Inspection Reports for
The Ozarks Methodist Manor
205 SOUTH COLLEGE, MARIONVILLE, MO, 65705-9340
Back to Facility Profile6 Reports
Inspection Report — Apr 11, 2024
Routine
Date: Apr 11, 2024
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One Missouri state licensure deficiency (Class III) concerning fire extinguishers not being installed and maintained in accordance with NFPA 10, including extinguishers mounted at improper heights and affecting all residents.
Deficiencies (1)
19 CSR 30-86.022(3)(D) Fire Extinguishers UL/FM, Maintain/Check: Based on observation, review and interview on April 11, 2024, the facility failed to ensure fire extinguishers were installed and maintained in accordance with NFPA 10, 1998 edition; the facility census was 35 and the deficiency affected 35 out of 35 residents.
Report Facts
residents affected: 35
fire extinguishers identified to be lowered: 2
total hallway fire extinguishers: 10
maximum allowed height for extinguisher tops: 60
Inspection Report — Jan 11, 2022
Routine
Date: Jan 11, 2022
Visit Reason
Missouri Department of Health and Senior Services State Form (state licensure); the survey type is not stated.
Findings
One state licensure deficiency (Class II) was cited for sprinkler system noncompliance. The deficiency concerns failed items from the facility's annual sprinkler inspection, including a painted sprinkler head, a leaking 2" 90-degree main drain valve, and a broken handle on the 2" 90-degree main drain.
Deficiencies (1)
19 CSR 30-86.022(11)(A) Complete Sprinkler System-NFPA 13 Sprinkler Systems.: Based on record review and interview on January 11, 2022, the facility failed to install and maintain a complete sprinkler system in accordance with NFPA 13. Record review showed three failed issues on the annual sprinkler inspection, including a painted head in the women's restroom by the riser, a leaking 2" 90-degree main drain valve needing replacement, and a broken handle on the 2" 90-degree main drain requiring replacement.
Report Facts
residents potentially affected: 22
failed issues on annual sprinkler inspection: 3
Inspection Report — Jan 30, 2020
Routine
Date: Jan 30, 2020
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
1 Missouri State Form deficiency (Class III) for clothes dryer vent/lint trap maintenance; the surveyor found a crushed dryer vent in the hall laundry room creating lint removal and overheating risk affecting all residents.
Deficiencies (1)
19 CSR 30-86.022(10)(C) Clothes Dryers Vented, Lint Traps Protection from Hazards: The facility failed to maintain the dryer vent; observation showed a crushed dryer vent in the hall laundry room that affected lint removal and created a risk of overheating. The deficiency affected 29 of 29 residents.
Report Facts
residents affected: 29
Inspection Report — Jan 23, 2020
Life Safety
Date: Jan 23, 2020
Visit Reason
Federal CMS-2567 life safety survey (K-tag life safety findings present) and a Missouri Department of Health and Senior Services State Form licensure survey; the survey type is life safety.
Findings
Four deficiencies were cited: two federal life-safety deficiencies involving hazardous area enclosure/door closure and smoking/ashtray disposal, and two Missouri state licensure deficiencies that refer to those same issues.
Deficiencies (2)
19 CSR 30-85.022(4) Hazardous Areas: Please refer to K321.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Please refer to K741.
Report Facts
wheelchairs observed: 30
Inspection Report — Mar 22, 2019
Life Safety
Date: Mar 22, 2019
Visit Reason
Federal Life Safety (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Six deficiencies were cited: three federal life safety deficiencies involving building construction integrity including missing sprinkler escutcheons and ceiling penetrations, missing GFCI protection in wet locations, and improper use of power strips; and three Missouri state licensure violations citing substantially constructed/maintained physical plant, electrical wiring/equipment, and extension cord/duplex receptacle requirements.
Deficiencies (3)
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Please see K161.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Please see K912.
19 CSR 30-85.032(37) Extension Cords/Duplex Receptacles: Please see K920.
Inspection Report — Jan 17, 2018
Routine
Date: Jan 17, 2018
Visit Reason
Missouri state licensure survey (State Form); the survey type is not stated.
Findings
One state licensure deficiency was cited for failure to maintain the facility fire alarm system, involving a missing transient suppressor and non-working horn notification devices/horn-strobes.
