Inspection Reports for
Warm Springs Medical Center Nursing Home

5995 SPRING STREET, WARM SPRINGS, GA, 31830

Back to Facility Profile

12 Reports

2017–2026

Inspection Report — May 14, 2025

Date: May 14, 2025

Visit Reason
The document is a statement of deficiencies and plan of correction for Warm Springs Medical Center Nursing Home following a survey completed on May 14, 2025.

Findings
The report contains initial comments but does not provide specific details on deficiencies or findings.

Inspection Report — Mar 27, 2025

Original Licensing
Date: Mar 27, 2025

Visit Reason
A State Licensure survey was conducted at Warm Springs Medical Center Nursing Home from March 25, 2025, through March 27, 2025.

Findings
The survey revealed there were no State Health deficiencies cited.

Inspection Report — Jan 4, 2024

Date: Jan 4, 2024

Visit Reason
The document is a statement of deficiencies and plan of correction for Warm Springs Medical Center Nursing Home following a survey completed on January 4, 2024.

Findings
The report contains initial comments but does not provide specific details on deficiencies or findings.

Inspection Report — Nov 5, 2023

Annual Inspection
Date: Nov 5, 2023

Visit Reason
A State Licensure survey was conducted at Warm Springs Medical Center Nursing Home from November 3, 2023 through November 5, 2023 to assess compliance with state health regulations and identify any deficiencies.

Findings
The survey revealed multiple deficiencies including failure to follow up on resident grievances regarding staff phone use, inadequate RN coverage on multiple days, improper renal diet service, lack of dietitian documentation for weight loss, incomplete wound assessments, unsafe medical equipment electrical connections, and poor dietary sanitation practices.

Deficiencies (6)
Facility failed to follow up on grievances related to CNAs not treating residents with dignity and respect, specifically CNAs HH, JJ, and II being distracted by phone use.
Facility failed to provide RN coverage for at least eight consecutive hours a day, seven days a week on 13 days in 2023.
Facility failed to serve a proper renal diet for one resident and failed to have dietitian document weight loss for another resident.
Facility failed to complete weekly wound assessments for one resident with multiple pressure ulcers.
Medical equipment (oxygen concentrator) was plugged into a power strip instead of a wall outlet in one resident room.
Facility failed to ensure one of three reach-in freezers and the ice machine were clean and free from debris; dietary staff failed to wash hands and change gloves properly to prevent cross contamination.
Report Facts
Days without RN coverage: 13 Residents ordered renal diet: 3 Residents reviewed for pressure ulcers: 3 Residents with oral diet: 74 Weight loss percentage: 9.9 Weight loss percentage: 5 Weight loss percentage: 3.7

Employees mentioned
NameTitleContext
HHCertified Nursing AssistantNamed in grievance related to phone use while providing care.
JJCertified Nursing AssistantNamed in grievance related to phone use while providing care.
IICertified Nursing AssistantNamed in grievance related to phone use while providing care.
GGHuman ResourcesConfirmed dates with no RN coverage.
KKLicensed Practical NurseAcknowledged wound assessments were incomplete.
FFDietary AideObserved not washing hands or changing gloves properly in dish room.

Inspection Report — Jul 22, 2022

Date: Jul 22, 2022

Visit Reason
The document is a statement of deficiencies and plan of correction related to a regulatory inspection of Warm Springs Medical Center Nursing Home.

Findings
The report contains initial comments but does not provide specific details on deficiencies or findings.

Inspection Report — Apr 21, 2022

Renewal
Date: Apr 21, 2022

Visit Reason
The inspection was conducted as a Licensure Survey from April 19, 2022 through April 21, 2022 to assess compliance for license renewal.

Findings
No deficiencies were identified during the Licensure Survey conducted from April 19, 2022 through April 21, 2022.

Inspection Report — Jul 15, 2020

Date: Jul 15, 2020

Visit Reason
The document is a statement of deficiencies and plan of correction for Warm Springs Medical Center Nursing Home following a survey completed on July 15, 2020.

Findings
The report contains initial comments and a summary statement of deficiencies identified during the survey. Specific deficiencies and their details are not provided in the available page.

Inspection Report — Feb 6, 2020

Renewal
Date: Feb 6, 2020

Visit Reason
A Licensure Survey was conducted from February 3, 2020 through February 6, 2020 to assess compliance with licensure requirements for the nursing home facility.

Findings
The facility failed to ensure post-dialysis assessments were completed for one resident receiving dialysis and failed to ensure open items in dry storage and cooler were labeled and dated, potentially affecting 68 of 72 residents receiving an oral diet.

