Inspection Report — Apr 18, 2024
Life Safety
Date: Apr 18, 2024
Visit Reason
Federal CMS-2567 Life Safety and Emergency Preparedness statements and Missouri Department of Health and Senior Services State Form licensure survey; the survey type is not stated.
Findings
Fourteen federal deficiencies (Emergency Preparedness and Life Safety) and nine Missouri state licensure deficiencies were cited. Main topics included an outdated Emergency Operations Plan, smoke barrier and fire/smoke door deficiencies, delayed-egress door issues, emergency lighting and generator testing deficiencies, sprinkler supervisory signal and extinguisher inspection failures, deficiencies in fire drill records and smoking area/ashtray disposal.
Deficiencies (9)
19 CSR 30-85.012(79) LSC Edition Required per Date of Fac Plan: See the deficiencies cited at K161, K222, K363, K761, K918, K920.
19 CSR 30-85.022(4) Hazardous Areas: See the deficiency cited at K321.
19 CSR 30-85.022(8)(D) Fire Extinguisher UL/FM, Monthly Check: Fire Extinguishers: See the deficiency cited at K355.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Sprinkler System: See the deficiency cited at K352.
19 CSR 30-85.022(25) Emergency Lighting: This emergency lighting system shall be equipped with an automatic transfer switch and required testing documentation; See the deficiency cited at K291.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Each smoke section shall be separated by one-hour fire-rated walls and doors; See the deficiency cited at K372.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Designated smoking areas shall have ashtrays of noncombustible material; See the deficiency cited at K741.
19 CSR 30-85.022(33)(A) Fire Drill/Emergency Preparedness - Plans: Fire Drills and Emergency Preparedness: Based on interview and record review, the facility failed to have documentation of an annual consultation with the local fire unit; See the deficiency cited at K712.
19 CSR 30-85.022(33)(F) Fire Drill Records: The facility shall keep a record of all fire drills including the simulated resident evacuation; See the deficiency cited at K712.
Inspection Report — Feb 9, 2024
Routine
Date: Feb 9, 2024
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Three deficiencies: two federal findings for inaccurate resident assessments and for failure to ensure residents were free from accident hazards/receive adequate supervision resulting in a missing resident, and one state licensure citation for nursing care per resident condition referencing the missing resident finding.
Deficiencies (1)
19 CSR 30-85.042(66) Nursing Care per Res Condition: See the deficiency cited at F689.
Report Facts
residents sampled: 3
Inspection Report — Jan 3, 2024
Routine
Date: Jan 3, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Five deficiencies were cited: three federal health deficiencies for failure to notify responsible parties of a change in condition/pressure ulcer, failure to ensure a resident was free from abuse/neglect, and inadequate RN coverage; and two Missouri state deficiencies corresponding to RN staffing requirements and notification of responsible party for changes in condition. Past noncompliance was noted.
Deficiencies (2)
19 CSR 30-85.042(35)(B) Licensed Nursing Requirements; Skilled Nursing Facility: See the deficiency cited at F727.
19 CSR 30-85.042(79) Notify Responsible Party-Change in Condition: See the deficiency cited at F580.
Report Facts
residents sampled: 6
Inspection Report — Jun 9, 2023
Complaint Investigation
Date: Jun 9, 2023
Visit Reason
Federal CMS-2567 health surveys and Missouri Department of Health and Senior Services State Form licensure surveys; the file contains a complaint investigation (complaint numbers MO00218376, MO00218207, MO00218442, MO00219500, MO00220214).
Complaint Details
Complaint numbers cited in the file include MO00218376, MO00218207, MO00218442, MO00219500, and MO00220214. The documents do not state whether the allegations were substantiated.
Findings
4 federal CMS-2567 deficiencies addressing environment/housekeeping, medication administration, pest control, and resident telephone access, and 7 Missouri state licensure deficiencies addressing nursing care, availability of towels/linens, floor and wall cleanliness/repair, garbage/rodent control, and telephone privacy.
Deficiencies (7)
19 CSR 30-85.042(66) Nursing Care per Res Condition: See the deficiency cited at F658.
19 CSR 30-85.042(87) Towels Available for Res Use: See the deficiency cited at F584.
19 CSR 30-87.020(12) Floor Surfaces: See the deficiency cited at F584.
19 CSR 30-87.020(15) Walls/Ceilings/Doors/Windows Clean: See the deficiency cited at F584.
19 CSR 30-87.020(37) Dispose of Garbage-Prevent Odors/Bugs: See the deficiency cited at F584.
19 CSR 30-87.020(39) Inspect/Rodent Control: See the deficiency cited at F925.
19 CSR 30-88.010(33) Telephone-Private Calls: See the deficiency cited at F576.
Report Facts
residents affected: 5
residents sampled: 14
residents affected: 1
residents affected: 4
sample size: 20
Inspection Report — Dec 8, 2022
Life Safety
Date: Dec 8, 2022
Visit Reason
Federal CMS-2567 life safety survey (K-tag life safety) and Missouri Department of Health and Senior Services State Form pages are included; the file also references a complaint investigation (MO00210731).
Complaint Details
Complaint MO00210731 is referenced; the documentation notes the complaint investigation determined the violation to be at an imminent danger (Class I) level and that corrective action was implemented.
Findings
Seven deficiencies were cited: four federal K-tag life safety deficiencies involving fire alarm and sprinkler system testing, maintenance, out-of-service and fire-watch requirements, and three Missouri 19 CSR state citations that refer to those same fire alarm/sprinkler issues.
Deficiencies (3)
19 CSR 30-85.022(10)(H) Fire Alarm System-Out of Service > than 4hrs: See the deficiency cited at K346.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: See the deficiency cited at K353.