Deficiencies (1)
19 CSR 30-86.022(9)(C) Fire Alarm System-Test/Maintain: Based on observation and interview the facility failed to maintain the fire alarm system. Surveyor observed no transient suppressor in the fire alarm panel and non-working horn notification devices and non-working horn-strobes in multiple areas.
Report Facts
residents affected: 28
8 CMS Surveys
Inspection Report — Apr 30, 2025
Complaint Investigation
Date: Apr 30, 2025
Visit Reason
The inspection was conducted due to a complaint investigation regarding the misappropriation of a resident's money, specifically $40 missing from Resident #1's wallet after returning from the hospital.
Complaint Details
The complaint investigation was triggered by an allegation from the resident's guardian that a Certified Nursing Assistant (CNA A) may have taken $40 from the resident. The resident thought a family member took the money. The allegation was reported to the Ombudsman and local police. Multiple staff, including CNAs and Licensed Practical Nurse (LPN D), were interviewed. The resident's family member and guardian provided statements. The facility conducted two follow-up investigations but was unable to determine what happened to the money.
Findings
The facility failed to ensure residents were free from misappropriation when $40 was taken from Resident #1's wallet without the resident's knowledge or consent. Despite multiple staff interviews and investigations, the facility was unable to determine what happened to the missing money. The investigation remains open with no individual identified as responsible.
Deficiencies (1)
Failure to protect resident from wrongful use of belongings or money, specifically $40 missing from Resident #1's wallet.
Report Facts
Amount of money missing: 40
Employees mentioned
| Name | Title | Context |
|---|---|---|
| CNA A | Certified Nursing Assistant | Named in allegation of possible theft of $40 from resident |
| LPN D | Licensed Practical Nurse | Charge nurse during incident, interviewed regarding missing money |
| CNA C | Certified Nursing Assistant | Assisted resident during incident, interviewed |
| CNA B | Certified Nursing Assistant | Witnessed resident interactions during incident, interviewed |
| Social Services Director | Social Services Director | Reviewed investigation statements and spoke with guardian |
| DON | Director of Nursing | Reviewed investigation, interviewed about ongoing investigation |
| Administrator | Administrator | Interviewed about ongoing investigation and resident funds |
Inspection Report — Jan 15, 2025
Life Safety
Date: Jan 15, 2025
Visit Reason
Federal CMS-2567 Life Safety Code survey (Life Safety). The survey documents K-tag deficiencies; no complaint number is stated.
Findings
Six Life Safety deficiencies were cited covering delayed-egress egress doors that did not function as labeled, exit directional signage, an unsealed hazardous area penetration in a boiler room, lack of required hood/exhaust for a cooking stove in an activity area, improperly located photoelectric smoke detectors relative to air diffusers, and unauthorized portable space heaters.
Deficiencies (6)
K222 Egress Doors: The facility failed to ensure doors labeled with delayed-egress signage operated as required; observations and interviews showed multiple exit doors labeled "PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS." did not function in the delayed egress locking mode and the door contractor could not repair them.
K293 Exit Signage: The facility failed to maintain exit directional signage in accordance with NFPA 101; an observed exit directional sign directed to a door that was "not an exit."
K321 Hazardous Areas - Enclosure: The facility failed to ensure one hazardous area was maintained with a one-hour fire barrier; observation revealed a 2" x 2" hole with conduit through the concrete wall of the boiler/fuel room.
K324 Cooking Facilities: The facility failed to ensure the electric stove used for cooking in an activity area was protected by an approved hood/exhaust system; a four-burner electric stove lacking a grease vapor removal system was observed in a memory care activity room.
K341 Fire Alarm System - Installation: The facility failed to ensure photoelectric smoke detectors were positioned in accordance with NFPA spacing from air diffusers; two detectors were measured to be only 28" and 15" from air diffusers rather than more than 36".
K781 Portable Space Heaters: The facility failed to ensure portable space heaters were not used in resident areas in accordance with NFPA 101; a space heater was observed in the Director of Nursing office within three feet of combustibles and without markings indicating maximum temperature.
Report Facts
residents potentially affected: 22
residents potentially affected: 15
photoelectric smoke detectors affected: 2
residents potentially affected: 10
Inspection Report — Jan 9, 2025
Annual Inspection
Date: Jan 9, 2025
Visit Reason
The inspection was conducted as a comprehensive annual survey to assess compliance with regulatory requirements for nursing home care.