Deficiencies (2)
Failure to ensure post-dialysis assessments were completed for one resident receiving dialysis, including missing Dialysis Communication Forms for 15 scheduled dialysis days.
Failure to ensure open items in the dry storage and cooler were labeled and dated, affecting 68 of 72 residents receiving an oral diet.
Report Facts
Missing Dialysis Communication Forms: 15 Containers of spices: 30 Containers of milk: 2 Residents affected: 68 Total residents receiving oral diet: 72

Employees mentioned
NameTitleContext
Registered Nurse (RN) SupervisorInterviewed regarding post-dialysis nursing responsibilities
Interim Director of Nursing (DON)Interviewed regarding post-dialysis nursing responsibilities and documentation
Quality Assurance (QA)/Educational NurseInterviewed regarding post-dialysis nursing responsibilities and inservices
Food Service Manager (FSM)Interviewed regarding kitchen observations and food labeling

Inspection Report — Aug 12, 2018

Routine
Date: Aug 12, 2018

Visit Reason
The inspection was conducted as a routine regulatory survey of Warm Springs Medical Center Nursing Home to assess compliance with state and federal regulations regarding pharmacy management, medical and nursing care, infection control, restorative services, and environmental sanitation.

Findings
The facility was found deficient in multiple areas including failure of the consultant pharmacist to recommend gradual dose reduction for certain medications, inadequate monitoring and documentation of medication effectiveness and behaviors, failure to implement care plans for restorative services and therapy recommendations, unsanitary storage of resident personal care items, and poor environmental sanitation including dirty wheelchairs and maintenance issues such as leaks, holes, and odors.

Deficiencies (4)
Consultant pharmacist failed to recommend gradual dose reduction for antidepressants and failed to recognize/document irregularities in opioid pain medication use and behavior monitoring for a resident.
Facility failed to store resident personal care items and specimen collection devices in a sanitary manner in multiple bathrooms.
Facility failed to implement care plans related to monitoring pain medication effectiveness, psychotropic medication dosage reduction, and restorative services including walking and therapy recommendations.
Facility failed to maintain a safe, clean, and comfortable environment including issues with leaks, broken ceiling tiles, holes in walls, odors, and dirty wheelchairs.
Report Facts
Sample size: 42 Hydrocodone/APAP administrations: 17 Hydrocodone/APAP administrations: 15 Hydrocodone/APAP administrations: 13 Restorative service days: 5 Restorative service days: 14

Employees mentioned
NameTitleContext
LPN EELicensed Practical NurseVerified lack of behavior and side effect monitoring and infection control concerns regarding urinal storage
Director of NursingDirector of Nursing (DON)Verified multiple deficiencies including lack of behavior monitoring, restorative services, and environmental sanitation issues
Certified Nursing Assistant IICNA IIReported on restorative walking services and wheelchair cleaning responsibilities
Environmental Aide JJEnvironmental AideReported that CNAs are responsible for cleaning wheelchairs
Maintenance WorkerMaintenance WorkerReported on facility maintenance issues including leaks, holes, and ceiling tile damage
Housekeeping SupervisorHousekeeping SupervisorReported on cleaning schedules and confirmed environmental sanitation concerns

Inspection Report — Oct 24, 2017

Follow-Up
Date: Oct 24, 2017

Visit Reason
Revisit survey conducted 10/23/2017 through 10/24/2017 for the Recertification survey of 9/4/2017.

Findings
The facility was cited for 2 federal deficiencies for failure to monitor privacy curtains and for ineffective administration related to implementation of the Plan of Correction.

Inspection Report — Sep 4, 2017

Routine
Date: Sep 4, 2017

Visit Reason
Licensure survey to determine compliance with State Long Term Care Requirements.

Findings
The facility failed to ensure that a comprehensive care plan was created related to hypertension and the administration of blood pressure medications for one resident (Resident #51).

Deficiencies (1)
N 1018 - Medical, Dental and Nursing Care: the facility failed to ensure that a comprehensive care plan was created related to hypertension and the administration of blood pressure medications for Resident #51.
Report Facts
: 29 : 30 : 7

Report — June 24, 2026

June 24, 2026

39 CMS Surveys

Inspection Report — May 14, 2025

Follow-Up
Date: May 14, 2025

Visit Reason
A revisit survey was conducted at Warm Spring Medical Nursing Home on May 14, 2025 to determine whether deficiencies cited in the March 27, 2025 recertification survey had been corrected.

Findings
All deficiencies cited as a result of the March 27, 2025 recertification survey were found to be corrected. The facility had a census of 68 residents.

Inspection Report — May 14, 2025

Follow-Up
Date: May 14, 2025

Visit Reason
On May 14, 2025, a Follow-Up Survey was conducted to determine whether previously cited survey tags were corrected.

Findings
On May 14, 2025, it was noted that all previously cited survey tags have been corrected.

Inspection Report — Mar 27, 2025

Complaint Investigation
Date: Mar 27, 2025

Visit Reason
The inspection was conducted to investigate a complaint regarding the facility's failure to follow a physician's orders for oxygen administration for one resident.

Complaint Details
The complaint was substantiated based on observations, record reviews, and staff interviews confirming the oxygen flow rate was below the physician's order for resident R18.
Findings
The facility failed to administer oxygen at the prescribed flow rate of 2 liters per minute for one resident, instead providing oxygen at 1.25 liters per minute. The issue was confirmed by observations and staff interview, and the flow rate was corrected during the inspection.

