safety (K-tag) deficiencies and nine Missouri State Form deficiencies. Main topics include egress doors and special locking arrangements, hazardous area doors and storage, fire alarm and sprinkler system out-of-service and maintenance deficiencies, smoke barrier penetrations, lint buildup behind dryers (building services), door inspection/testing, emergency generator and electrical system testing, surge protectors/extension cord misuse, and ignition sources near oxygen.
Deficiencies (9)
19 CSR 30-85.022(2)(E) No Fire Hazard: Please refer to K500 and K925.
19 CSR 30-85.022(4) Hazardous Areas: Please refer to K321.
19 CSR 30-85.022(10)(H) Fire Alarm System-Out of Service > than 4hrs Complete Fire Alarm Systems: Please refer to K346.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Please refer to K353.
19 CSR 30-85.022(11)(E) Sprinkler System Out of Service More Than 4hr: Please refer to K354.
19 CSR 30-85.022(16) Door Locks: Please refer to K222.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Please refer to K372.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Please refer to K918.
19 CSR 30-85.032(37) Extension Cords/Duplex Receptacles: Please refer to K920.
Report Facts
smoke zones affected: 4
electric clothes dryers: 3
Inspection Report — Jul 11, 2024
Routine
Date: Jul 11, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Six deficiencies were cited: three federal deficiencies involving resident self-determination, failure to transmit required MDS assessments, and infection prevention related to oxygen tubing and concentrator filters; and three Missouri licensure citations for infection control/communicable disease, clinical records/assessment interventions, and resident exercise/voice grievances.
Deficiencies (3)
19 CSR 30-85.042(77) Infection Control/Communicable Disease: Please refer to F880.
19 CSR 30-85.042(98)(B) Clinical Records - assessment/interventions: Refer to F640.
19 CSR 30-88.010(20) Exercise Rights/Voice Grievances: Please refer to F561.
Report Facts
residents sampled: 5
residents affected: 1
residents with MDS not transmitted: 10
residents sampled: 16
residents affected: 4
Inspection Report — Jan 11, 2024
Complaint Investigation
Date: Jan 11, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the file documents a complaint investigation. Complaint number MO00230021 is cited in the record.
Complaint Details
MO00230021; substantiation not stated in the document.
Findings
Two deficiencies were cited: one federal health deficiency involving respiratory/tracheostomy care where staff failed to ensure a resident's nasal cannula was connected to and the oxygen concentrator was turned on, and one Missouri state licensure deficiency for nursing care per resident condition which refers to the federal finding.
Deficiencies (1)
19 CSR 30-85.042(66) Nursing Care per Res Condition: Please refer to F695.
Report Facts
physician oxygen flow order (minimum liters per minute): 2
physician oxygen flow order (maximum liters per minute): 5
observed oxygen saturation: 55
Inspection Report — Sep 22, 2023
Routine
Date: Sep 22, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
8 federal deficiencies addressing medication management and storage, activities/programming, restraints/supervision and safe transfers, medication cart security, dietary staffing and menus, food safety/sanitation and refuse; and 12 Missouri state licensure deficiencies largely referencing those same topics (medication administration/storage, protective oversight, activity program, nutrition/menus, kitchen waste and food safety).
Deficiencies (12)