19 CSR 30-85.022(11)(E) Sprinkler System Out of Service More Than 4hr: See the deficiency cited at K354.
Report Facts
days fire alarm was out of service: 11
days sprinkler system not fully functional: 29
Inspection Report — Sep 9, 2022
Routine
Date: Sep 9, 2022
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Seventeen deficiencies were cited: nine federal health deficiencies addressing privacy, assessment accuracy, care planning, skin/pressure ulcer care, accident prevention/fall risk, tube feeding management, medication errors, food safety, and infection control; and eight Missouri state licensure deficiencies referencing medication safety, protective oversight/voluntary leave, nursing care, pressure sore prevention/treatment, infection control, food storage/containers and equipment cleaning, and resident dignity/privacy.
Deficiencies (8)
19 CSR 30-85.042(46) Safe/Effective Medication System: See deficiency cited at F759.
19 CSR 30-85.042(65) Protective Oversight, Voluntary Leave: See deficiency cited at F689.
19 CSR 30-85.042(66) Nursing Care per Res Condition: See deficiency cited at F693.
19 CSR 30-85.042(74) Pressure Sore Prevention/Treatment: See deficiency cited at F686.
19 CSR 30-85.042(77) Infection Control/Communicable Disease: See deficiency cited at F880.
19 CSR 30-87.030(14) Food-Clean Containers, Storage, Covers: See deficiency cited at F812.
19 CSR 30-87.030(52) Equipment-Cleaning/Sanitizing: See deficiency cited at F812.
19 CSR 30-88.010(29) Dignity/Privacy: See deficiency cited at F583.
Report Facts
sample_size: 18
residents_with_pressure_ulcers: 10
medication_administration_opportunities: 26
medication_errors: 2
Inspection Report — Sep 9, 2022
Life Safety
Date: Sep 9, 2022
Visit Reason
CMS-2567 life safety (Life Safety Code) survey and Missouri Department of Health and Senior Services State Form are included; the survey type is not stated.
Findings
Eight federal life safety deficiencies were cited addressing egress signage, self-closing and corridor doors, sprinkler maintenance and testing, electrical/utilities, HVAC, smoking area maintenance, and unsecured gas cylinders; five Missouri state deficiencies cited hazardous areas, sprinkler testing/maintenance, ashtray disposal, building construction/maintenance and electrical wiring issues.
Deficiencies (5)
19 CSR 30-85.022(4) Hazardous Areas: See the deficiency cited at K223.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: See the deficiency cited at K353.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: See the deficiency cited at K741.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: See the deficiencies cited at K200, K363, K521 and K922.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: See the deficiency cited at K511.
Report Facts
smoke compartments: 7
corridor doors with impediments observed: 4
Inspection Report — Mar 5, 2020
Life Safety
Date: Mar 5, 2020
Visit Reason
Federal CMS-2567 health and life safety survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated in the forms.
Findings
Seventeen deficiencies were cited across federal (10 life-safety/emergency preparedness) and Missouri state (7) forms. Main topics include emergency preparedness training, means of egress/exit signage and delayed-egress doors, sprinkler system maintenance and out-of-service notifications, smoke barrier construction and fire door closures, fire drill completeness/records, and electrical/generator testing and receptacle testing.
Deficiencies (7)
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: See the deficiency cited at K353.
19 CSR 30-85.022(11)(E) Sprinkler System Out of Service More Than 4hr: See the deficiency cited at K354.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: See the deficiencies cited at K372 and K374.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: See the deficiency cited at K712.
19 CSR 30-85.022(33)(F) Fire Drill Records: The facility failed to maintain required fire drill records as evidenced by missing documentation of drill times, transmission of alarm, conditions of the simulated emergency and drill outcomes; see related findings.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: See the deficiencies cited at K200, K222 and K918.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: See the deficiency cited at K914.
Report Facts
number of smoke compartments affected (one stated): 1
number of smoke compartments affected (five stated): 5
number of smoke compartments affected (two stated): 2
18 CMS Surveys
Inspection Report — Sep 9, 2025
Routine
Date: Sep 9, 2025
Visit Reason
The inspection was conducted to assess the facility's compliance with maintaining a safe, clean, comfortable, and homelike environment for residents, specifically focusing on pest control and maintenance issues.
Findings
The facility failed to maintain adequate pest control in resident rooms, with multiple ants observed in Resident #4's room and brown droppings (rat feces) behind Resident #5's bed. Additionally, an air conditioning unit leak caused wall discoloration and damage in Resident #4's room. Maintenance logs were incomplete, and pest control measures were insufficiently documented or effective.
Deficiencies (3)
Failure to maintain adequate pest control in resident rooms, including presence of ants and pest droppings.
Failure to notice and repair air conditioning unit leak causing wall discoloration and damage.
Incomplete maintenance logs and inadequate pest control documentation and follow-up.
Report Facts
Sample size: 12
Work order date: 81825
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Licensed Practical Nurse A | Licensed Practical Nurse (LPN) | Interviewed regarding awareness of ants in Resident #4's room |
| Certified Medication Technician B | Certified Medication Technician (CMT) | Interviewed about reporting ants in Resident #4's room |
| Housekeeping Manager | Interviewed about maintenance and pest control issues, observed conditions in Resident #4's room | |
| Director of Nursing | Director of Nursing (DON) | Interviewed about maintenance logs and pest control priorities |
| Assistant Director of Nursing | Assistant Director of Nursing (ADON) | Interviewed about housekeeping responsibilities and pest control |
Inspection Report — Aug 6, 2025
Complaint Investigation
Date: Aug 6, 2025
Visit Reason
The inspection was conducted due to an allegation of abuse by a Certified Nurse Aide (CNA A) against Resident #3, who reported being roughed up by the CNA on 7/31/25.
Complaint Details
The complaint investigation was substantiated with findings that CNA A was not removed immediately after the resident alleged abuse on 7/31/25 and staff failed to notify the Administrator and Director of Nursing promptly. The resident provided a written statement and multiple staff statements were collected. The resident was diagnosed with multiple conditions but had no cognitive impairment. The facility initiated interventions including staff in-service and social services follow-up.