Deficiencies (1)
F 0695: The facility failed to follow physician's orders for oxygen administration for one resident by providing oxygen at 1.25 liters per minute instead of the ordered 2 liters per minute. This posed a risk of respiratory complications.
Report Facts
Residents with oxygen orders: 18 Oxygen flow rate ordered: 2 Oxygen flow rate observed: 1.25

Employees mentioned
NameTitleContext
Licensed Practical Nurse (LPN) BBVerified and adjusted oxygen flow rate for resident R18
Director of Nursing (DON)Stated nurses manage oxygen settings and document checks once per shift

Inspection Report — Mar 27, 2025

Complaint Investigation
Date: Mar 27, 2025

Visit Reason
The inspection was conducted to investigate a complaint regarding the facility's failure to follow physician's orders for oxygen administration for one resident.

Complaint Details
The complaint was substantiated as the facility did not follow the physician's oxygen order for resident R18, administering oxygen at a lower flow rate than ordered.
Findings
The facility failed to administer oxygen at the prescribed flow rate of 2 liters per minute for one resident, instead providing oxygen at 1.25 liters per minute. The issue was confirmed by observations and staff interview, and the flow rate was corrected during the inspection.

Deficiencies (1)
F 0695: The facility failed to follow physician's orders for oxygen administration for one resident, providing oxygen at 1.25 liters per minute instead of the ordered 2 liters per minute. This posed a risk of respiratory complications.
Report Facts
Residents affected: 1 Oxygen flow rate ordered: 2 Oxygen flow rate observed: 1.25

Employees mentioned
NameTitleContext
Licensed Practical Nurse (LPN) BBVerified oxygen flow rate was set incorrectly and adjusted it
Director of Nursing (DON)Stated nurses manage oxygen settings and document checks once per shift

Inspection Report — Mar 27, 2025

Annual Inspection
Date: Mar 27, 2025

Visit Reason
A standard survey was conducted March 25-27, 2025 to determine compliance with Medicare/Medicaid regulations; Complaint Intake Numbers GA00245145, GA00248073, GA00248466, GA00249447, and GA00250561 were investigated in conjunction with this survey.

Complaint Details
Complaint Intake Numbers GA00245145, GA00248073, GA00248466, GA00249447, and GA00250561 were investigated and were unsubstantiated.
Findings
The facility was cited for 1 deficiency for failing to follow a physician's order for oxygen for one resident (R18); the O2 concentrator was set at 1.25 LPM while the order was for 2 LPM.

Deficiencies (1)
F 0695 - Oxygen administration: the facility failed to follow physician's orders for oxygen for one of 18 residents (R18); observations showed the O2 concentrator flow was set at 1.25 LPM while the physician's order dated 3/17/2025 was for 2 LPM continuous.

Inspection Report — Mar 26, 2025

Life Safety
Date: Mar 26, 2025

Visit Reason
Life Safety Code survey and Emergency Preparedness Program review conducted on March 26, 2025.

Findings
The facility was cited for 2 Life Safety Code deficiencies for emergency lighting that failed to function on backup batteries and unsealed penetrations through a rated smoke wall in the ground floor elevator area.

Deficiencies (2)
K 0291 - Emergency Lighting: two exit signs with emergency lighting failed to function on a backup battery when tested during a tour on 3/26/2025, affecting residents and staff on the ground level.
K 0311 - Vertical Openings - Enclosure: holes had been drilled through the smoke wall in the ground floor elevator area to run electrical wires and the holes were not sealed with fire caulk.

Inspection Report — Jan 4, 2024

Follow-Up
Date: Jan 4, 2024

Visit Reason
Health revisit survey conducted January 2-4, 2024 to verify correction of deficiencies cited in the November 5, 2023 recertification survey.

Findings
All deficiencies cited as a result of the November 5, 2023 recertification survey were found to be corrected.

Inspection Report — Dec 21, 2023

Follow-Up
Date: Dec 21, 2023

Visit Reason
Life Safety Code revisit to verify correction of previously cited survey tags.

Findings
A Life Safety Code revisit was conducted on 2023-12-21 and it was noted that all previously cited survey tags have been corrected.

Inspection Report — Nov 5, 2023

Complaint Investigation
Date: Nov 5, 2023

Visit Reason
The inspection was conducted following complaints regarding Certified Nursing Assistants (CNAs) using cell phones while providing care and failure to follow up on grievances.

Complaint Details
The complaint investigation was substantiated with findings that CNAs were using cell phones during care and grievances were not properly addressed. The facility acknowledged the issues but corrective actions were limited.
Findings
The facility failed to follow up on grievances related to CNAs using cell phones while providing care, failed to complete weekly wound assessments for one resident with pressure ulcers, and had medical equipment improperly plugged into a power strip instead of a wall outlet.

Deficiencies (3)
F 0585: The facility failed to follow up on grievances related to CNAs using cell phones while providing care to three residents. Complaints were made but no follow-up or resolution was documented.
F 0686: The facility failed to complete weekly wound assessments for one resident with Stage 3 and Stage 4 pressure ulcers, despite policy requiring ongoing wound monitoring.
F 0689: The facility failed to ensure medical equipment was plugged into a wall outlet rather than a power strip in one resident room, creating a potential accident hazard.
Report Facts
Residents sampled: 33 Residents reviewed for pressure ulcers: 3 Resident with wound assessment deficiency: 1 Resident rooms observed: 42

Employees mentioned
NameTitleContext
KKLicensed Practical Nurse (LPN)Named in relation to wound assessment deficiency for resident R51
Director of Nursing (DON)Interviewed regarding improper medical equipment plugging; no full name provided
AdministratorInterviewed about resident council meeting and CNA phone use; no full name provided

Inspection Report — Nov 5, 2023

Complaint Investigation
Date: Nov 5, 2023

Visit Reason
The inspection was conducted to investigate complaints and compliance with regulatory requirements related to resident rights, staff conduct, pre-employment screening, wound care, safety, dietary services, nursing coverage, and food handling.