19 CSR 30-85.042(48) Med Administration-Dr, Nurse, CMT: Please refer to F658.
19 CSR 30-85.042(55) Medication Storage: Please refer to F761.
19 CSR 30-85.042(65) Protective Oversight, Voluntary Leave: Please see F689.
19 CSR 30-85.042(92) Activity Program: Please refer to F679.
19 CSR 30-85.052(1) Nutritional Needs Met, Assess Res, Inform Dr: Please refer to F803.
19 CSR 30-85.052(14) Personnel Sufficient, Trained: Please refer to F801.
19 CSR 30-85.052(21) Menus Plan/Post/Keep, List Substitutes: Please refer to F803.
19 CSR 30-87.020(31) Kitchen Waste Containers Covered: Please refer to F814.
19 CSR 30-87.020(32) Outside Dumpsters Cleanable/Covered: Please refer to F814.
19 CSR 30-87.030(2) Wash Hands/Arms & Clean Fingernails: Please refer to F812.
19 CSR 30-87.030(13) Food-Protected, Temp, Need to Contact DHSS: Please refer to F812.
19 CSR 30-87.030(84) Equip/Utensils Air Dried, Self-Drain Utensils: Please refer to F812.
Report Facts
residents sampled: 2
residents affected (dependent): 6
Inspection Report — Sep 22, 2023
Life Safety
Date: Sep 22, 2023
Visit Reason
CMS-2567 life safety survey (K-tag life safety) and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Eight CMS life-safety (K-tag) deficiencies were cited addressing cooking equipment without proper exhaust/suppression, fire alarm testing/maintenance, sprinkler system testing, smoke barrier construction/penetrations, utilities/electrical panel security, fire drill documentation, combustible decorations (candles), and emergency generator maintenance/testing. Six Missouri state deficiencies cited corresponding licensure rules for fire hazard, fire alarm, sprinkler, smoke section walls/doors, fire drill requirements and electrical wiring/equipment.
Deficiencies (6)
19 CSR 30-85.022(2)(E) No Fire Hazard: Please refer to K324 and K753.
19 CSR 30-85.022(10)(B) Fire Alarm System-Test/Maintain: Please refer to K345.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Please refer to K353.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Please refer to K372.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Refer to K712.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Please refer to K511 and K918.
Report Facts
pipes resealed: 3
Inspection Report — Sep 12, 2022
Life Safety
Date: Sep 12, 2022
Visit Reason
CMS-2567 Life Safety (K-tag) pages and Missouri Department of Health and Senior Services State Form pages are included; this file documents a Life Safety Code survey.
Findings
10 federal life safety (K-tag) deficiencies were cited addressing means of egress obstructions, self-closing doors, hazardous area enclosures, fire alarm and sprinkler testing/maintenance, fire drills, smoking areas/ashtrays, electrical panels/working space, emergency generator/testing, and oxygen/gas cylinder storage. 10 Missouri State Form deficiencies were cited addressing night-lights, hazardous area protections, oxygen storage, fire alarm records, sprinkler inspections, corridor requirements, designated smoking/ashtrays, fire drill plans/consultation, fire drill evacuation requirements, and electrical wiring/equipment maintenance.
Deficiencies (10)
19 CSR 30-85.012(125) Night-lights-Required Locations: Based on observation, interview, and record review, facility staff failed to provide night-lights in one resident room or its adjacent toilet room and in four common toilet rooms.
19 CSR 30-85.022(4) Hazardous Areas: See the deficiency cited at K223 and K321.
19 CSR 30-85.022(6) Oxygen Storage: See the deficiency cited at K923.
19 CSR 30-85.022(10)(F) Fire Alarm System Records: See the deficiency cited at K345.
19 CSR 30-85.022(11)(A) Inspections Completed, Certification Annually Sprinkler System: See the deficiency cited at K353.
19 CSR 30-85.022(21) Corridor Requirements: See the deficiency cited at K211.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: See the deficiency cited at K741.
19 CSR 30-85.022(33)(A) Fire Drill/Emergency Preparedness - Plans: Based on interview and record review, facility staff failed to request an annual fire department consultation and provide an up-to-date copy of the facility's plan to the local jurisdiction emergency management director.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: See the deficiency cited at K712.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: See deficiencies cited at K911 and K918.
Report Facts
smoke_zones_affected: 2
smoke_zones_affected: 3
smoke_zones_affected: 7
Inspection Report — Jun 6, 2019
Life Safety
Date: Jun 6, 2019
Visit Reason
Federal CMS-2567 health and life safety survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated in the forms.
Findings
Eight deficiencies were cited: five federal deficiencies addressing emergency preparedness training and testing, failure to participate in a tabletop exercise, corridor door latching, inspection/testing of fire-rated doors, and improper use/maintenance of power strips and cords; and three Missouri state deficiencies referencing electrical appliances, fire drill/emergency preparedness plans, and employee orientation/continuing education.