Findings
The facility failed to ensure residents were free from potential abuse when CNA A was not immediately removed after the allegation and continued to provide care until the end of the shift. Staff also failed to promptly notify the Administrator and Director of Nursing. The investigation included multiple staff and resident interviews and review of statements, revealing inconsistent accounts but no physical evidence of injury.
Deficiencies (1)
Failure to remove CNA A immediately after abuse allegation and failure to notify Administrator and Director of Nursing promptly.
Report Facts
Date of alleged abuse: Jul 31, 2025
Date of investigation: Aug 1, 2025
Employees mentioned
| Name | Title | Context |
|---|---|---|
| CNA A | Certified Nurse Aide | Accused staff member in abuse allegation |
| LPN C | Licensed Practical Nurse | Staff member who took statements and was involved in investigation |
| ADON | Assistant Director of Nursing | Interviewed regarding proper procedures for abuse allegations |
| DON | Director of Nursing | Notified late about the abuse allegation |
Inspection Report — May 1, 2025
Date: May 1, 2025
Visit Reason
The inspection was conducted to evaluate the facility's compliance with professional standards of care, specifically regarding the timely processing and administration of ordered narcotic medication (Tramadol) to residents.
Findings
The facility failed to ensure timely processing and administration of Tramadol 50 mg for Resident #1, resulting in 6 missed doses due to delays in pharmacy processing and lack of signed prescriptions. Staff documented medication administration when the medication was not delivered, and the facility lacked a protocol to ensure timely prescription signing and medication availability.
Deficiencies (3)
Failure to ensure ordered Tramadol 50 mg was processed timely by the pharmacy, resulting in 6 missed doses for Resident #1.
Staff documented medication administration when the medication was not delivered to the facility.
Lack of facility protocol to ensure signed prescriptions for narcotic medications are received timely by the pharmacy.
Report Facts
Residents present: 76
Missed doses: 6
Quantity: 6
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Licensed Practical Nurse A | Licensed Practical Nurse | Interviewed regarding difficulty accessing e-kit for narcotics and medication order processing |
| Director of Nursing | Interviewed about delays in narcotic medication administration and facility protocols |
Inspection Report — Nov 22, 2024
Date: Nov 22, 2024
Visit Reason
The inspection was conducted to assess compliance with regulatory requirements related to resident privacy, safety, and the environment at Amberwood Estates Nursing and Rehabilitation.
Findings
The report identified deficiencies related to maintaining residents' personal and medical records confidentiality, ensuring a safe, clean, and homelike environment, and providing adequate supervision to prevent accidents. All deficiencies were noted as causing minimal harm or potential for actual harm affecting a few or some residents.
Deficiencies (3)
Keep residents' personal and medical records private and confidential.
Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Inspection Report — Sep 19, 2024
Routine
Date: Sep 19, 2024
Visit Reason
Routine inspection of Amberwood Estates Nursing and Rehabilitation to assess compliance with resident privacy, water temperature safety, abuse reporting, wound care, fall investigations, and overall facility safety.
Findings
The facility was found deficient in maintaining resident privacy and confidentiality, ensuring appropriate water temperatures, timely reporting and investigating abuse allegations, providing adequate wound care and assessments, and conducting thorough fall investigations. Specific issues included exposure of resident medical information, use of personal devices for sending prescriptions, water temperatures exceeding safe limits, incomplete abuse and drug diversion investigations, presence of maggots in a resident's wound, and incomplete fall documentation.
Deficiencies (5)
Failure to maintain privacy and confidentiality of resident medical information, including unsecured shred bins and use of personal devices to send prescriptions.
Failure to maintain appropriate water temperatures throughout the facility, with some rooms having water temperatures exceeding safe limits.
Failure to timely report and thoroughly investigate allegations of physical abuse and misappropriation of property.
Failure to ensure weekly wound assessments and ordered treatments were performed, resulting in maggots found in a resident's wound and brief.
Failure to ensure complete and thorough investigation and documentation after a resident fall, including lack of witness statements and neuro checks.
Report Facts
Sample size: 16
Water temperature: 136.5
Water temperature: 141
Missed wound care treatments: 11
Missed wound care treatments: 17
Missed wound care treatments: 10
Missed wound care treatments: 8
Missed wound care treatments: 11
Missed wound care treatments: 3
Missed wound care treatments: 4
Missed wound care treatments: 7
Employees mentioned
| Name | Title | Context |
|---|---|---|
| LPN C | Licensed Practical Nurse | Named in allegation of drug diversion and misappropriation of medications |
| LPN A | Licensed Practical Nurse | Named in privacy violation for using personal device and email to send resident prescription |
| Administrator A | Administrator | Reported drug diversion allegation and terminated LPN C |
| Administrator B | Administrator | Current administrator interviewed regarding investigations and facility policies |
| DON | Director of Nursing | Interviewed regarding wound care, fall investigations, and abuse reporting |
| SSD | Social Services Director | Interviewed regarding abuse allegations and resident care |
| HRD | Human Resources Director | Interviewed regarding drug diversion allegation and investigations |
| LPN M | Licensed Practical Nurse | Interviewed regarding wound care and assessments |
| LPN N | Licensed Practical Nurse | Interviewed regarding wound care and assessments |
| LPN L | Licensed Practical Nurse | Interviewed regarding wound care and maggot incident |
Inspection Report — Apr 18, 2024
Routine
Date: Apr 18, 2024
Visit Reason
The inspection was a routine regulatory survey to assess compliance with healthcare facility regulations, including resident rights, safety, care, and medication management.
Findings
The facility had multiple deficiencies including failure to maintain resident dignity and privacy, inadequate promotion of resident self-determination, unsafe and non-functional bathroom equipment, failure to prevent resident-to-resident abuse, inadequate assistance with activities of daily living including showers, failure to prevent skin impairments, lack of restorative nursing services, unsafe resident handling and transfers, incomplete smoking assessments, malfunctioning exit door alarms with inadequate staff response, missing dialysis orders and communication, insufficient staffing, failure to notify physicians of pharmacy recommendations, lack of gradual dose reductions for psychotropic medications, improper medication storage and labeling, inaccurate medication administration documentation, failure to follow infection control practices, and non-functional call light system for a resident.