Findings
The facility was found deficient in multiple areas including dignity in meal service, cleanliness of bathroom vents, timely completion and transmission of resident assessments, comprehensive care planning, pressure ulcer care, nutritional monitoring and intervention, staffing requirements, nurse staffing postings, dietary manager qualifications, completeness of medical records, infection prevention program review, and antibiotic stewardship.
Deficiencies (13)
Failed to ensure residents were treated with dignity during meal service, resulting in a resident being left without a meal while others ate.
Failed to maintain clean bathroom exhaust vents for seven residents.
Failed to complete a significant change assessment within 14 days for a resident admitted to hospice.
Failed to transmit completed Minimum Data Set (MDS) assessments to CMS within required time frames for four residents.
Failed to develop comprehensive care plans with measurable goals and interventions for six residents, including failure to address diagnoses and treatments.
Failed to provide appropriate pressure ulcer care and update care plans for a resident with a pressure ulcer.
Failed to identify and intervene for significant weight loss and poor intake for two residents.
Failed to ensure registered nurse coverage for at least eight consecutive hours a day, seven days a week on multiple dates.
Failed to post daily nurse staffing information accurately, missing resident census, nurse license type, and actual hours worked.
Dietary Manager lacked required certification and had not completed Serv-Safe courses.
Failed to maintain complete and accurate medical records, specifically missing physician progress notes for a resident.
Failed to conduct an annual review and update of the Infection Prevention and Control Program (IPCP).
Failed to conduct ongoing antibiotic stewardship review for a resident receiving multiple antibiotics over several months.
Report Facts
Weight loss percentage: 9.6
Weight loss percentage: 19.38
RN coverage missing days: 8
Antibiotic courses: 7
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Dietary Manager | Dietary Manager | Named in relation to lack of certification and failure to complete Serv-Safe courses. |
| Registered Dietitian | Registered Dietitian | Provided information about dietary services and certification status of Dietary Manager. |
| Director of Nursing | Director of Nursing | Named in relation to oversight of nursing coverage, antibiotic stewardship, and care plan expectations. |
| Assistant Director of Nursing | Assistant Director of Nursing | Named in relation to care plan development and weight loss monitoring. |
| Social Services Director | Social Services Director | Named in relation to care plan and medical record documentation. |
| Licensed Practical Nurse 1 | Licensed Practical Nurse | Interviewed regarding wound care and resident care. |
| Licensed Practical Nurse 2 | Licensed Practical Nurse | Interviewed regarding weight monitoring and resident care. |
| Certified Nursing Assistant 1 | Certified Nursing Assistant | Interviewed regarding meal intake recording and resident care. |
| Restorative Nursing Aide 1 | Restorative Nursing Aide | Interviewed regarding weights and resident care. |
| Administrator | Administrator | Named in relation to staffing issues, medical record documentation, and infection control program oversight. |
| Infection Preventionist | Infection Preventionist | Named in relation to infection prevention and control program review. |
| Human Resources Director | Human Resources Director | Named in relation to staffing and nurse coverage. |
| Central Supply | Central Supply | Named in relation to staffing and nurse coverage. |
Inspection Report — Jul 12, 2023
Complaint Investigation
Date: Jul 12, 2023
Visit Reason
The inspection was conducted due to a complaint regarding the facility's failure to timely report an allegation of abuse involving a staff member threatening and cursing at a resident.
Complaint Details
The complaint involved a staff member (Certified Nurse Aide B) threatening and cursing at a resident (Resident #1), which was overheard by another staff member (Housekeeper A). The facility failed to report this allegation within the required two-hour timeframe to management and the state licensing agency.
Findings
The facility failed to report an allegation of abuse immediately to facility management and the state licensing agency within the required two-hour timeframe. This deficiency was uncorrected from a previous citation.
Deficiencies (1)
Timely report suspected abuse, neglect, or theft and report the results of the investigation to proper authorities.
Report Facts
Sample size: 5
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Housekeeper | Staff member who overheard the abuse | |
| Certified Nurse Aide | Staff member who threatened and cursed at the resident |
Inspection Report — May 18, 2023
Date: May 18, 2023
Visit Reason
The inspection was conducted to investigate allegations of abuse, review compliance with care and safety regulations, and assess facility operations including dietary services, infection control, resident care, and environmental conditions.