Deficiencies (3)
19 CSR 30-85.022(2)(H) Electrical Appliances UL/FM Good Repair: Please refer to K920.
19 CSR 30-85.022(33)(A) Fire Drill/Emergency Preparedness - Plans: Please refer to E039.
19 CSR 30-85.042(20) Employee Orientation/Continuing Ed.: Please refer to E037.
Inspection Report — Jun 6, 2019
Routine
Date: Jun 6, 2019
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
The survey cited 5 federal health deficiencies addressing activities programming, bed rail/entrapment assessment, nursing coverage/charge nurse duties, medication labeling/storage, and infection prevention and control. It also cited 6 Missouri state licensure deficiencies referencing nursing staffing, medication labeling and storage, protective oversight/voluntary leave, infection control, and the activity program.
Deficiencies (6)
19 CSR 30-85.042(35)(B) SNF RN-Day Shift, LPN/RN eve/nights: See deficiency cited at F727.
19 CSR 30-85.042(54) Medication Labeling: See deficiency cited at F761.
19 CSR 30-85.042(56) Medication Storage: See deficiency cited at F761.
19 CSR 30-85.042(66) Protective Oversight, Voluntary Leave: See deficiency cited at F700.
19 CSR 30-85.042(78) Infection Control/Communicable Disease: See deficiency cited at F880.
19 CSR 30-85.042(93) Activity Program: See deficiency cited at F679.
Report Facts
residents sampled: 16
residents with missing TB tests: 3
residents with side rails: 3
Inspection Report — Jun 15, 2018
Routine
Date: Jun 15, 2018
Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form licensure survey; the survey type is not stated.
Findings
Six deficiencies were cited: four federal health deficiencies addressing resident assessment/CAA documentation, medication administration and documentation, psychotropic medication PRN use/orders, and infection prevention including water management; and two Missouri state licensure deficiencies that refer to the related federal findings.
Deficiencies (2)
19 CSR 30-85.042(67) Nursing Care per Res Condition: See the deficiency cited at F658.
19 CSR 30-85.042(7B) Infection Control/Communicable Disease: See the deficiency cited at F880.
Report Facts
residents sampled: 19
residents affected by medication omissions/refusals: 14
Inspection Report — Jun 15, 2018
Life Safety
Date: Jun 15, 2018
Visit Reason
Federal CMS-2567 health and life safety survey (K- and E- tags present) accompanied by Missouri Department of Health and Senior Services State Form; Initial Comments indicate Life Safety/NFPA survey.
Findings
Ten deficiencies were cited: five federal life-safety/emergency-preparedness deficiencies addressing emergency preparedness communication, corridor/egress doors, HVAC/exhaust ventilation, fire drills and fire drill documentation/conditions, and maintenance/inspection/testing of doors; and five Missouri state deficiencies addressing door construction/transoms, ventilation requirements, fire drill/plans, fire drill evacuation requirements, and lack of night-lights in resident toilet/bathrooms.
Deficiencies (5)
19 CSR 30-85.012(81) Door No Louvre/Transom, Solid-Core Wood/Metal: Please refer to K363 and K761.
19 CSR 30-85.012(95) Ventilation Requirements-See Table: Please refer to K521.
19 CSR 30-85.022(33)(A) Fire Drill/Emergency Preparedness - Plans: Please refer to E0035.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Please refer to K712.
19 CSR 30-85.032(33) Night Lights Provided: Based on observation and interview, facility staff failed to provide night-lights in all resident toilet rooms and bathrooms.
12 CMS Surveys
Inspection Report — Jul 11, 2024
Life Safety
Date: Jul 11, 2024
Visit Reason
CMS-2567 Life Safety Code survey with accompanying Missouri Department of Health and Senior Services State Form licensure survey; the survey is a life safety survey.