Deficiencies (15)
Failure to maintain dignity and provide personal privacy for Resident #71 by not covering catheter drainage bag visible from hallway.
Failure to promote and facilitate resident self-determination for residents dependent on staff for transfer assistance and showers.
Failure to ensure functional bathroom toilet, lights, call light, and water temperature for multiple residents.
Failure to protect residents from physical abuse in a resident-to-resident altercation resulting in injury.
Failure to ensure residents who require assistance with activities of daily living received showers as per personal needs.
Failure to ensure a resident at risk for skin injury did not develop skin impairment and failure to report skin impairment to nurse.
Failure to ensure residents with limited mobility received appropriate restorative nursing services and equipment.
Failure to ensure bed rail assessment and fall assessments with new interventions for Resident #71; failure to ensure safe mechanical lift transfers for three residents; failure to complete smoking assessments for two residents; failure to respond timely to exit door alarm.
Failure to post nurse staffing information daily including total number and actual hours worked for licensed and unlicensed staff.
Failure to notify attending physician about pharmacy medication regimen review recommendations and follow-up actions for Resident #71.
Failure to attempt or document gradual dose reduction for psychotropic medications for Residents #17 and #19.
Failure to ensure drugs and biologicals were labeled and stored properly; presence of expired and undated medications; unsafe medication room refrigerator setup.
Failure to accurately document medication administration when medication was not available for Resident #38.
Failure to follow infection control practices during personal care for Resident #41 and during medication administration for Resident #23.
Failure to provide a working call light system for Resident #36.
Report Facts
Residents affected: 21
Deficiencies cited: 15
Resident count on 300 hall: 26
Nurse Aide Hours Per Resident Day: 90
Nurse Aide Hours Per Resident Day: 120
Licensed Nurse Hours Per Resident Day: 16
Licensed Nurse Hours Per Resident Day: 24
Registered Nurse Hours Per Resident Day: 8
Registered Nurse Hours Per Resident Day: 16
Employees mentioned
| Name | Title | Context |
|---|---|---|
| LPN K | Licensed Practical Nurse | Named in medication administration and infection control findings |
| LPN C | Licensed Practical Nurse | Named in staffing and mechanical lift transfer findings |
| CNA L | Certified Nursing Assistant | Named in staffing and shower assistance findings |
| CNA D | Certified Nursing Assistant | Named in bed mobility and staffing findings |
| Regional Nurse Consultant | Named in multiple findings including staffing, medication, and infection control | |
| Maintenance Director | Named in door alarm and call light maintenance findings | |
| ADON | Assistant Director of Nursing | Named in medication and staffing findings |
| CMT J | Certified Medication Technician | Named in medication storage findings |
| LPN A | Licensed Practical Nurse | Named in catheter care observation |
| CNA F | Certified Nursing Assistant | Named in mechanical lift transfer observation |
Inspection Report — Apr 18, 2024
Routine
Date: Apr 18, 2024
Visit Reason
The inspection was conducted to assess compliance with regulatory requirements related to resident care, safety, abuse prevention, activities of daily living assistance, and staffing adequacy at Amberwood Estates Nursing and Rehabilitation.
Findings
The facility was found deficient in maintaining functional bathroom equipment and call lights, preventing resident abuse, providing adequate assistance with activities of daily living including showers, and maintaining sufficient nursing staff to meet resident needs. Several residents experienced issues such as clogged toilets, non-functional call lights, inadequate showering, and insufficient staff support for care and safety.
Deficiencies (4)
Failure to ensure functional bathroom toilet, lights, call lights, and comfortable water temperature for residents.
Failure to protect residents from physical abuse during a resident-to-resident altercation resulting in injury.
Failure to provide adequate assistance with activities of daily living, including showers, for multiple residents.
Failure to maintain appropriate and competent nursing staff to adequately provide resident care and meet resident needs.
Report Facts
Sample size: 21
Residents affected: 8
Residents affected: 3
Residents affected: 4
Registered Nurse Hours per Resident Day: 8
Registered Nurse Hours per Resident Day: 16
Licensed Nurse Hours per Resident Day: 16
Licensed Nurse Hours per Resident Day: 24
Nurse Aide Hours per Resident Day: 90
Nurse Aide Hours per Resident Day: 120
Total Nursing Hours per Resident Day: 112
Total Nursing Hours per Resident Day: 160
Employees mentioned
| Name | Title | Context |
|---|---|---|
| CNA G | Certified Nurse Aide | Mentioned in relation to hot water issue and staffing concerns |
| Maintenance Director | Mentioned regarding maintenance and equipment inspections | |
| CNA I | Certified Nurse Aide | Mentioned regarding call light functionality and staffing |
| LPN C | Licensed Practical Nurse | Mentioned regarding staffing shortages and medication passing |
| CNA L | Certified Nurse Aide | Mentioned regarding shower assistance and staffing |
| Regional Nurse Consultant | Mentioned regarding expectations for resident care and staffing | |
| Social Services Director | Mentioned regarding investigation of resident altercation | |
| Administrator | Mentioned regarding resident abuse and staffing | |
| Director of Nursing | Mentioned regarding resident abuse and staffing | |
| CNA D | Certified Nurse Aide | Mentioned regarding resident repositioning and staffing |
| LPN N | Licensed Practical Nurse | Mentioned regarding resident care and communication with CNA |
Inspection Report — Apr 18, 2024
Life Safety
Date: Apr 18, 2024
Visit Reason
Federal CMS-2567 Life Safety and Emergency Preparedness statements and Missouri Department of Health and Senior Services State Form licensure survey; the survey type is not stated.
