Inspection Reports for
Riverside Nursing &Amp; Rehabilitation Center, LLC
4700 NW CLIFFVIEW DR, RIVERSIDE, MO, 64150-1237
Back to Facility Profile9 Reports
Inspection Report — Apr 10, 2025
Life Safety
Date: Apr 10, 2025
Visit Reason
Federal CMS-2567 Life Safety survey (K-tags) and Missouri Department of Health and Senior Services State Form; the survey is a Life Safety inspection and no complaint numbers are listed.
Findings
Eight deficiencies were cited: four federal life-safety deficiencies involving building construction/fire-resistance penetrations, delayed-egress door locking and signage, smoking-area ashtray disposal, and electrical receptacles/testing; and four Missouri state licensure deficiencies addressing door locks, ashtrays, building maintenance, and electrical wiring/testing.
Deficiencies (4)
19 CSR 30-85.022(16) Door Locks: Refer to K222.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Refer to K741.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Refer to K161.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Refer to K914.
Inspection Report — Apr 25, 2024
Routine
Date: Apr 25, 2024
Visit Reason
Missouri Department of Health and Senior Services State Form; the survey type is not stated.
Findings
Three state deficiencies were cited addressing employee EDL checks, employee tuberculosis screening/infection control, and insufficient surety bond for resident funds.
Deficiencies (3)
19 CSR 30-85.042(19) Employee/Volunteer Not on EDL: Based on interview and record review the facility failed to ensure employees were checked against the Employee Disqualification List; EDL checks were not found for multiple sampled employees.
19 CSR 30-85.042(77) Infection Control/Communicable Disease: Based on interview and record review the facility failed to monitor employee health and complete required two-step tuberculosis screening for multiple sampled employees.
19 CSR 30-88.020(14) Resident Fund Bond Requirements: Based on record review and interview the facility failed to maintain a surety bond sufficient to protect resident funds; the approved bond amount was decreased making the bond insufficient.
Report Facts
sampled employees affected: 4
sampled employees missing second-step TB: 4
average monthly resident trust balance: 60702.77
approved bond amount prior to decrease: 126000
bond amount after decrease: 85000
bond insufficiency amount: 6500
Inspection Report — Feb 29, 2024
Routine
Date: Feb 29, 2024
Visit Reason
Federal health survey (CMS-2567) and Missouri State licensure survey (State Form) are present; the survey type is not stated.
Findings
Two deficiencies were cited: one federal health deficiency regarding staff qualifications and failure to maintain a qualified/licensed administrator, and one Missouri State licensure deficiency for licensed administrator that references the federal finding.
Deficiencies (1)
19 CSR 30-85.042(1) Licensed Administrator: Please refer to F839.
Inspection Report — Nov 20, 2023
Complaint Investigation
Date: Nov 20, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure forms are present in the file; the record cites complaint MO225076, so this is a complaint investigation.
Complaint Details
MO225076 is cited in the file; the forms do not explicitly state whether the complaint allegation was formally substantiated.
Findings
Twelve deficiencies were cited in total: 7 federal health deficiencies addressing care planning, ADL assistance and bathing, quality of care/changes in condition, trauma-informed care, bed rail assessments/entrapment, resident call systems, and sanitary/odor issues; and 5 Missouri state licensure citations covering call system requirements, furniture/equipment comfort and safety, nursing care per resident condition, cleanliness/odor-free requirements, and clinical record documentation. Some findings were noted as previously cited or uncorrected from the 11/20/2023 survey and an Immediate Jeopardy related to quality of care was removed during the onsite review.
Deficiencies (5)
19 CSR 30-85.032(27) Call System Requirements: Refer to F919.
19 CSR 30-85.032(38) Furniture/Equip, Provide Comfort & Safety: Refer to F921.
19 CSR 30-85.042(66) Nursing Care per Res Condition: Refer to F684.
19 CSR 30-85.042(67) Clean, Dry, Odor Free: Refer to F677.
19 CSR 30-85.042(98)(B) Clinical Records - assessment/interventions: Refer to F656 and F699.
Report Facts
residents sampled: 22
Inspection Report — Nov 20, 2023
Life Safety
Date: Nov 20, 2023
Visit Reason
Federal CMS-2567 Life Safety survey and Missouri Department of Health and Senior Services State Form; Life Safety survey (K-tags present).