Findings
Twenty deficiencies were cited: eleven federal Life Safety (K-tag) deficiencies and nine Missouri State Form deficiencies. Main topics include egress doors and special locking arrangements, hazardous area doors and storage, fire alarm and sprinkler system out-of-service and maintenance deficiencies, smoke barrier penetrations, lint buildup behind dryers (building services), door inspection/testing, emergency generator and electrical system testing, surge protectors/extension cord misuse, and ignition sources near oxygen.
Deficiencies (11)
K222 Egress Doors: Based on observation, interviews, and record review, facility staff failed to maintain egress doors and proper signage and allowed delayed- or access-controlled egress arrangements and conflicting signage that impeded full and instant use of the means of egress.
K321 Hazardous Areas - Enclosure: Facility staff failed to ensure doors to hazardous areas were self-closing and resisted passage of smoke; multiple resident rooms used for storage contained combustible materials and did not have self-closing doors.
K346 Fire Alarm System - Out of Service: Facility staff failed to ensure a complete policy and procedures were in place for notification, fire watch, impairment coordination, tagging, and actions to be followed when the fire alarm system is out of service.
K353 Sprinkler System - Maintenance and Testing: Facility staff failed to identify and correct a leak, failed to maintain sprinkler areas free of obstructions and foreign materials, and failed to ensure inspection/testing documentation and required actions were completed.
K354 Sprinkler System - Out of Service: Facility staff failed to ensure required procedures and notification actions are followed when the sprinkler system is impaired or out of service for extended periods, and the facility's fire watch policy was incomplete.
K372 Subdivision of Building Spaces - Smoke Barrie[r] Construction: Facility staff failed to maintain required smoke/fire barrier walls free of openings and failed to seal penetrations where wires passed through smoke barriers.
K500 Building Services - Other: Facility staff failed to maintain the back and surrounding areas to the electric dryers free of lint buildup, creating an increased fire risk.
K761 Maintenance, Inspection & Testing - Doors: Facility staff failed to inspect and document non-rated door assemblies located within a means of egress as required, and multiple doors did not close or latch properly or had defects affecting egress.
K918 Electrical Systems - Essential Electric System: Facility staff failed to inspect, test, and maintain the emergency generator in accordance with standards (missing or incomplete four-hour load testing, fuel testing, weekly/monthly documentation, and accessible/functional annunciator panel), and observed obstructions and wasp nests in generator housing.
K920 Electrical Equipment - Power Cords and Extension Cords: Facility staff failed to maintain electrical wiring and surge protector usage per code; multiple resident rooms contained surge protectors or cords not meeting UL/listing requirements or routed through walls/closets and medical devices were plugged into non‑approved protectors.
K925 Gas Equipment - Respiratory Therapy Sources: Facility staff failed to eliminate ignition sources near oxygen; a resident possessed an electronic cigarette and charger in a room with oxygen, creating a fire/ignition hazard.
Report Facts
smoke zones affected: 4
electric clothes dryers: 3
Inspection Report — Jul 11, 2024
Routine
Date: Jul 11, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Six deficiencies were cited: three federal deficiencies involving resident self-determination, failure to transmit required MDS assessments, and infection prevention related to oxygen tubing and concentrator filters; and three Missouri licensure citations for infection control/communicable disease, clinical records/assessment interventions, and resident exercise/voice grievances.
Deficiencies (3)
F561 Self-Determination: Based on observation, interview, and record review, staff failed to promote a resident's self-determination and allowed restrictions on an independently desired outing for one sampled resident.
F640 Encoding/Transmitting Resident Assessments: Facility staff failed to transmit required Minimum Data Set (MDS) assessments to the CMS system for ten of the sampled residents.
F880 Infection Prevention & Control: Staff failed to change, label, and/or properly clean oxygen tubing and oxygen concentrator filters, placing sampled residents at risk of infection.
Report Facts
residents sampled: 5
residents affected: 1
residents with MDS not transmitted: 10
residents sampled: 16
residents affected: 4
Inspection Report — Jan 11, 2024
Complaint Investigation
Date: Jan 11, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the file documents a complaint investigation. Complaint number MO00230021 is cited in the record.