Findings
Fourteen federal deficiencies (Emergency Preparedness and Life Safety) and nine Missouri state licensure deficiencies were cited. Main topics included an outdated Emergency Operations Plan, smoke barrier and fire/smoke door deficiencies, delayed-egress door issues, emergency lighting and generator testing deficiencies, sprinkler supervisory signal and extinguisher inspection failures, deficiencies in fire drill records and smoking area/ashtray disposal.
Deficiencies (14)
E004 Develop EP Plan, Review and Update Annually: Based on interview and record review, the facility failed to update their Emergency Operations Plan (EOP) at least annually; the EOP contained outdated names and contacts and other items.
K161 Building Construction Type and Height: Based on observation and interview, the facility failed to maintain appropriate construction standards and continuous walls protecting studs and interstitial spaces, affecting multiple smoke compartments.
K222 Egress Doors: Based on observation and interview, delayed-egress doors and exit doors were not maintained and did not operate or release as required, with sandbags and nonfunctioning delayed-egress devices observed.
K291 Emergency Lighting: Based on observation, interview and record review, the facility failed to ensure emergency lighting was tested monthly and maintained; battery-operated emergency lights did not operate during testing and documentation was incomplete.
K321 Hazardous Areas - Enclosure: Based on observation and interview, the facility failed to maintain hazardous areas with corridor doors equipped with self-closing devices; a beauty shop over 50 square feet lacked a self-closing door.
K352 Sprinkler System - Supervisory Signals: Based on interview and record review, the facility failed to ensure deficiencies identified during sprinkler inspections were corrected in a timely manner; records showed repeated supervisory low air pressure switch failures.
K355 Portable Fire Extinguishers: Based on observation, interview and record review, the facility failed to ensure portable fire extinguishers were maintained and documented monthly; monthly checks were missing for February and March 2024.
K363 Corridor - Doors: Based on observation and interview, corridor doors were not maintained to ensure closing and no impediment to closing, with multiple doors held open or with holes and other damage.
K372 Subdivision of Building Spaces - Smoke Barrier Construction: Based on observation and interview, the facility failed to maintain smoke barrier walls and the functioning of smoke dampers and self-closing barrier access doors.
K712 Fire Drills: Based on interview and record review, the facility failed to ensure fire drills were completed on each shift quarterly; documentation was incomplete for 2023 and early 2024.
K741 Smoking Regulations: Based on observation and interview, the facility failed to dispose of ashtray contents in accordance with NFPA regulations; ashtrays and cigarette butts were observed in the smoking area.
K761 Maintenance, Inspection & Testing - Doors: Based on observation, interview and record review, the facility failed to provide documentation of annual inspection and testing for doors and door assemblies as required.
K918 Electrical Systems - Essential Electric System Maintenance and Testing: Based on observation, interview and record review, the facility failed to properly document weekly generator exercises and monthly load tests and other required generator testing records were missing.
K920 Electrical Equipment - Power Cords and Extension Cords: Based on observation and interview, the facility did not prohibit use of extension cords and power strips in patient care and other areas; multiple extension cords and power strips were observed in several rooms.
Inspection Report — Feb 9, 2024
Routine
Date: Feb 9, 2024
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Three deficiencies: two federal findings for inaccurate resident assessments and for failure to ensure residents were free from accident hazards/receive adequate supervision resulting in a missing resident, and one state licensure citation for nursing care per resident condition referencing the missing resident finding.
Deficiencies (2)
F641 Accuracy of Assessments: The facility failed to accurately complete the Minimum Data Set assessment for a resident as evidenced by review of the resident's discharge MDS and interviews.
F689 Free of Accident Hazards/Supervision/Devices: The facility failed to ensure each resident received adequate supervision and assistance to prevent accidents and failed to immediately report and investigate when a resident did not return to the facility, resulting in a missing resident and documentation deficiencies in leave-of-absence procedures.
Report Facts
residents sampled: 3
Inspection Report — Jan 3, 2024
Routine
Date: Jan 3, 2024
Visit Reason
CMS-2567 federal health survey and Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Five deficiencies were cited: three federal health deficiencies for failure to notify responsible parties of a change in condition/pressure ulcer, failure to ensure a resident was free from abuse/neglect, and inadequate RN coverage; and two Missouri state deficiencies corresponding to RN staffing requirements and notification of responsible party for changes in condition. Past noncompliance was noted.
Deficiencies (3)
F580 Notify of Changes (Injury/Decline/Room, etc.): Based on interview and record review, the facility failed to notify the resident's responsible party after the development of a pressure ulcer for one resident; the sample was six and the census was 90.
F600 Free from Abuse and Neglect: Based on interview and record review, the facility failed to ensure one resident was free from physical abuse when another resident struck the resident in the face with a fork; the sample was six and the census was 90.
F727 RN 8 Hrs/7 days/Wk, Full Time DON: Based on interview and record review, the facility failed to provide a Registered Nurse for eight consecutive hours per day, seven days a week, as staffing sheets showed no RN coverage on several weekends.
Report Facts
residents sampled: 6
Inspection Report — Jul 31, 2023
Routine
Date: Jul 31, 2023
Visit Reason
The inspection was conducted to assess the facility's compliance with residents' rights to reasonable access and privacy in communication methods, specifically regarding telephone use and reception of phone calls after hours.
Findings
The facility failed to ensure residents had reasonable access to a telephone in a private area and failed to ensure phone calls from outside the facility were received after 8:00 P.M. The cordless phone for residents was not working, and the corded phone was located in a non-private nurse's station area. Additionally, phone calls to the facility after 8:00 P.M. were not answered due to lack of receptionist coverage and unplugged phone lines.
Deficiencies (2)
Failed to ensure residents had reasonable access to a telephone in a private area for making calls.
Failed to ensure phone calls from outside the facility were received after 8:00 P.M.