Complaint Details
The visit was complaint-related, investigating issues including failure to provide Medicare notices, resident grievances about staff conduct, pre-employment screening deficiencies, wound care lapses, safety hazards, dietary errors, nursing coverage gaps, and food safety violations. Substantiation status is not explicitly stated.
Findings
The facility was found deficient in multiple areas including failure to provide required Medicare notices to discharged residents, inadequate follow-up on resident grievances, lack of pre-employment reference checks, incomplete wound assessments, unsafe medical equipment use, improper dietary services including incorrect renal diet and missing dietitian documentation, insufficient RN coverage on multiple days, and poor food safety and hygiene practices in dietary services.

Deficiencies (8)
F 0582: The facility failed to provide the Skilled Nursing Facility Advance Beneficiary Notice (SNFABN) to two residents discharged from Medicare Part A services but remaining in the facility.
F 0585: The facility failed to follow up on grievances related to CNAs using cell phones while providing care, affecting three residents.
F 0607: The facility failed to conduct pre-employment reference checks for 10 of 33 employees reviewed.
F 0686: The facility failed to complete weekly wound assessments for one resident with multiple pressure ulcers.
F 0689: The facility failed to ensure medical equipment was plugged into wall outlets rather than power strips in one resident room.
F 0692: The facility failed to serve a proper renal diet to one resident and failed to have registered dietitian documentation for weight loss for another resident.
F 0727: The facility failed to provide RN coverage for at least eight consecutive hours a day on multiple days over June and October 2023.
F 0812: The facility failed to maintain cleanliness of food storage and ice machines and failed to ensure dietary staff washed hands and changed gloves to prevent cross contamination.
Report Facts
Residents affected: 2 Residents affected: 3 Employees: 10 Residents affected: 1 Residents affected: 1 Residents affected: 2 Days without RN coverage: 13

Inspection Report — Nov 5, 2023

Annual Inspection
Date: Nov 5, 2023

Visit Reason
A standard survey was conducted November 3, 2023 through November 5, 2023 to assess the facility's compliance with Medicare/Medicaid requirements. Complaint Intake Number GA00232017 was investigated in conjunction with this standard survey.

Complaint Details
Complaint Intake Number GA00232017 was investigated in conjunction with this standard survey and was substatiated without deficiencies.
Findings
The facility was cited for 8 deficiencies involving beneficiary notices (SNFABN), grievance follow-up, pre-employment reference checks, wound assessment frequency, electrical safety of medical equipment, nutrition/dietary documentation and meal service, RN staffing coverage, and food safety/handling.

Deficiencies (8)
F 0582 - Medicaid/Medicare Coverage/Liability Notice: the facility failed to provide the Skilled Nursing Facility Advance Beneficiary Notice (SNFABN) (Form CMS-10055) to two residents (R47 and R36) of three residents discharged from Medicare Part A who remained in the facility.
F 0585 - Grievances: the facility failed to follow up on grievances that CNAs were on their phones and not treating residents with dignity and respect for three residents ("A","B","C") of 33 sampled residents.
F 0607 - Develop/Implement Abuse/Neglect Policies: the facility failed to conduct pre-employment reference checks for 10 of 33 employees reviewed, including the Administrator, Director of Nursing, Dietary Manager, Infection Preventionist, Social Services Director, LPN AA, LPN BB, LPN CC, CNA DD, and CNA DD.
F 0686 - Treatment/Services to Prevent/Heal Pressure Ulcer: the facility failed to complete weekly wound assessments for resident R51 who had two Stage 3 pressure ulcers and one Stage 4 pressure ulcer.
F 0689 - Free of Accident Hazards/Supervision/Devices: the facility had an oxygen concentrator in resident room 53 plugged into a power strip lying on the floor instead of being plugged into a wall outlet.
F 0692 - Nutrition/Hydration Status Maintenance: the facility served potato wedges to R28 who was ordered a renal diet (should have been buttered noodles) and failed to have the registered dietitian document weight loss for R68 despite documented weight loss.
F 0727 - RN 8 Hrs/7 days/Wk, Full Time DON: the facility failed to provide the services of a Registered Nurse for at least eight consecutive hours a day, seven days a week on 13 days (dates documented).
F 0812 - Food Procurement,Store/Prepare/Serve-Sanitary: the facility failed to ensure one reach-in freezer and the ice machine were clean and free from debris, and observed dietary staff (dish room) not changing gloves or washing hands between dirty and clean dishes, risking cross-contamination.

Inspection Report — Nov 4, 2023

Life Safety
Date: Nov 4, 2023

Visit Reason
Life Safety Code Survey and Emergency Preparedness Program review conducted on 11/04/2023.