Complaint Details
MO00230021; substantiation not stated in the document.
Findings
Two deficiencies were cited: one federal health deficiency involving respiratory/tracheostomy care where staff failed to ensure a resident's nasal cannula was connected to and the oxygen concentrator was turned on, and one Missouri state licensure deficiency for nursing care per resident condition which refers to the federal finding.
Deficiencies (1)
F695 Respiratory/Tracheostomy Care and Suctioning: Based on interview and record review, staff failed to connect Resident #1's nasal cannula tubing to the oxygen concentrator and failed to turn the concentrator on, resulting in diminished lung sounds and oxygen saturation as low as 55%.
Report Facts
physician oxygen flow order (minimum liters per minute): 2
physician oxygen flow order (maximum liters per minute): 5
observed oxygen saturation: 55
Inspection Report — Sep 22, 2023
Routine
Date: Sep 22, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
8 federal deficiencies addressing medication management and storage, activities/programming, restraints/supervision and safe transfers, medication cart security, dietary staffing and menus, food safety/sanitation and refuse; and 12 Missouri state licensure deficiencies largely referencing those same topics (medication administration/storage, protective oversight, activity program, nutrition/menus, kitchen waste and food safety).
Deficiencies (8)
F658 Services Provided Meet Professional Standards: Facility staff failed to follow narcotic counting and sign-out procedures, with multiple observations of nurses not signing narcotic logs and numerous on/off-going narcotic counts not signed by two licensed staff.
F679 Activities Meet Interest/Needs Each Resident: The facility failed to provide an ongoing documented activity program to meet residents' interests and needs, with multiple residents showing little or no participation and activity attendance not being documented on numerous days.
F689 Free of Accident Hazards/Supervision/Devices: The facility failed to assess and ensure safe use of restraints and assistive devices and to supervise residents and equipment, with missing pre-restrain assessments, improper use of recliners and lapses in maintaining safety during transfers and wheelchair propulsion.
F761 Label/Store Drugs and Biologicals: Facility staff failed to store and label medications in a safe and effective manner, including unlocked/unattended medication carts, OTC and prescription medications left on top of carts, and expired or unlabeled items observed.
F801 Qualified Dietary Staff: The facility failed to employ sufficient qualified dietary/nutrition staff or designate a person with the required qualifications as Director of Food and Nutrition Services; the dietary manager did not have required certification/education documentation.
F803 Menus Meet Resident Nds/Prep in Adv/Followed: Facility staff failed to serve food in accordance with nutritionally calculated menus and standardized recipes and failed to record or maintain substitution documentation and correct portioning for residents.
F812 Food Procurement,Store/Prepare/Serve-Sanitary: Facility staff failed to store, prepare, and handle food to prevent contamination, with numerous unlabeled/undated opened items, dented cans and improperly stored dry and refrigerated goods, and other unsafe food handling and storage practices.
F814 Dispose Garbage and Refuse Properly: The facility failed to properly contain and secure refuse, with outside dumpster lids and indoor waste containers observed open or uncovered and waste-handling practices that could harbor pests or create contamination risks.
Report Facts
residents sampled: 2
residents affected (dependent): 6
Inspection Report — Sep 22, 2023
Life Safety
Date: Sep 22, 2023
Visit Reason
CMS-2567 life safety survey (K-tag life safety) and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Eight CMS life-safety (K-tag) deficiencies were cited addressing cooking equipment without proper exhaust/suppression, fire alarm testing/maintenance, sprinkler system testing, smoke barrier construction/penetrations, utilities/electrical panel security, fire drill documentation, combustible decorations (candles), and emergency generator maintenance/testing. Six Missouri state deficiencies cited corresponding licensure rules for fire hazard, fire alarm, sprinkler, smoke section walls/doors, fire drill requirements and electrical wiring/equipment.
Deficiencies (8)
K324 Cooking Facilities: Staff used commercial griddles in dining areas without exhaust/suppression and griddles and surrounding walls were observed greasy; staff were observed using oiled sprays and preparing food on griddles not under an approved exhaust system.