Report Facts
Sample size: 20
Phone call duration: 11
Receptionist coverage hours: 12
Phone ring duration: 2
Phone ring duration: 1
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Certified Nurse Aide A | CNA | Moved corded phone for resident use and described phone access issues |
| Certified Nurse Aide C | CNA | Described phone usage and issues with cordless phone |
| Licensed Practical Nurse D | LPN | Reported cordless phone not working and lack of other phones for residents |
| Receptionist B | Receptionist | Described phone call handling and receptionist coverage hours |
| Director of Nursing | DON | Discussed phone usage and issues with cordless phone and after-hours call reception |
| Administrator | Administrator | Commented on privacy concerns and phone line issues |
Inspection Report — Jun 9, 2023
Complaint Investigation
Date: Jun 9, 2023
Visit Reason
Federal CMS-2567 health surveys and Missouri Department of Health and Senior Services State Form licensure surveys; the file contains a complaint investigation (complaint numbers MO00218376, MO00218207, MO00218442, MO00219500, MO00220214).
Complaint Details
Complaint numbers cited in the file include MO00218376, MO00218207, MO00218442, MO00219500, and MO00220214. The documents do not state whether the allegations were substantiated.
Findings
4 federal CMS-2567 deficiencies addressing environment/housekeeping, medication administration, pest control, and resident telephone access, and 7 Missouri state licensure deficiencies addressing nursing care, availability of towels/linens, floor and wall cleanliness/repair, garbage/rodent control, and telephone privacy.
Deficiencies (4)
F 584 Safe/Clean/Comfortable/Homelike Environment: Based on observation, interview and record review, the facility failed to provide a clean, comfortable, and homelike environment for all residents when the staff did not keep the floors in resident rooms and common areas clean, hallway walls had missing paint and ceiling sections were missing leaving drywall exposed, there was an insufficient amount of towels and linens maintained in good condition, the lawn was not well maintained, beverages were provided in disposable plastic cups at mealtimes, and garbage was stored in a pile in the dining room where residents eat.
F 658 Services Provided Meet Professional Standards: Based on interview and record review, the facility failed to ensure physician orders were followed when staff did not administer medications as ordered and/or document medications were administered or refused for one of 14 sampled residents (Resident #3).
F 925 Maintains Effective Pest Control Program: Based on observation, interview and record review, the facility failed to maintain an effective pest control program to prevent mice in resident rooms and common areas, with evidence of mice/pellets and gaps allowing pest entry, affecting four of 14 sampled residents.
F 576 Right to Forms of Communication w/ Privacy: Based on observation, interview and record review, the facility failed to ensure residents had reasonable access to the use of a telephone in a place in the facility where calls can be made without being overheard, with phones at the nurse's station not consistently available or functional and residents having limited private access to make or receive calls.
Report Facts
residents affected: 5
residents sampled: 14
residents affected: 1
residents affected: 4
sample size: 20
Inspection Report — Mar 24, 2023
Routine
Date: Mar 24, 2023
Visit Reason
The inspection was conducted to evaluate compliance with discharge planning, activities of daily living assistance, elopement prevention, and overall resident care and safety at Amberwood Estates Nursing and Rehabilitation.
Findings
The facility failed to ensure an effective discharge planning process addressing resident goals and needs, including caregiver support and referrals. Residents who were unable to carry out activities of daily living did not consistently receive showers as scheduled or desired. The facility also failed to provide adequate supervision to prevent an elopement, resulting in a resident being missing for over 21 hours and found with hypothermia. Documentation and communication deficiencies were noted in discharge planning and shower scheduling.
Deficiencies (3)
Failure to ensure a discharge planning process addressing discharge goals, caregiver support, and referrals for residents.
Failure to provide care and assistance to perform activities of daily living, including showers, as scheduled or desired.
Failure to ensure adequate supervision to prevent elopement, resulting in a resident missing for over 21 hours and found with hypothermia.
Report Facts
Residents affected: 2
Residents affected: 2
Residents affected: 1
Missed showers: 20
Missed showers: 19
Resident missing duration (hours): 21
Resident body temperature (F): 84
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Nurse A | Provided information about discharge planning and resident care | |
| Social Services Director (SSD) | Social Services Director | Responsible for discharge planning and arranging services |
| Administrator | Administrator | Provided statements regarding discharge planning and shower scheduling |
| CNA G | Certified Nursing Assistant | Provided information about shower scheduling and resident care |
| CNA F | Certified Nursing Assistant | Provided information about shower scheduling and resident care |
| Nurse E | Provided information about shower scheduling and resident care | |
| Director of Nurses (DON) | Director of Nurses | Discussed shower scheduling and documentation issues |
| Hospital Staff B | Provided information about resident hospital admission | |
| Receptionist C | Receptionist | Observed resident leaving facility and reported to unit manager |
| Certified Nursing Assistant (CNA) D | Certified Nursing Assistant | Provided information about resident presence and elopement |
| Certified Medication Technician (CMT) B | Certified Medication Technician | Reported medication administration and resident LOA status |
Inspection Report — Dec 8, 2022
Life Safety
Date: Dec 8, 2022
Visit Reason
Federal CMS-2567 life safety survey (K-tag life safety) and Missouri Department of Health and Senior Services State Form pages are included; the file also references a complaint investigation (MO00210731).
Complaint Details
Complaint MO00210731 is referenced; the documentation notes the complaint investigation determined the violation to be at an imminent danger (Class I) level and that corrective action was implemented.
Findings
Seven deficiencies were cited: four federal K-tag life safety deficiencies involving fire alarm and sprinkler system testing, maintenance, out-of-service and fire-watch requirements, and three Missouri 19 CSR state citations that refer to those same fire alarm/sprinkler issues.
Deficiencies (4)
K345 Fire Alarm System - Testing and Maintenance: Based on interview and record review, the facility failed to ensure the fire alarm system was maintained and tested in accordance with requirements; records and interviews showed the fire alarm was placed in test/out-of-service modes over multiple days.