Findings
The facility was cited for 3 Life Safety Code deficiencies for broken/missing ceiling tiles that could prevent sprinkler activation, penetrations through smoke barriers, and open electrical panels creating a shock hazard.

Deficiencies (3)
K 0331 - Interior Wall and Ceiling Finish: broken and missing ceiling tiles in the maintenance office would not allow the sprinkler system to activate as needed. This affected one of three smoke compartments.
K 0372 - Subdivision of Building Spaces - Smoke Barrier Construction: observation revealed two locations had penetrations through smoke barriers (generator room through to open corridor and on the main upper floor near the elevator).
K 0511 - Utilities - Gas and Electric: two electrical panels had open circuits not covered, panels identified as "QIF 2-82" and "DEM" at the generator (both on the lower level), creating a risk of electrical shock.

Inspection Report — Aug 15, 2023

Annual Inspection
Date: Aug 15, 2023

Visit Reason
Annual inspection of Warm Springs Medical Center Nursing Home to assess compliance with health and safety regulations.

Findings
No health deficiencies were found during the inspection.

Inspection Report — Aug 15, 2023

Routine
Date: Aug 15, 2023

Visit Reason
COVID-19 focused emergency preparedness and focused infection control surveys were conducted at Warm Springs Medical Center Nursing Home.

Findings
The facility was found to be in compliance with 42 CFR §483.73 related to E-0024(b)(6) and in substantial compliance with Medicare/Medicaid regulations; no deficiencies were cited.

Inspection Report — Jul 22, 2022

Follow-Up
Date: Jul 22, 2022

Visit Reason
A revisit survey was conducted on 7/22/22 to verify correction of the deficiency cited as a result of the 4/21/22 Recertification Survey.

Findings
The deficiency cited as a result of the 4/21/22 Recertification Survey was found to be corrected.

Report Facts
:

Inspection Report — Jul 22, 2022

Follow-Up
Date: Jul 22, 2022

Visit Reason
A revisit survey was conducted on 7/22/22 to verify corrections from the 5/19/22 Federal Monitoring Health Comparative and COVID Survey.

Findings
All deficiencies cited as a result of the 5/19/22 Federal Monitoring Health Comparative and COVID Survey were found to be corrected. The facility had a census of 70.

Inspection Report — May 19, 2022

Monitoring
Date: May 19, 2022

Visit Reason
A Federal Monitoring Health Comparative and COVID Survey was conducted at Warm Springs Medical Center Nursing Home from 05/16/2022 through 05/19/2022.

Findings
The facility was cited for 11 deficiencies related to resident rights and accommodations; advance directives and care planning; PASARR coordination; medication management, monitoring, labeling and storage; building and environmental maintenance; and food safety.

Deficiencies (11)
F 0550 - Resident Rights/Exercise of Rights: CNA #3 stood over Resident #171 while assisting with breakfast instead of sitting to feed the resident, contrary to the resident's care plan and facility expectation (1 of 18 sampled residents).
F 0558 - Reasonable Accommodations/Needs: Resident #47, who is 6'4", had a bed that did not accommodate his height so his feet touched the end of the bed and he was uncomfortable, and staff/administration had not obtained a longer bed despite being informed.
F 0578 - Request/Refuse/Advance Directives: Resident #55's chart contained an Advance Directive dated 11/19/21 indicating full code while physician orders, eMAR and hospice plan indicated DNR/DNAR and the discrepancy was not reconciled in the record.
F 0584 - Safe/Clean/Comfortable/Homelike Environment: Observations identified damaged walls, missing paint and gouges, stained and cracked floor tiles, splintered closet door, loose sink faucet, cracked/peeling ceiling, and crumbling cement floor joint affecting rooms 8 and 57 and common areas (potentially affecting multiple residents).
F 0644 - Coordination of PASARR and Assessments: The facility failed to complete PASARR Level II assessments for Residents #40 and #35 despite documentation of schizophrenia or qualifying mental health diagnoses.
F 0656 - Develop/Implement Comprehensive Care Plan: The facility failed to implement the care plan for dehydration for Resident #47, including incomplete Plan of Care Kardex entries for intake/output and meal consumption during April–May 2022.
F 0658 - Services Provided Meet Professional Standards: The facility failed to follow a physician's order to reduce methocarbamol for Resident #1, resulting in the resident receiving double the prescribed dose for an entire month.
F 0684 - Quality of Care: The facility failed to adequately monitor and document meal consumption, intake and output, bladder and bowel action for Resident #47 per physician orders, contributing to unrecognized dehydration and hospitalization.
F 0757 - Drug Regimen is Free from Unnecessary Drugs: Resident #172 became lethargic/sleepy after increases in antipsychotic (Seroquel) and addition/increase of Xanax, and staff did not document holding doses or timely notify the physician or adequately monitor/report the adverse response.
F 0761 - Label/Store Drugs and Biologicals: Medication refrigerator temperature logs were not documented for multiple days for two medication refrigerators and the downstairs refrigerator contained expired acetaminophen suppositories that had not been removed.
F 0812 - Food Procurement/Store/Prepare/Serve-Sanitary: Kitchen and nourishment refrigerators contained unlabeled or undated food (e.g., 25 unlabeled brownies, unlabeled resident sandwiches), expired items (e.g., marinade, Glucerna, creamer), and wet-stacked pans/trays increasing risk of cross-contamination and foodborne illness.

