Inspection Report — May 26, 2026

Routine
Date: May 26, 2026

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Two Missouri state licensure deficiencies were cited concerning fire extinguisher maintenance/mounting and improper ashtray/cigarette butt disposal.

Deficiencies (2)
19 CSR 30-85.022(8)(D) Fire Extinguisher UL/FM, Monthly Check: Based on observation and interview, the facility failed to maintain all fire extinguishers to NFPA standards; several portable extinguishers were mounted more than 60 inches above the finished floor and staff indicated they would lower them.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Based on observation and interview, the facility failed to ensure cigarette butts and ashtray contents were properly disposed in the designated smoking area; surveyors observed over 107 cigarette butts on the ground and an ashcan tower positioned next to a large trashcan.
Report Facts
smoke compartments affected: 5 cigarette butts observed: 107

Inspection Report — Jun 17, 2025

Routine
Date: Jun 17, 2025

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Two state deficiencies were cited: one for malfunctioning/secured exit doors and inadequate egress (door locks) and one for failures in the medication administration system (unsafe handling and unmonitored distribution).

Deficiencies (2)
19 CSR 30-85.022(16) Door Locks: The facility failed to maintain two exit doors in exit pathways with acceptable quick-release egress; exterior exit doors did not open when pushed, required badge swipe/activation, and lacked appropriate signage/instructions. This deficiency had the potential to affect all residents.
19 CSR 30-85.042(46) Safe/Effective Medication System: Staff opened pharmacy-distributed pill packets with their teeth and distributed medications to residents without monitoring consumption, leaving medications unattended and unobserved for several residents. Observations, interviews and record review showed multiple instances of unsafe medication administration practices.
Report Facts
residents sampled for medication review: 9

Inspection Report — Dec 6, 2024

Routine
Date: Dec 6, 2024

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
2 state deficiencies citing failures to follow the facility's change-in-condition policy and failures to promptly notify the physician and document assessments, resulting in a resident being sent to the hospital.

Deficiencies (2)
19 CSR 30-85.042(66) Nursing Care per Res Condition: Based on interview and record review, the facility failed to follow their change in condition policy by failing to ensure staff promptly assessed and notified the physician for one resident who exhibited pale color, lethargy and vigorous shaking; the resident was sent to the hospital and admitted with hyperkalemia and other diagnoses.
19 CSR 30-85.042(78) Dr Notification-Change in Condition: Based on interview and record review, the facility failed to promptly notify the resident's physician after staff identified a change in condition that included pale skin, lethargy and shaking; the RN documented the change but the physician was not notified in a timely manner and the resident was later sent to the hospital and admitted with hyperkalemia.
Report Facts
residents sampled for condition change: 3 residents with problems identified: 1

Inspection Report — Apr 26, 2024

Routine
Date: Apr 26, 2024

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Eight Missouri state deficiencies were cited, all addressing fire/life safety and building maintenance: storage under stairways, hazardous area doors lacking self-closing devices, an active fire alarm trouble indicator, sprinkler system maintenance (missing escutcheon plates and ceiling tiles and lack of quarterly inspections), delayed‑egress door locking and obstructions, smoke barrier damper failures and penetrations, non‑rated trashcans, and damaged/unsealed walls/ceilings.

Deficiencies (8)
19 CSR 30-85.022(2)(D) Combustibles Not Stores Under Stairways: Based on observation, interview and record review, facility staff failed to prohibit storage underneath two stairways used as exit pathways; items observed included a full sized refrigerator and plastic storage bins under the stairwells.
19 CSR 30-85.022(4) Hazardous Areas: Based on observation and interview, the facility failed to maintain hazardous areas with corridor doors equipped with self-closing devices; storage rooms and vending machine room doors did not feature self-closing devices and rooms contained large amounts of stored materials.
19 CSR 30-85.022(10)(G) Fire Alarm System-Correct Faults: Based on observation and interview, the facility failed to ensure an activated trouble indicator light on the fire alarm panel was addressed in a timely manner; the activated trouble signal was observed and monitoring records indicated it had been active for days.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Based on observation, interview and record review, the facility failed to ensure sprinkler system components were maintained, including multiple sprinkler heads without escutcheon plates, missing ceiling tiles near sprinkler heads, and lack of required quarterly sprinkler inspections.
19 CSR 30-85.022(16) Door Locks: Based on observation, interview and record review, the facility failed to ensure egress doors in exit stairwells opened immediately and remained free of obstructions; a delayed‑egress door required 30 seconds to release and a crocheted door handle cover was observed preventing easy operation.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Based on observation and interview, the facility failed to maintain smoke barrier walls and related devices; two smoke dampers did not function and multiple penetrations and unsealed areas were observed in smoke barrier walls.
19 CSR 30-85.022(40)(A) Wastebaskets, Metal/UL/FM: Based on observation and interview, the facility failed to ensure all trash cans were metal or UL/FM approved; numerous unrated plastic trash cans were observed throughout the building.
19 CSR 30-87.020(15) Walls/Ceilings/Doors/Windows Clean: Based on observation and interview, the facility failed to maintain walls in good repair and with proper smoke resistance, including holes and unpatched openings in drywall and closet spaces left unsealed.