K346 Fire Alarm System - Out of Service: The facility failed to implement an approved fire watch and failed to notify appropriate parties when the fire alarm system was out of service for an extended period (the system was out of service for 11 days).
K353 Sprinkler System - Maintenance and Testing: The facility failed to maintain the dry-pipe sprinkler system in accordance with NFPA 25; interviews and observations documented lack of a working air compressor, signs of water damage, and incomplete repairs/maintenance.
K354 Sprinkler System - Out of Service: The facility failed to complete an approved fire watch, to tag the sprinkler system, and to notify their property insurance when the sprinkler system was impaired or out of service for an extended period (the sprinkler system was not fully functional for at least 29 days).
Report Facts
days fire alarm was out of service: 11
days sprinkler system not fully functional: 29
Inspection Report — Sep 9, 2022
Routine
Date: Sep 9, 2022
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Seventeen deficiencies were cited: nine federal health deficiencies addressing privacy, assessment accuracy, care planning, skin/pressure ulcer care, accident prevention/fall risk, tube feeding management, medication errors, food safety, and infection control; and eight Missouri state licensure deficiencies referencing medication safety, protective oversight/voluntary leave, nursing care, pressure sore prevention/treatment, infection control, food storage/containers and equipment cleaning, and resident dignity/privacy.
Deficiencies (9)
F583 Personal Privacy/Confidentiality of Records: The facility failed to ensure privacy during perineal/incontinence care for a resident, leaving the resident exposed to the hall and not providing curtain/door privacy.
F641 Accuracy of Assessments: The facility failed to ensure that the resident assessment accurately reflected the resident's status for several sampled residents, with documentation and MDS items not reflecting hospice status, communication ability, or prognosis.
F656 Develop/Implement Comprehensive Care Plan: The facility failed to develop and implement complete, accurate person-centered care plans addressing identified needs for sampled residents, including ADL and toileting interventions.
F686 Treatment/Svcs to Prevent/Heal Pressure Ulcer (Skin Integrity): The facility failed to promote healing and provide ordered wound care for a resident with pressure ulcers and did not ensure appropriate dressing orders and wound follow-up.
F689 Free of Accident Hazards/Supervision/Devices: The facility failed to ensure adequate fall prevention interventions for a resident who was bed bound and experienced falls, and did not implement appropriate interventions documented on the care plan.
F693 Tube Feeding Mgmt/Restore Eating Skills: The facility failed to follow enteral feeding policies and provide accurate labeling and feeding pump management for residents receiving tube feedings, with multiple documentation and practice problems identified.
F759 Free of Medication Errors Rts 5 Prcnt or More: The facility's medication administration practices resulted in a medication error rate above acceptable levels, with observed errors in insulin/patch handling and related deficiencies in medication procedures.
F812 Food Procurement,Store/Prepare/Serve-Sanitary: The facility failed to maintain food and kitchen equipment under sanitary conditions, including exposed/open food containers in storage and inadequate cleaning/maintenance of kitchen equipment.
F880 Infection Prevention & Control: The facility failed to provide care to prevent the spread of infection for residents during incontinence care, including inadequate hand hygiene, glove changes, and disposal of soiled linen and supplies.
Report Facts
sample_size: 18
residents_with_pressure_ulcers: 10
medication_administration_opportunities: 26
medication_errors: 2
Inspection Report — Sep 9, 2022
Life Safety
Date: Sep 9, 2022
Visit Reason
CMS-2567 life safety (Life Safety Code) survey and Missouri Department of Health and Senior Services State Form are included; the survey type is not stated.
Findings
Eight federal life safety deficiencies were cited addressing egress signage, self-closing and corridor doors, sprinkler maintenance and testing, electrical/utilities, HVAC, smoking area maintenance, and unsecured gas cylinders; five Missouri state deficiencies cited hazardous areas, sprinkler testing/maintenance, ashtray disposal, building construction/maintenance and electrical wiring issues.
Deficiencies (8)
K200 Means of Egress Requirements - Other: The facility failed to maintain proper signage on doors leading to the outside; several doors were not marked with EXIT or 'NO EXIT' signs and some doors were held open or blocked, creating potential egress confusion.
K223 Doors with Self-Closing Devices: The facility failed to ensure doors protecting hazardous areas and enclosures were self-closing and kept closed; some doors did not self-close fully or latch and others were held open or propped, affecting safe compartmentation.
K353 Sprinkler System - Maintenance and Testing: The facility failed to maintain required sprinkler system inspection records and complete quarterly sprinkler inspections since 1/25/22, indicating the sprinkler system was not being inspected as required.
K363 Corridor - Doors: The facility failed to maintain corridor doors so they provided positive latching and closure; multiple corridor doors were propped, had broken or inadequate latching hardware, or did not close and latch properly.
K511 Utilities - Gas and Electric: The facility failed to maintain electrical wiring and devices in safe condition; receptacles and cover plates were loose or separated, items were plugged into power strips, and items were stored near electrical panels.
K521 HVAC: The facility failed to maintain HVAC equipment in proper working order; a refrigerant line was dripping condensation onto the air handler and water was pooling beneath the unit.
K741 Smoking Regulations: The facility failed to maintain designated smoking areas and ashtray disposal; ashcans and lids did not self-close properly, ashtrays and cigarette butts were scattered, and appropriate noncombustible disposal containers were not in place.
K922 Gas Equipment - Other: The facility failed to ensure compressed gas cylinders were secured and stored properly; helium tanks were unsecured, a rolling cart was missing a securing bracket, and tanks could be knocked over.
Report Facts
smoke compartments: 7
corridor doors with impediments observed: 4
Inspection Report — Feb 15, 2022
Routine
Date: Feb 15, 2022
Visit Reason
Routine inspection of Amberwood Estates Nursing and Rehabilitation to assess compliance with healthcare regulations including medication self-administration, resident accommodations, call light functionality, financial management, safety, infection control, and care practices.