Findings
The facility failed to timely report and investigate an allegation of abuse, ensure proper documentation and follow-up of residents' code status and behavioral health needs, maintain adequate fall prevention care plans, provide timely treatment for urinary tract infections, employ a qualified dietary manager, maintain food safety and sanitation standards, properly dispose of refuse, maintain accessible call light systems, and implement an effective pest control program.
Deficiencies (10)
Failed to timely report an allegation of abuse to the state licensing agency and failed to complete an investigation of the allegation.
Failed to ensure residents' code status forms were properly signed and documented.
Failed to identify and implement new fall prevention interventions after resident's functional decline and multiple falls.
Failed to provide timely treatment and care for a resident with symptoms of urinary tract infection.
Failed to provide necessary behavioral health care and services including care planning and social services follow-up for a resident with depression.
Failed to employ a qualified dietary manager with required certification or education.
Failed to store and prepare food in accordance with professional standards including improper cold food temperatures, storage of dented and expired food, inadequate cleaning and sanitation, improper hairnet use, and improper glove use.
Failed to properly dispose of empty cardboard boxes in kitchen areas to prevent pest harboring.
Failed to ensure call light pull cords in residents' bathrooms were accessible and of adequate length.
Failed to maintain an effective pest control program as evidenced by presence of live and dead cockroaches and beetles in kitchen areas.
Report Facts
Date of inspection: May 18, 2023
Number of dented cans observed: 9
Cold food temperatures: 51.6
Cold food temperatures: 43.3
Cold food temperatures: 42.6
Cold food temperatures: 41.5
Leukocyte esterase: 3
White blood cells: 2
Bacteria: 1
E. coli colony count: 100000
Employees mentioned
| Name | Title | Context |
|---|---|---|
| D | Certified Nursing Assistant (CNA)/Certified Medication Technician (CMT) | Interviewed regarding abuse allegation and resident care |
| E | Certified Nursing Assistant (CNA) | Interviewed regarding abuse allegation and fall interventions |
| F | Certified Medication Technician (CMT) | Interviewed regarding abuse allegation and fall interventions |
| I | Licensed Practical Nurse (LPN) | Interviewed regarding abuse allegation, UTI care, depression signs, and care plan updates |
| Administrator | Administrator | Interviewed regarding abuse reporting, dietary management, cleaning, pest control, and call light accessibility |
| DON | Director of Nursing | Interviewed regarding abuse investigation, care plans, depression care, and pest control |
| MDS/Care Plan Coordinator | MDS/Care Plan Coordinator | Interviewed regarding care plan updates and resident declines |
| P | Licensed Practical Nurse (LPN) | Interviewed regarding UTI care and lab result monitoring |
| Q | Certified Medication Technician (CMT) | Interviewed regarding fall interventions and depression signs |
| DA N | Dietary Aide | Observed and interviewed regarding food temperature and glove use |
| DA M | Dietary Aide | Observed and interviewed regarding food temperature and glove use |
| DA J | Dietary Aide | Interviewed regarding food temperature, expired food, cleaning, and pest control |
| K | Dietary Aide | Interviewed regarding food temperature, expired food, cleaning, hairnet use, and pest control |
| L | Assistant Dietary Manager | Interviewed regarding food temperature, expired food, cleaning, hairnet use, and pest control |
| DM | Dietary Manager | Interviewed regarding qualifications, food safety, cleaning, hairnet use, glove use, expired food, dented cans, and pest control |
| ES/PD | Environmental Services/Plant Director | Interviewed regarding pest control and call light maintenance |
Inspection Report — Jan 23, 2020
Annual Inspection
Date: Jan 23, 2020
Visit Reason
The inspection was conducted as part of the facility's annual survey to assess compliance with federal regulations and ensure resident safety and quality of care.
Findings
The facility was found deficient in multiple areas including failure to post prior survey results in an accessible location, incomplete and late Minimum Data Set (MDS) assessments and transmissions, inadequate policies and procedures for abuse reporting, failure to document antibiotic monitoring for a resident with a urinary tract infection, lack of physician orders and cleaning protocols for a resident's CPAP machine, incomplete documentation of a resident's decline before death, and non-functioning bathroom exhaust ventilation in multiple resident rooms.
Deficiencies (9)
Failed to ensure prior survey results were posted in a readily accessible public location for residents and visitors.