Inspection Report — Apr 21, 2022

Date: Apr 21, 2022

Visit Reason
The inspection was conducted to evaluate compliance with food service standards, specifically ensuring meals are served at safe and appetizing temperatures.

Findings
The facility failed to ensure that lunch meals remained hot upon delivery to residents, with observations confirming food temperatures as low as 64 degrees. Interviews and policy reviews indicated ongoing issues with cold food service affecting some residents.

Deficiencies (1)
F 0804: The facility failed to ensure food and drink were palatable, attractive, and served at a safe and appetizing temperature. Observations showed lunch meals were cold upon delivery, affecting 18 residents on the hall.
Report Facts
Residents affected: 18 Food temperature: 64

Inspection Report — Apr 21, 2022

Annual Inspection
Date: Apr 21, 2022

Visit Reason
A standard survey was conducted at Warm Springs Medical Center Nursing Home from 4/19/2022 through 4/21/2022.

Findings
The facility was cited for one deficiency for failing to ensure meals remained hot upon delivery; a sampled tray measured 64 degrees and the issue potentially affected 18 residents on the hall.

Deficiencies (1)
F 0804 - Nutritive Value/Appear, Palatable/Prefer Temp: based on observation, interview, and review of facility policy, the facility failed to ensure that a lunch meal remained hot upon delivery to residents, with a test tray sampled at 64 degrees and the condition potentially affecting 18 residents on the hall.

Inspection Report — Apr 20, 2022

Life Safety
Date: Apr 20, 2022

Visit Reason
A review of the Emergency Preparedness Program was conducted on 04-20-2022. During a Life Safety Code Survey conducted on 04-20-2022, the facility was assessed for compliance with applicable requirements.

Findings
The emergency preparedness program and life safety elements were found to be in compliance with the applicable requirements; no deficiencies were cited.

Inspection Report — Apr 29, 2021

Follow-Up
Date: Apr 29, 2021

Visit Reason
A revisit survey was conducted by desk review on 4/29/2021.

Findings
All deficiencies cited as a result of the 2/24/2021 COVID-19 Focused Infection Control Survey were found to be corrected.

Inspection Report — Feb 24, 2021

Routine
Date: Feb 24, 2021

Visit Reason
A COVID-19 Focused Infection Control Survey was conducted to assess the facility's implementation of CMS and CDC recommended practices for COVID-19.

Findings
The facility was cited for failure to have an effective immunization program for influenza and pneumococcal vaccinations; specifically, it failed to ensure residents were offered pneumococcal vaccination per CDC recommendations, affecting 1 of 5 sampled residents.

Deficiencies (1)
F 0883 - Influenza and Pneumococcal Immunizations: the facility failed to have an effective immunization program to ensure residents were offered pneumococcal vaccinations per CDC recommendations; this affected 1 of 5 sampled residents (R#1) who had no record the second pneumococcal vaccine (PPSV23) was offered.

Inspection Report — Aug 17, 2020

Follow-Up
Date: Aug 17, 2020

Visit Reason
Follow-Up desk review to verify correction of previously cited survey tags.

Findings
A Follow-Up desk review was conducted on 08-17-2020 and it was noted that all previously cited survey tags have been corrected.

Inspection Report — Jul 15, 2020

Follow-Up
Date: Jul 15, 2020

Visit Reason
Revisit survey to verify correction of deficiencies cited in the 2/6/2020 Recertification Survey.

Findings
A revisit survey was conducted on 7/15/2020 and all deficiencies cited as a result of the 2/6/2020 Recertification Survey were found to be corrected.

Inspection Report — Jul 15, 2020

Routine
Date: Jul 15, 2020

Visit Reason
A COVID-19 Focused Emergency Preparedness and Infection Control Survey was conducted at Warm Springs Medical Center Nursing Home on 7/15/2020.

Findings
The facility was found to be in compliance with emergency preparedness requirements (42 CFR 483.73 related to E-0024(b)(6)) and with 42 CFR 483.80 infection control regulations and CMS/CDC recommended practices for COVID-19.

Inspection Report — Feb 6, 2020

Annual Inspection
Date: Feb 6, 2020

Visit Reason
A standard survey was conducted February 3-6, 2020 to assess the facility's compliance with Medicare/Medicaid requirements for long term care facilities.

Findings
The facility was cited for 2 deficiencies for failing to complete post-dialysis assessments and for failing to ensure open food items in storage and the cooler were labeled and dated, potentially affecting 68 of 72 residents.

Deficiencies (2)
F 0698 - Dialysis: the facility failed to ensure post-dialysis assessments were completed for one resident (R#28) of three receiving dialysis; 15 scheduled dialysis days were missing Dialysis Communication Forms and nursing notes lacked documentation of post-dialysis vital signs and site assessment.
F 0812 - Food Procurement/Store/Prepare/Serve-Sanitary: open items in the dry storage and cooler were not labeled and dated (30 containers of spices and two opened milk containers were found unlabeled), a practice that potentially affected 68 of 72 residents receiving an oral diet.