Findings
The facility had multiple deficiencies including failure to assess resident ability to self-administer medications, failure to ensure call lights were functional and within reach, improper management of resident funds, inadequate monitoring of personal refrigerators, failure to maintain personal inventory lists, failure to clean tube feeding spillage, water temperature issues, failure to provide scheduled showers, failure to identify and notify physician of resident eye inflammation, failure to reposition residents, incomplete post-fall assessments, improper tube feeding care, medication errors, lack of quality control for blood glucose testing, improper food preparation and storage, infection control lapses, failure to maintain side rails and bed safety, and malfunctioning call light system on the 500 hall.
Deficiencies (19)
Failure to assess resident's ability to safely self-administer medications and failure to have physician orders for bedside inhalers.
Failure to ensure call lights were in working order and within reach for multiple residents.
Failure to ensure resident funds were placed in separate accounts and timely access to funds was not provided.
Failure to monitor and clean personal refrigerators and failure to maintain personal inventory lists for residents.
Failure to clean tube feeding spillage and failure to monitor water temperatures in shower rooms.
Failure to provide scheduled showers and document bathing assistance or refusals for multiple residents.
Failure to identify, assess, and notify physician of eye inflammation and failure to reposition residents as per care plans.
Failure to maintain bed in low position for fall risk resident and failure to complete post-fall neuro checks.
Failure to follow physician orders for tube feeding and dressing changes, including failure to document tube feeding interruptions.
Failure to provide consistent dialysis care including communication with dialysis center and avoiding blood pressure measurements on dialysis arm.
Failure to complete required assessments, obtain consent, and physician orders for side rail use.
Medication error rate of 5% due to incorrect dosing of medications via gastrostomy tube.
Failure to complete quality control checks for blood glucose test machines for three months.
Failure to prepare pureed food according to recipes resulting in inconsistent texture and appearance.
Failure to store, prepare, distribute and serve food safely including unlabeled, expired food and unclean kitchen equipment and floors.
Failure to follow infection control practices including hand hygiene, glove use, cleaning of reusable supplies, and maintaining clean resident areas and urinals.
Failure to complete routine inspections of bed frames, mattresses, and side rails to identify entrapment hazards.
Call light system malfunction on the 500 hall resulting in inability to detect resident calls.
Failure to maintain handrails with missing end caps exposing sharp edges on 200 and 300 halls.
Report Facts
Medication error rate: 5
Resident sample size: 18
Resident funds held in operating account: 49479.87
Expired food item date: Aug 23, 2021
Missing handrail end caps: 18
Employees mentioned
| Name | Title | Context |
|---|---|---|
| Nurse A | Nurse | Mentioned in relation to tube feeding care and medication administration errors. |
| Nurse Manager E | Nurse Manager | Mentioned in relation to medication administration, neuro checks, tube feeding, and side rail use. |
| Nurse D | Nurse | Mentioned in relation to tube feeding care, medication administration, and side rail use. |
| Assistant Director of Nursing | ADON | Mentioned in relation to tube feeding care, side rail assessments, and infection control. |
| Director of Nurses | DON | Mentioned in relation to medication administration, neuro checks, tube feeding, side rail use, and infection control. |
| Dietary Manager | Dietary Manager | Mentioned in relation to pureed food preparation and kitchen cleanliness. |
| Maintenance Director | Maintenance Director | Mentioned in relation to call light system and handrail end caps. |
| Physician H | Physician | Mentioned in relation to resident eye inflammation and tube feeding orders. |
Inspection Report — Mar 5, 2020
Life Safety
Date: Mar 5, 2020
Visit Reason
Federal CMS-2567 health and life safety survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated in the forms.
Findings
Seventeen deficiencies were cited across federal (10 life-safety/emergency preparedness) and Missouri state (7) forms. Main topics include emergency preparedness training, means of egress/exit signage and delayed-egress doors, sprinkler system maintenance and out-of-service notifications, smoke barrier construction and fire door closures, fire drill completeness/records, and electrical/generator testing and receptacle testing.
Deficiencies (10)
E 037 EP Training Program: The facility failed to provide required emergency preparedness training to facility staff on an annual basis; the deficiency had the potential to affect all occupants of the building.
K 200 Means of Egress Requirements - Other: The facility failed to ensure doors that led to the outside (but not to a public way) were identified by signage (no "no exit" signs posted) which could mislead occupants.
K 222 Egress Doors: A delayed-egress exit door at the front lobby did not release automatically with activation of the fire alarm and did not manually reset as required, preventing proper egress.
K 353 Sprinkler System - Maintenance and Testing: The facility failed to maintain required sprinkler system inspection and testing records and lacked an adequate supply of spare sprinkler heads; quarterly/annual inspections were not documented for all required periods.
K 354 Sprinkler System - Out of Service: The facility failed to follow required procedures and notifications when the sprinkler system was impaired/out-of-service (fire watch and DHSS notification issues were noted).
K 372 Subdivision of Building Spaces - Smoke Barrie(r): The facility failed to maintain smoke barriers (holes and penetrations and an unsecured access door) compromising the required smoke compartmentation in multiple areas.
K 374 Subdivision of Building Spaces - Smoke Barrie(r) Doors: The facility failed to ensure smoke barrier doors closed and provided required protection during testing (gaps and doors not closing properly were observed).
K 712 Fire Drills: The facility failed to ensure required fire drills were completed and documented on each shift and at varying times for four of four quarters; drill documentation and transmission of alarm/conditions were incomplete.
K 914 Electrical Systems - Maintenance and Testing: The facility failed to ensure non-hospital grade electrical receptacles in resident sleeping areas were tested annually as required; one resident room was noted with non-hospital grade receptacles not tested.
K 918 Electrical Systems - Essential Electric Syste(m): The facility failed to ensure the emergency generator was exercised/loaded and monthly load tests documented in 2019 as required by standards.
Report Facts
number of smoke compartments affected (one stated): 1
number of smoke compartments affected (five stated): 5
number of smoke compartments affected (two stated): 2