K345 Fire Alarm System - Testing and Maintenance: Facility records did not provide complete and verifiable documentation for required semi-annual/annual inspection and testing of the fire alarm system by qualified individuals and NICET credential verification for the listed technician showed no results.
K353 Sprinkler System - Maintenance and Testing: Records lacked documentation of a required full flow trip test of the dry pipe valve within the last three years; the last documented full flow trip test was dated 03/14/20.
K372 Subdivision of Building Spaces - Smoke Barrier Construction: Multiple smoke barrier penetrations and openings were found (sealed with joint compound, an unsealed pipe area, telecommunications line through an unsealed hole, manila colored foam) and the facility lacked a routine inspection schedule for barrier walls.
K511 Utilities - Gas and Electric: Electrical panels in corridors by resident rooms were observed unlocked and accessible to the general public and facility staff could not provide consistent policy or assurance that panels are kept locked.
K712 Fire Drills: Facility failed to provide complete, verifiable documentation showing that fire drills under varying conditions were conducted on each shift quarterly; records did not document simulated conditions for several drills.
K753 Combustible Decorations: Facility staff allowed the presence and use of candles with wicks in common areas and resident rooms (observed wax pillar candles in front entrance lobby and wax candles in resident rooms).
K918 Electrical Systems - Essential Electric System Maintenance and Testing: Facility failed to provide complete and verifiable documentation of weekly inspections and an annual fuel quality test for the diesel generator; weekly inspection records and an annual fuel quality test were missing for multiple dates.
Report Facts
pipes resealed: 3
Inspection Report — Sep 12, 2022
Life Safety
Date: Sep 12, 2022
Visit Reason
CMS-2567 Life Safety (K-tag) pages and Missouri Department of Health and Senior Services State Form pages are included; this file documents a Life Safety Code survey.
Findings
10 federal life safety (K-tag) deficiencies were cited addressing means of egress obstructions, self-closing doors, hazardous area enclosures, fire alarm and sprinkler testing/maintenance, fire drills, smoking areas/ashtrays, electrical panels/working space, emergency generator/testing, and oxygen/gas cylinder storage. 10 Missouri State Form deficiencies were cited addressing night-lights, hazardous area protections, oxygen storage, fire alarm records, sprinkler inspections, corridor requirements, designated smoking/ashtrays, fire drill plans/consultation, fire drill evacuation requirements, and electrical wiring/equipment maintenance.
Deficiencies (10)
K211 Means of Egress - General: Based on observations, interviews and record review, facility staff failed to maintain means of egress free of obstructions, including storage in the utility hallway and a table on a stair landing that reduced passage widths.
K223 Doors with Self-Closing Devices: Based on observations and interviews, facility staff failed to ensure doors with self-closing devices had no impediments to closing and latching, with doors observed held open by magnets and wedges and some not latching on actuation.
K321 Hazardous Areas - Enclosure: Based on observations, interviews and record review, facility staff failed to ensure doors to hazardous areas were self-closing, positively latching, and resisted the passage of smoke, and combustible storage was maintained in rooms not protected as required.
K345 Fire Alarm System - Testing and Maintenance: Based on observations, interviews, and record review, facility staff failed to secure the fire alarm control panel against unauthorized access and failed to ensure complete and required inspection/testing documentation for the fire alarm system.
K353 Sprinkler System - Maintenance and Testing: Based on observations, interviews, and record review, facility staff failed to inspect and maintain the sprinkler system in accordance with NFPA 25, including unsealed escutcheon plates, visible loading and other deficiencies affecting sprinkler condition.
K712 Fire Drills: Based on interviews and record review, facility staff failed to conduct or document fire drills under varying simulated conditions and failed to document simulated conditions for multiple drills.
K741 Smoking Regulations: Based on observations, interviews and record review, facility staff failed to maintain designated smoking areas free from fire hazards and to ensure proper ashtray disposal and that smoking occurred only in designated areas.