Failed to develop and implement policies and procedures for timely reporting of abuse to the Department of Health and Senior Services within two hours.
Failed to complete Minimum Data Set (MDS) assessments within required timeframes for three residents.
Failed to electronically transmit encoded MDS data within 14 days for one resident.
Failed to ensure a registered nurse certified the MDS completion date within 14 days after the assessment reference date for three residents.
Failed to document monitoring of antibiotic use every shift for one resident with a urinary tract infection.
Failed to have a physician order for use and cleaning of a CPAP machine for one resident; CPAP machine was unclean and dusty.
Failed to document a resident's decline in condition for seven days before death.
Failed to maintain functioning bathroom exhaust ventilation systems in 23 resident bathrooms.
Report Facts
Residents affected: 60
Residents affected: 3
Residents affected: 1
Residents affected: 3
Residents affected: 1
Residents affected: 1
Residents affected: 1
Residents affected: 23
Employees mentioned
| Name | Title | Context |
|---|---|---|
| LPN E | Licensed Practical Nurse | Assisted MDS coordinator with completing late MDS assessments and training |
| RN C | Registered Nurse | Interviewed regarding antibiotic documentation and CPAP machine care |
| Director of Nursing | Director of Nursing (DON) | Interviewed regarding survey result posting, abuse reporting, MDS assessments, antibiotic monitoring, CPAP machine care, and documentation |
| Administrator | Facility Administrator | Interviewed regarding survey result posting, MDS assessments, antibiotic monitoring, CPAP machine care, and documentation |
| Certified Medication Technician B | Certified Medication Technician | Interviewed regarding abuse reporting procedures |
| Certified Nurse Aide A | Certified Nurse Aide | Interviewed regarding location of survey results |
| Certified Nurse Aide F | Certified Nurse Aide | Interviewed regarding resident condition changes and care |
| Maintenance Supervisor | Maintenance Supervisor | Interviewed regarding bathroom exhaust ventilation system |
| MDS Coordinator | MDS Coordinator | Interviewed regarding MDS assessment completion and transmission |
Inspection Report — Jan 23, 2020
Life Safety
Date: Jan 23, 2020
Visit Reason
Federal CMS-2567 life safety survey (K-tag life safety findings present) and a Missouri Department of Health and Senior Services State Form licensure survey; the survey type is life safety.
Findings
Four deficiencies were cited: two federal life-safety deficiencies involving hazardous area enclosure/door closure and smoking/ashtray disposal, and two Missouri state licensure deficiencies that refer to those same issues.
Deficiencies (2)
K321 Hazardous Areas - Enclosure: Based on observation and interview, the facility failed to ensure hazardous areas were separated from the rest of the facility by self-closing doors and a one-hour fire rating; a shower room used for storage contained approximately 30 wheelchairs and the door did not have a self-closure device.
K741 Smoking Regulations: The facility failed to properly maintain smoking materials and disposal; cigarette butts were mixed with paper trash in ashtray/metal butt can and trash was observed in the smoking area.
Report Facts
wheelchairs observed: 30
Inspection Report — Mar 22, 2019
Life Safety
Date: Mar 22, 2019
Visit Reason
Federal Life Safety (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Six deficiencies were cited: three federal life safety deficiencies involving building construction integrity including missing sprinkler escutcheons and ceiling penetrations, missing GFCI protection in wet locations, and improper use of power strips; and three Missouri state licensure violations citing substantially constructed/maintained physical plant, electrical wiring/equipment, and extension cord/duplex receptacle requirements.
Deficiencies (3)
K 161 Building Construction Type and Height: Based on observation, interview and record review the facility failed to maintain the integrity of the building construction by having unsealed penetrations between the attic and areas below, including missing sprinkler escutcheons in the laundry area and resident rooms and missing ceiling tile in a resident bathroom.
K 912 Electrical Systems - Receptacles: The facility failed to ensure receptacles in wet locations were equipped with ground-fault circuit interrupter (GFCI) protection, with multiple resident rooms and utility/medication/storage areas observed with non-GFCI receptacles near sinks.
K 920 Electrical Equipment - Power Cords and Extens: The facility allowed improper use of power strips and extension cords, including appliances and a salon chair/hair dryer and a mini-fridge plugged into power strips, creating risk to the electrical system.
Viewing