Findings
Ten deficiencies were cited: five federal Life Safety deficiencies involving vertical opening penetrations, sprinkler system maintenance and testing, corridor wall penetrations, inadequate fire drill scheduling, and unsafe use of electrical/power cords; and five Missouri state rule violations that refer to the Life Safety findings (required corridors, sprinkler inspections, fire drill requirements, facility construction/maintenance, and extension cords/duplex receptacles).
Deficiencies (5)
19 CSR 30-85.012(34) Required Corridors: Please refer to K362.
19 CSR 30-85.022(11)(A) Inspections Completed, Certification Annually: Please refer to K353.
19 CSR 30-85.022(33)(D) Fire Drill Requirements, Evacuation: Please refer to K712.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Please refer to K311 and K362.
19 CSR 30-85.032(37) Extension Cords/Duplex Receptacles: Please refer to K920.
Report Facts
smoke sections affected: 4
smoke sections affected: 3
Inspection Report — May 23, 2023
Routine
Date: May 23, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Seven deficiencies were cited: four federal health deficiencies involving resident rights, environment/housekeeping, comprehensive care planning, and pain management, and three Missouri state licensure deficiencies referencing floor surfaces, wall/ceiling surfaces, and nursing care per resident condition.
Deficiencies (3)
19 CSR 30-85.012(8)4 Floor Surfaces: Please refer to F584.
19 CSR 30-85.022(37) Wall/Ceiling Surface Requirements: Please refer to F584.
19 CSR 30-85.042(66) Nursing Care per Res Condition: Please refer to F697.
Report Facts
residents sampled: 20
Inspection Report — May 23, 2023
Life Safety
Date: May 23, 2023
Visit Reason
Federal Life Safety (CMS-2567) and Missouri state licensure (State Form); life safety survey.
Findings
Twelve deficiencies were cited: seven federal Life Safety Code deficiencies and five Missouri State licensure citations. Findings address egress door locking, emergency lighting, sprinkler system testing/maintenance, corridor wall fire resistance, smoke barrier penetrations, utilities/electrical receptacles, and improper use of power strips/extension cords.
Deficiencies (5)
19 CSR 30-85.022(2)(E) No Fire Hazard: Refer to K511.
19 CSR 30-85.022(16) Door Locks: Please refer to K222.
19 CSR 30-85.022(25) Emergency Lighting: Refer to K291.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Refer to K372.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Refer to K362 and K372.
Report Facts
smoke zones affected: 1
smoke compartments affected: 5
smoke compartments affected: 2
smoke compartments affected: 3
Inspection Report — Nov 4, 2021
Life Safety
Date: Nov 4, 2021
Visit Reason
CMS-2567 federal life safety and emergency preparedness survey pages and Missouri Department of Health and Senior Services State Form licensure pages; life safety.
Findings
27 deficiencies were cited across federal CMS-2567 life-safety/emergency preparedness pages (17 items) and Missouri State Form licensure pages (10 items). Main topics include emergency preparedness subsistence planning, sprinkler system maintenance, exit signage and egress door locking, hazardous area doors and smoke barriers, portable fire extinguisher maintenance, electrical/power strip use and breaker covers, and unsafe smoking/disposing practices.
Deficiencies (10)
19 CSR 30-85.022(2)(E) No Fire Hazard: Refer to K511.
19 CSR 30-85.022(4) Hazardous Areas: Refer to K321.
19 CSR 30-85.022(8)(D) Fire Extinguisher UL/FM, Monthly Check: Refer to K355.
19 CSR 30-85.022(11)(C) Sprinkler System-Test/Maintain: Refer to K353.
19 CSR 30-85.022(16) Door Locks: Refer to K222.
19 CSR 30-85.022(22) Exit Sign Requirements: Refer to K293.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Refer to K372 and K374.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Refer to K161, K362, K363 and K372.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Refer to K511 and K920.
19 CSR 30-85.032(37) Extension Cords/Duplex Receptacles: Refer to K920.
Report Facts
smoke zones affected: 4
sprinkler heads with dust/grease/corrosion in kitchen: 10
Inspection Report — Nov 22, 2019
Life Safety
Date: Nov 22, 2019
Visit Reason
Federal CMS-2567 Life Safety (K-tag) survey and Missouri Department of Health and Senior Services State Form; the survey is a life safety survey.
Findings
There are 14 federal life-safety deficiencies (K-tags) concerning building construction and penetrations between ceiling/attic spaces, smoke barrier walls and doors, egress/exit doors and stairwell storage, emergency and exit lighting, portable fire extinguishers, corridor doors, vertical openings, hazardous area enclosures, smoking/disposal, and electrical power strips and inspections. There are 11 Missouri State Form deficiencies reflecting many of the same issues, including hazardous areas, fire extinguisher monthly checks, exit sign requirements, emergency lighting, vertical shaft requirements, smoke section walls/doors, ashtrays, fire drill/consultation, substantial construction/maintenance, and electrical inspection/certification.