Inspection Report — Feb 5, 2020

Life Safety
Date: Feb 5, 2020

Visit Reason
Life Safety Code survey to assess compliance with NFPA 101 and a review of the emergency preparedness program.

Findings
The facility was cited for 2 Life Safety Code deficiencies: missing handrails on the main entrance stairway and combustible liquids improperly stored in the nursing home generator storage area.

Deficiencies (2)
K 0211 - Means of Egress - General: observation revealed that no hand rails were provided on either side and within 44 inches of all portions of the front entry stairway at the main entrance.
K 0321 - Hazardous Areas - Enclosure: observation revealed that over 10 gallons of Class II flammable liquids (10 gallons of diesel fuel and several containers of motor oil) were stored in the nursing home generator area and were not separated by the required construction or stored in an approved flammable liquids cabinet.

Inspection Report — Mar 20, 2019

Complaint Investigation
Date: Mar 20, 2019

Visit Reason
An Abbreviated/Partial Extended Survey was conducted to investigate complaint GA00195336.

Complaint Details
Complaint GA00195336 was unsubstantiated with no deficiencies.
Findings
Complaint GA00195336 was unsubstantiated and no deficiencies were cited.

Inspection Report — Feb 18, 2019

Complaint Investigation
Date: Feb 18, 2019

Visit Reason
An Abbreviated/Partial Extended Survey investigating complaint number GA00194808.

Complaint Details
Complaint GA00194808 was unsubstantiated.
Findings
An Abbreviated/Partial Extended Survey investigating complaint number GA00194808 was conducted on 2019-02-18. The complaint was unsubstantiated.

Inspection Report — Oct 11, 2018

Follow-Up
Date: Oct 11, 2018

Visit Reason
A revisit survey was conducted on October 11, 2018 to determine whether previously cited deficiencies had been corrected.

Findings
All deficiencies cited as a result of the August 12, 2018 standard survey were verified as corrected; the facility was in compliance as of 9/26/18.

Inspection Report — Aug 12, 2018

Annual Inspection
Date: Aug 12, 2018

Visit Reason
Standard survey (recertification) of the nursing home conducted August 10-12, 2018.

Findings
The facility was cited for 15 deficiencies across resident rights, advance directives, environment, care planning, restorative services, nutrition, staffing, medication management, food safety, and infection control. Deficiencies included failures to maintain resident dignity, post required notices, secure POLST signatures, maintain a safe/clean environment, implement and timely develop care plans, provide restorative and nutritional care, post nurse staffing, monitor psychotropic and PRN opioid use, maintain hot food temperatures, and store personal care items hygienically.

Deficiencies (15)
F 0550 - Resident rights/dignity: based on observations and record review the facility pulled residents backwards in Geri-chairs and wheelchairs for three residents (R#16, R#9, R#51), failing to maintain dignity.
F 0574 - Required notices/contact info: the facility failed to provide residents with information/signage on how to report abuse or neglect to the state and residents did not know where the state inspection book was located.
F 0577 - Right to survey results/advocate info: the facility failed to post notice of the availability/location of the State survey results so residents and visitors were aware of where to review them.
F 0578 - Advance directives/POLST: the facility failed to obtain concurring physician signatures for POLST DNR consents for two residents (R#37 and R#42) and had documentation issues related to healthcare agent/POA authority.
F 0584 - Safe/clean/comfortable environment: multiple areas contained leaks, buckled or missing ceiling tiles, holes in walls, missing paint, stains and strong odors, and several residents' wheelchairs had dirt and buildup.
F 0656 - Develop/implement comprehensive care plan: the facility failed to implement care plans for monitoring pain medication effectiveness and behaviors and pharmacy GDR review for R#20, follow PT/OT recommendations for R#64, and timely develop a comprehensive care plan for R#38.
F 0657 - Care plan timing/revision: the facility failed to develop a comprehensive care plan within the required timeframe for R#38 (admission MDS 6/19/18; care plan not completed until 8/11/18).
F 0688 - Mobility/ROM: the facility failed to provide restorative services including walking for R#64 and failed to provide/document active range of motion and dressing/grooming restorative services for R#33 as indicated.
F 0692 - Nutrition/hydration maintenance: the facility failed to reassess need for meal assistance or adequately address poor intake for R#11 who experienced a 12.5% weight loss in three months and had frequent documented low intake/refusals.
F 0732 - Posted nurse staffing information: the facility failed to post daily nurse staffing data in a prominent place accessible to residents and visitors; posting had been removed for painting and not replaced.
F 0756 - Drug regimen review/report irregularities: the consultant pharmacist review did not document recommendations (including gradual dose reduction) for long-term antidepressant use and did not report irregularities related to PRN opioid documentation for R#20.
F 0757 - Unnecessary drugs/general: the facility lacked evidence of adequate monitoring/documentation for frequent PRN opioid (Hydrocodone/APAP) use for R#20, as MARs and nurses' notes did not consistently document indication, time, or effectiveness.
F 0758 - Psychotropic drug monitoring/PRN use: the facility failed to consider gradual dose reduction for R#20's antidepressants and failed to monitor and document behaviors and side effects related to antipsychotic use.
F 0812 - Food procurement/temperature: the facility served hot foods that were below required holding temperatures on the steam table (turkey cutlets with gravy 133°F, pureed egg noodles 120°F) and reheated them.
F 0880 - Infection prevention and control: toilet hats, urinals and bedpans were stored unbagged/unlabeled and a urinal with residue was hung on a grab bar in shared bathrooms, creating sanitation/infection control concerns.

