Inspection Report

Renewal
Deficiencies: 0 Date: Jun 6, 2025

Visit Reason
A re-licensure survey was conducted from 06/04/2025 to 06/05/2025 to assess compliance with state licensure requirements for a personal care home.

Findings
The facility was found to be in compliance with 902 KAR 20:430 state licensure requirements, with no deficiencies cited.

Inspection Report

Annual Inspection
Deficiencies: 0 Date: Apr 17, 2025

Visit Reason
Annual inspection survey conducted to assess compliance with health and safety regulations at Nazareth Home.

Findings
No health deficiencies were found during the inspection.

Inspection Report

Re-Inspection
Census: 104 Deficiencies: 0 Date: Apr 17, 2025

Visit Reason
A recertification survey was conducted to evaluate the facility's compliance with health care standards.

Findings
The survey identified no health care deficiencies during the inspection period from 04/15/2025 to 04/17/2025.

Report Facts
Sample Size: 36

Inspection Report

Life Safety
Census: 107 Capacity: 118 Deficiencies: 3 Date: Apr 16, 2025

Visit Reason
The Life Safety Recertification Survey was initiated on 04/16/2025 to assess compliance with the Life Safety Code and requirements for participation in Medicare and Medicaid.

Findings
The facility failed to maintain smoke/fire dampers in accordance with NFPA standards, failed to perform required testing of the emergency generator, and failed to maintain power strips and extension cords in accordance with NFPA standards. These deficiencies had the potential to affect all residents and staff.

Deficiencies (3)
K521 HVAC: The facility failed to maintain smoke/fire dampers as required by NFPA standards. Smoke/fire dampers had not been tested or inspected for the required 4-year period.
K918 Electrical Systems: The facility failed to perform required weekly testing and documentation of the emergency generator as per NFPA standards. Only one weekly inspection was completed in the prior 12 months.
K920 Electrical Equipment: The facility failed to maintain power strips and extension cords according to NFPA standards, with unapproved and unsafe power strips found in resident rooms and common areas.
Report Facts
Facility capacity: 118 Census: 107 Deficiency count: 3

Employees mentioned
NameTitleContext
Maintenance DirectorInterviewed and verified findings related to smoke/fire dampers, emergency generator testing, and power strip deficiencies
AdministratorPresent at exit conference and verified findings
Assistant AdministratorResponsible for monitoring adherence to preventative maintenance and power strip protocols

Inspection Report

Annual Inspection
Deficiencies: 0 Date: Dec 12, 2019

Visit Reason
Annual survey inspection of the nursing home to assess compliance with health and safety regulations.

Findings
No health deficiencies were found during the inspection.

Inspection Report

Annual Inspection
Deficiencies: 0 Date: Nov 9, 2018

Visit Reason
Annual inspection survey of the nursing home facility to assess compliance with health and safety regulations.

Findings
No health deficiencies were found during the inspection.