Deficiencies (11)
19 CSR 30-85.022(4) Hazardous Areas: Please refer to K321.
19 CSR 30-85.022(8)(D) Fire Extinguisher UL/FM, Monthly Check: Please refer to K355.
19 CSR 30-85.022(22) Exit Sign Requirements: Please refer to K222.
19 CSR 30-85.022(25) Emergency Lighting: Please refer to K291 and K281.
19 CSR 30-85.022(26) Vertical Shaft Requirements: Please refer to K311.
19 CSR 30-85.022(29) Smoke Section Walls/Doors: Please refer to K372.
19 CSR 30-85.022(32) Ashtrays Noncombustibles/Safe/Disposal: Please refer to K741.
19 CSR 30-85.022(33)(A) Fire Drill/Emergency Preparedness - Plans: Based on interview and record review, the facility failed to have an annual fire department consultation to review the fire and emergency plans.
19 CSR 30-85.032(2) Substantially Constructed/Maintained: Please refer to K225, K372, K374, K363 and K161 for Plan of Correction.
19 CSR 30-85.032(31)(A) Electrical Wiring & Equipment Maintained: Please refer to K920.
19 CSR 30-85.032(31)(B) Electrical System-Certification Every 2 Years: Please refer to K914.
Report Facts
residents affected: 110
residents affected: 14
11 CMS Surveys
Inspection Report — Apr 10, 2025
Life Safety
Date: Apr 10, 2025
Visit Reason
Federal CMS-2567 Life Safety survey (K-tags) and Missouri Department of Health and Senior Services State Form; the survey is a Life Safety inspection and no complaint numbers are listed.
Findings
Eight deficiencies were cited: four federal life-safety deficiencies involving building construction/fire-resistance penetrations, delayed-egress door locking and signage, smoking-area ashtray disposal, and electrical receptacles/testing; and four Missouri state licensure deficiencies addressing door locks, ashtrays, building maintenance, and electrical wiring/testing.
Deficiencies (4)
K161 Building Construction Type and Height: Based on observation and interview, facility staff failed to maintain the fire resistance rating of the walls by not repairing openings; observations included a one inch gap around pipes at the C Hall nurses station and a gap around a sprinkler pipe near the dining exit door.
K222 Egress Doors: Facility staff failed to maintain a door in the path of egress and failed to provide proper documentation concerning how to unlock electronically controlled delayed-egress exit doors; an egress door on the F Hallway with delayed-egress hardware lacked appropriate signage showing the door could be opened within 15 seconds.
K741 Smoking Regulations: Based on observation and interview, the facility failed to ensure staff properly disposed of cigarette butts in two smoking areas; observations showed red metal barrels containing multiple pieces of paper and plastic trash in the patio and C Hallway smoking areas.
K914 Electrical Systems - Maintenance and Testing: Based on interview and record review, facility staff failed to replace receptacles that failed during annual testing of non-hospital grade electrical receptacles in patient sleeping areas; facility documentation listed multiple rooms with receptacles needing replacement.
Inspection Report — Oct 15, 2024
Life Safety
Date: Oct 15, 2024
Visit Reason
Federal CMS-2567 life safety and emergency preparedness survey (CMS form). The survey type is not stated on the form.
Findings
Seven federal deficiencies were cited addressing emergency preparedness training/testing and multiple Life Safety Code topics, including means of egress, vertical openings enclosure, hazardous areas enclosure, fire alarm installation, sprinkler system installation, and electrical systems maintenance/testing.
Deficiencies (7)
E036 EP Training and Testing: Based on record review and interview, the facility failed to ensure all staff were tested in emergency preparedness and had no documented evidence of required annual emergency preparedness testing.
K211 Means of Egress - General: Based on observation and interview, the facility failed to ensure means of egress were maintained in accordance with NFPA 101; observations included a gate swinging in the wrong direction and bushes obstructing exit discharge paths.
K311 Vertical Openings - Enclosure: Based on observation and interview, the facility failed to ensure vertical openings were properly enclosed; a transfer grill was missing and an opening leading to the roof and basement was observed.
K321 Hazardous Areas - Enclosure: Based on observation and interview, the facility failed to ensure hazardous area enclosures were intact; a hole in the lower-level laundry room duct vent and missing framing created an unsealed opening.