K911 Electrical Systems - Other: Based on observations, interview, and record review, facility staff failed to ensure electrical panels had required clear working space and were secured/locked against unauthorized access, with multiple panels found obstructed or unlocked.
K918 Electrical Systems - Essential Electric System: Based on observations, interviews and record review, facility staff failed to provide complete and verifiable documentation of periodic exercising/testing of main and feeder circuit breaker components and failed to provide documentation of an annual diesel fuel test for the emergency generator.
K923 Gas Equipment - Cylinder and Container Storage: Based on observations, interviews and record review, facility staff failed to ensure oxygen and other gas cylinders were secured against tipping or falling and that oxygen storage was protected from unauthorized entry.
Report Facts
smoke_zones_affected: 2
smoke_zones_affected: 3
smoke_zones_affected: 7
Inspection Report — May 24, 2022
Routine
Date: May 24, 2022
Visit Reason
Federal health survey (CMS-2567); the survey type is not stated. The survey addresses COVID-19 staff vaccination requirements.
Findings
One federal deficiency cited for failure to ensure staff COVID-19 vaccination compliance; the finding focused on incomplete vaccination documentation and a single CNA with a missed/overdue second vaccine dose.
Deficiencies (1)
F888 COVID-19 Vaccination of Facility Staff: Based on observation and record review, the facility failed to ensure one staff, Certified Nurse Assistant (CNA A), out of eight sampled staff was either fully vaccinated, had an approved exemption, or a temporary delay; CNA A had only received one dose of the Moderna vaccine and the second dose was overdue.
Report Facts
staff sampled: 8
employees fully vaccinated: 83
days past due for second vaccine dose: 53
Inspection Report — Jun 12, 2020
Routine
Date: Jun 12, 2020
Visit Reason
Federal CMS-2567 health survey; a COVID-19 Focused Emergency Preparedness survey and a COVID-19 Focused Infection Control Survey as stated in the Initial Comments. No complaint number is cited.
Findings
No deficiencies were cited; the survey found the facility in compliance with COVID-19-focused infection control and emergency preparedness requirements.
Inspection Report — Jun 6, 2019
Life Safety
Date: Jun 6, 2019
Visit Reason
Federal CMS-2567 health and life safety survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated in the forms.
Findings
Eight deficiencies were cited: five federal deficiencies addressing emergency preparedness training and testing, failure to participate in a tabletop exercise, corridor door latching, inspection/testing of fire-rated doors, and improper use/maintenance of power strips and cords; and three Missouri state deficiencies referencing electrical appliances, fire drill/emergency preparedness plans, and employee orientation/continuing education.
Deficiencies (5)
E037 EP Training Program: Facility staff failed to provide annual emergency preparedness training and testing during the 12-month review period.
E039 EP Testing Requirements: Facility staff failed to participate in a facilitator-led tabletop exercise during the 12-month review period.
K363 Corridor - Doors: Facility staff failed to ensure a corridor door to a room containing flammable materials had positive latching hardware and observed tape and other impediments on the oxygen storage room door.
K761 Maintenance, Inspection & Testing - Doors: Facility failed to inspect, test, and maintain 90-minute fire-rated door assemblies and to maintain required inspection documentation.
K920 Electrical Equipment - Power Cords and Extension Cords: Facility failed to maintain electrical wiring practices regarding power strips and cords, with observations of refrigerators, recliner, and oxygen machine plugged into power strips and use of power strips without proper circuits.
Inspection Report — Jun 6, 2019
Routine
Date: Jun 6, 2019
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
The survey cited 5 federal health deficiencies addressing activities programming, bed rail/entrapment assessment, nursing coverage/charge nurse duties, medication labeling/storage, and infection prevention and control. It also cited 6 Missouri state licensure deficiencies referencing nursing staffing, medication labeling and storage, protective oversight/voluntary leave, infection control, and the activity program.
Deficiencies (5)
F679 Activities Meet Interest/Needs Each Resident: Facility staff failed to provide an ongoing activities program to meet residents' interests and did not provide evening and weekend activities; multiple sampled residents reported no participation and activity records/calendars showed limited offerings.