Inspection Report — Aug 10, 2018

Life Safety
Date: Aug 10, 2018

Visit Reason
Review of the Emergency Preparedness plan and a Life Safety Code survey to assess compliance with NFPA 101 and emergency preparedness requirements.

Findings
The facility was found in substantial compliance with Emergency Preparedness and Life Safety Code requirements; no deficiencies were cited.

Inspection Report — May 31, 2018

Complaint Investigation
Date: May 31, 2018

Visit Reason
Abbreviated/Partial Extended Survey to investigate complaints #GA00188548 and #GA00188571.

Complaint Details
Complaints #GA00188548 and #GA00188571 were unsubstantiated.
Findings
An Abbreviated/Partial Extended Survey investigating complaints #GA00188548 and #GA00188571 was conducted on May 31, 2018. The complaints were unsubstantiated.

Inspection Report — Dec 28, 2017

Follow-Up
Date: Dec 28, 2017

Visit Reason
A revisit survey was conducted on December 28, 2017.

Findings
All deficiencies cited as a result of October 24, 2017 Revisit Survey were found to be corrected as of December 1, 2017.

Inspection Report — Oct 25, 2017

Follow-Up
Date: Oct 25, 2017

Visit Reason
On 10/25/2017 a Follow-Up Survey was conducted by this FSCO.

Findings
On this follow-up survey it was noted that all previously cited survey tags have been corrected.

Inspection Report — Oct 24, 2017

Follow-Up
Date: Oct 24, 2017

Visit Reason
Revisit survey conducted 10/23/2017 through 10/24/2017 for the Recertification survey of 9/4/2017.

Findings
The facility was cited for 2 federal deficiencies for failure to monitor privacy curtains and for ineffective administration related to implementation of the Plan of Correction.

Deficiencies (2)
F 0460 - Bedrooms assure full visual privacy: the facility failed to monitor privacy curtains for appropriate size/length and curtain tracks as required by the Plan of Correction, with documentation missing for multiple dates in September and October 2017, potentially affecting all 73 residents.
F 0490 - Effective administration/resident well-being: the facility failed to ensure its Plan of Correction was fully implemented related to monitoring privacy curtains, failing to monitor as required which could affect all 73 residents.

Inspection Report — Sep 5, 2017

Life Safety
Date: Sep 5, 2017

Visit Reason
Life Safety Code survey to determine compliance with 42 CFR Subpart 483.70(a) and NFPA 101 Life Safety Code.

Findings
The facility was cited for failing to conduct sensitivity testing on smoke detectors (K 0345), which could place residents at risk in the event of fire.

Deficiencies (1)
K 0345 - NFPA 101 Fire Alarm System - Testing and Maintenance: during record review with Staff M on 09/05/2017 between 1:00 PM and 4:00 PM, there were no records of sensitivity testing being conducted on the smoke detectors.

Inspection Report — Sep 4, 2017

Routine
Date: Sep 4, 2017

Visit Reason
Licensure survey to determine compliance with State Long Term Care Requirements.

Findings
The facility failed to ensure that a comprehensive care plan was created related to hypertension and the administration of blood pressure medications for one resident (Resident #51).

Deficiencies (5)
F 0279 - Develop comprehensive care plans: the facility failed to ensure a comprehensive care plan was created for hypertension and the administration of blood pressure medications for Resident #51.
F 0282 - Services by qualified persons/per care plan: the facility failed to follow care plans and administer sliding-scale insulin as ordered for Residents #22 and #76.
F 0309 - Provide care/services for highest well being: the facility failed to implement an active DNR order upon death for Resident #18 and did not ensure physician-ordered parameters for blood pressure medications were followed for Resident #51 or that sliding-scale insulin was administered per orders for Residents #22 and #76.
F 0371 - Food procure, store/prepare/serve sanitary: kitchen refrigeration and sanitation practices were deficient, including incorrect temperatures (e.g., Supplement refrigerator 60°F, Vegetable freezer 20°F, thaw-out unit issues), missing/incorrect logs, lack of sanitizer testing and staff training, and equipment problems.
F 0460 - Bedrooms assure full visual privacy: privacy curtains did not provide full visual privacy in two rooms (room 60 bed B had no curtain and room 15 bed B had a short curtain).
Report Facts
: 29 : 30 : 7

Inspection Report — Mar 15, 2017

Complaint Investigation
Date: Mar 15, 2017

Visit Reason
Complaint survey conducted on 03/15/17 to investigate complaint #GA00165784 to determine compliance with Federal and State Long Term regulations (42 CFR, Part 483, Subpart B) for Long Term Care Facilities.

Complaint Details
Complaint GA00165784 was unsubstantiated with no regulatory violations cited.
Findings
No deficiencies were cited as a result of the complaint survey.

Viewing

Loading inspection reports...