K341 Fire Alarm System - Installation: Based on observations and interview, the facility failed to ensure required manual pull stations were located at required exit doors; manual pull stations were measured to be located too far from exit doors.
K351 Sprinkler System - Installation: Based on observation and interview, the facility failed to ensure sprinklers were installed in accordance with NFPA 13; an exterior wood-frame canopy lacked required sprinkler coverage.
K914 Electrical Systems - Maintenance and Testing: Based on record review and interview, the facility failed to ensure required receptacle testing and electrical system maintenance were documented and performed annually throughout the facility.
Report Facts
residents potentially affected: 110
residents potentially affected: 57
residents potentially affected: 28
residents potentially affected: 62
residents potentially affected: 10
Inspection Report — Apr 19, 2024
Complaint Investigation
Date: Apr 19, 2024
Visit Reason
Federal health survey (CMS-2567); the Initial Comments state this was a Recertification and Complaint survey.
Findings
Twelve federal deficiencies were cited covering notice requirements before transfer/discharge, accuracy of assessments (MDS/PASARR), comprehensive care planning, professional standards for services (medication administration), supervision and care for residents who smoke, pain management, nurse aide performance reviews and in-service training, high medication error rate, food safety/handling, lack of a written transfer agreement, infection prevention and control, and antibiotic stewardship.
Deficiencies (12)
F 623 Notice Requirements Before Transfer/Discharge: The facility failed to ensure the Ombudsman was notified of unplanned facility-initiated hospital discharges for Resident R263 as required.
F 641 Accuracy of Assessments: The facility failed to ensure accurate completion of Minimum Data Set assessments and related PASARR/antipsychotic medication documentation for sampled residents.
F 656 Develop/Implement Comprehensive Care Plan: The facility failed to develop a person-centered comprehensive care plan to address chronic wounds and edema for a sampled resident (R50).
F 658 Services Provided Meet Professional Standards: The facility failed to meet professional standards of quality by not ensuring physician-ordered medications (eye drops) were administered and documented as prescribed for a sampled resident (R44).
F 689 Free of Accident Hazards/Supervision/Devices: The facility failed to assess and provide required supervision for residents who smoke and did not implement an effective system to identify supervision needs or smoking materials for residents observed smoking unsupervised.
F 697 Pain Management: The facility failed to ensure timely availability and administration of pain medication and appropriate pain management practices for a sampled resident (R24).
F 730 Nurse Aide Perform Review-12 hr/yr In-Service: The facility failed to complete required performance reviews and provide regular in-service education for nurse aides at least once every 12 months.
F 759 Free of Medication Error Rts 5 Prcnt or More: The facility failed to ensure prescribed medications were administered at the prescribed times and were available for administration, resulting in numerous medication administration errors.
F 812 Food Procurement,Store/Prepare/Serve-Sanitary: The facility failed to ensure food items and food-preparation/storage equipment were maintained in a sanitary manner and staff performed appropriate hand hygiene and safe food handling.
F 843 Transfer Agreement: The facility failed to have a written transfer agreement with a hospital to assure timely hospital admission and exchange of necessary resident information.
F 880 Infection Prevention & Control: The facility failed to implement and maintain an infection prevention and control program with adequate surveillance, tracking/trending and corrective actions, and lacked sufficient documentation of the program.
F 881 Antibiotic Stewardship Program: The facility failed to implement and document an antibiotic stewardship program to monitor and evaluate antibiotic use and related measures.
Report Facts
residents sampled: 36
medication errors: 29
medication opportunities: 59
residents who smoke: 22
residents lacking monitoring: 5
Inspection Report — Apr 16, 2024
Life Safety
Date: Apr 16, 2024
Visit Reason
CMS-2567 Life Safety Code survey (K-tags) conducted; the survey is a Life Safety survey.
Findings
Five K-tag life safety deficiencies were cited covering kitchen hood/fire suppression inspections, sprinkler system maintenance and testing, unsealed smoke barrier penetrations, missing fire drill records, and missing generator/essential electrical system documentation. Several deficiencies were noted to have the potential to affect the facility's residents (115 census).
Deficiencies (5)
K324 Cooking Facilities: Based on record review and interview, facility staff failed to maintain the kitchen hood fire suppression system and the required inspection documentation was missing. The surveyor noted this deficient practice had the potential to affect staff and 12 residents residing in the central area of the building.