F700 Bedrails: Facility staff failed to assess residents' risk for entrapment or document alternatives prior to the use of side rails for three residents, and documentation did not show assessment of entrapment risk.
F727 Registered nurse: The facility failed to ensure the Director of Nursing did not serve as the charge nurse when the facility had an average daily occupancy over 60, resulting in potential coverage gaps affecting all residents.
F761 Label/Store Drugs and Biologicals: Facility staff failed to store and label medications in a safe and effective manner, including expired or undated insulin/medication vials and issues in medication carts and storage rooms.
F880 Infection Prevention & Control: The facility failed to implement elements of its infection prevention program; staff did not use barriers when performing blood glucose monitoring and the facility did not complete required two-step TB testing for several residents.
Report Facts
residents sampled: 16
residents with missing TB tests: 3
residents with side rails: 3
Inspection Report — Jun 15, 2018
Routine
Date: Jun 15, 2018
Visit Reason
Federal health survey (CMS-2567) and Missouri Department of Health and Senior Services State Form licensure survey; the survey type is not stated.
Findings
Six deficiencies were cited: four federal health deficiencies addressing resident assessment/CAA documentation, medication administration and documentation, psychotropic medication PRN use/orders, and infection prevention including water management; and two Missouri state licensure deficiencies that refer to the related federal findings.
Deficiencies (4)
F636 Comprehensive Assessments & Timing: Based on record review and interview, facility staff failed to document the date and location of the Care Area Assessment (CAA) section of the MDS for multiple sampled residents.
F658 Services Provided Meet Professional Standards: Based on observation, interview, and record review, staff failed to administer and document medications as ordered and did not document reasons for omitted or refused medications for multiple residents.
F758 Free from Unnec Psychotropic Meds/PRN Use: Based on staff interview and record review, staff failed to obtain required 14-day stop dates for PRN psychotropic medications and failed to attempt gradual dose reductions for residents receiving psychotropic PRNs.
F880 Infection Prevention & Control: Based on observation, interview, and record review, staff failed to follow infection prevention practices including proper glove changes and hand hygiene, failed to bag/date oxygen and nebulizer tubing, and the facility lacked an implemented water management program to address Legionella risk.
Report Facts
residents sampled: 19
residents affected by medication omissions/refusals: 14
Inspection Report — Jun 15, 2018
Life Safety
Date: Jun 15, 2018
Visit Reason
Federal CMS-2567 health and life safety survey (K- and E- tags present) accompanied by Missouri Department of Health and Senior Services State Form; Initial Comments indicate Life Safety/NFPA survey.
Findings
Ten deficiencies were cited: five federal life-safety/emergency-preparedness deficiencies addressing emergency preparedness communication, corridor/egress doors, HVAC/exhaust ventilation, fire drills and fire drill documentation/conditions, and maintenance/inspection/testing of doors; and five Missouri state deficiencies addressing door construction/transoms, ventilation requirements, fire drill/plans, fire drill evacuation requirements, and lack of night-lights in resident toilet/bathrooms.
Deficiencies (5)
E035 LTC and ICF/IID Sharing Plan with Patients: Facility failed to develop and implement a method for sharing information regarding the facility emergency preparedness program with residents, which could delay response procedures.
K363 Corridor - Doors: Facility failed to ensure doors leading to the corridor were solid and resisted the passage of smoke; observations included holes and gaps in multiple doors.
K521 HVAC: Facility failed to provide functioning exhaust ventilation units to provide negative airflow to vent odors in multiple common toilet rooms, staff bathrooms and soiled utility rooms.
K712 Fire Drills: Facility failed to conduct fire drills at various times and under varying conditions on each shift and failed to maintain required documentation and simulation of varying fire conditions.
K761 Maintenance, Inspection & Testing - Doors: Facility failed to inspect, test and maintain non-rated egress doors in accordance with NFPA requirements; records did not show required inspections and several doors had holes or gaps.
Viewing