Inspection Report — Sep 22, 2023

Routine
Date: Sep 22, 2023

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
1 state deficiency regarding failure to follow the facility's abuse and neglect policy, including not suspending an employee after an alleged verbal abuse incident and allowing that employee to continue assisting residents; the deficiency also notes problems with the facility's investigation and documentation.

Deficiencies (1)
19 CSR 30-88.010(23) Develop/Implement A/N Policies: Based on interview and record review, the facility failed to follow its abuse and neglect policy by not suspending an employee immediately after personally hearing the alleged verbal abuse of one resident and allowing the employee to continue to assist other residents with meal service; the facility's investigation and documentation did not fully support the response to the allegation.

Inspection Report — Jun 22, 2023

Routine
Date: Jun 22, 2023

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
1 state licensure deficiency related to Schedule II medication storage: controlled substances were not secured with double locks and refrigerators in medication rooms on the first and second floors had no locks and contained narcotics.

Deficiencies (1)
19 CSR 30-85.042(56) Schedule II Meds-Storage: Based on observation, interview and record review, the facility failed to ensure controlled substances were locked behind a double lock in two of three medication storage rooms; refrigerators on the first and second floors had no locks and contained boxes of lorazepam.

Inspection Report — Mar 14, 2022

Complaint Investigation
Date: Mar 14, 2022

Visit Reason
Missouri state licensure survey (State Form); complaint investigation (Complaint #MO00181015).

Complaint Details
Complaint MO00181015: allegation of staff-to-resident physical abuse was substantiated.
Findings
One Missouri state deficiency was cited concerning failure to report abuse/neglect. The survey found staff did not notify the state of a substantiated staff-to-resident physical abuse incident.

Deficiencies (1)
19 CSR 30-88.010(25) Report A/N to DHSS/DMH When Needed: Based on interview and record review, the facility staff failed to report one incident of staff-to-resident (Resident #1) physical abuse to the Department of Health and Senior Services. The investigation substantiated the abuse by CNA A and the CNA was terminated, and the facility did not notify the state agency.

Inspection Report — Nov 20, 2019

Routine
Date: Nov 20, 2019

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
1 state deficiency (Class II) was cited involving protective oversight and supervision, assessment and monitoring of side rails/lap buddy use, and inadequate investigation of a resident injury that resulted in a fractured right upper arm.

Deficiencies (1)
19 CSR 30-85.042(66) Protective Oversight, Voluntary Leave: Based on observation, interview and record review, the facility failed to ensure residents received twenty-four hour protective oversight and supervision and failed to assess and document appropriate use of side rails and a lap buddy or to thoroughly investigate an injury. One of three sampled residents sustained a fractured right upper arm.
Report Facts
residents_sampled: 3 residents_affected: 1

Inspection Report — Mar 20, 2019

Routine
Date: Mar 20, 2019

Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.

Findings
Four Missouri state deficiencies were cited addressing sprinkler system maintenance, smoke barrier/wall penetrations, missing/insufficient fire drills, and building maintenance/generator inspection and documentation.

Deficiencies (4)
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Based on observation, interview and record review, the facility failed to maintain sprinkler heads free of debris and in good repair; escutcheon plates were loose, missing or not flush and some sprinkler heads were crooked or loaded with dust, and a storage room and a vending machine alcove were not properly sprinkled.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Based on observation and interview, the facility failed to maintain smoke barriers to provide the required fire resistance rating; multiple penetrations and unsealed conduits were observed in smoke barrier walls.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Based on interview and record review, the facility failed to conduct required fire drills quarterly on each shift for two of the four quarters reviewed, missing night and evening shift drills.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Based on observation, interview and record review, the facility failed to maintain the building in good repair (e.g., an unsealed hole in the laundry room wall) and failed to complete and document required generator inspections and routine checks.
Report Facts
smoke compartments affected: 7 quarters with missing drills: 2

Viewing