K353 Sprinkler System - Maintenance and Testing: Based on record review and interview, required quarterly tests and inspections of the sprinkler system were not conducted or documentation was missing. The surveyor noted this deficient practice had the potential to affect all 115 residents who resided at the facility.
K372 Subdivision of Building Spaces - Smoke Barrie[r]: Based on observation and interview, unsealed penetrations/overcuts were observed in smoke barriers (dining room and Room 94) and documentation/interviews indicated staff were unaware of the unsealed gaps. The surveyor noted this deficient practice had the potential to affect all 115 residents.
K712 Fire Drills: Based on record review and interview, the facility failed to conduct required quarterly fire drills on each shift and fire drill records were missing for some shifts. The surveyor noted this deficient practice had the potential to affect all 115 residents at the facility.
K918 Electrical Systems - Essential Electric Syste[m]: Based on record review and interview, the facility failed to maintain required generator/essential electrical system documentation and was unable to provide missing inspection/testing records. The surveyor noted this deficient practice had the potential to affect all 115 residents.
Report Facts
residents potentially affected: 12
residents potentially affected: 115
Inspection Report — Feb 29, 2024
Routine
Date: Feb 29, 2024
Visit Reason
Federal health survey (CMS-2567) and Missouri State licensure survey (State Form) are present; the survey type is not stated.
Findings
Two deficiencies were cited: one federal health deficiency regarding staff qualifications and failure to maintain a qualified/licensed administrator, and one Missouri State licensure deficiency for licensed administrator that references the federal finding.
Deficiencies (1)
F839 Staff Qualifications: Based on interview and record review, the facility failed to maintain a qualified administrator on duty, the Missouri Board registry did not list the administrator as currently licensed, and the application for full licensure was incomplete.
Inspection Report — Nov 20, 2023
Complaint Investigation
Date: Nov 20, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure forms are present in the file; the record cites complaint MO225076, so this is a complaint investigation.
Complaint Details
MO225076 is cited in the file; the forms do not explicitly state whether the complaint allegation was formally substantiated.
Findings
Twelve deficiencies were cited in total: 7 federal health deficiencies addressing care planning, ADL assistance and bathing, quality of care/changes in condition, trauma-informed care, bed rail assessments/entrapment, resident call systems, and sanitary/odor issues; and 5 Missouri state licensure citations covering call system requirements, furniture/equipment comfort and safety, nursing care per resident condition, cleanliness/odor-free requirements, and clinical record documentation. Some findings were noted as previously cited or uncorrected from the 11/20/2023 survey and an Immediate Jeopardy related to quality of care was removed during the onsite review.
Deficiencies (7)
F656 Develop/Implement Comprehensive Care Plan: The facility failed to develop and implement comprehensive person‑centered care plans with measurable objectives for sampled residents, including lack of care plan interventions regarding side rail use and skin/pain issues for residents noted in the review.
F677 ADL Care Provided for Dependent Residents: The facility failed to ensure dependent residents received necessary assistance with grooming and bathing as scheduled and lacked a facility policy on Activities of Daily Living (ADLs), with multiple residents not receiving expected showers or care.
F684 Quality of Care: The facility failed to evaluate and respond to changes in condition for residents, resulting in one resident being emergently discharged to the hospital for severe dehydration/possible sepsis and another experiencing critically high blood glucose readings without timely physician notification.
F699 Trauma Informed Care: The facility failed to provide trauma‑informed care for sampled residents with PTSD, including incomplete trauma screening documentation, care plans that did not identify triggers or person‑centered interventions, and staff who lacked training on trauma‑informed approaches.
F700 Bedrails: The facility failed to assess residents for entrapment risk, measure bed dimensions, and ensure appropriate installation/use of bed rails and lacked an entrapment policy for multiple sampled residents.
F919 Resident Call System: The facility failed to ensure the resident call light system was accessible and functioning properly for bedside and toileting/bathing facilities for sampled residents, and did not provide a policy regarding call lights.
F921 Safe/Functional/Sanitary/Comfortable Environ: The facility failed to provide a sanitary, comfortable environment and to maintain mattress covers in good condition; inspectors observed stained, malodorous mattress covers and residents placed on soiled bedding.
Report Facts
residents sampled: 22
Inspection Report — Nov 20, 2023
Life Safety
Date: Nov 20, 2023
Visit Reason
Federal CMS-2567 Life Safety survey and Missouri Department of Health and Senior Services State Form; Life Safety survey (K-tags present).
Findings
Ten deficiencies were cited: five federal Life Safety deficiencies involving vertical opening penetrations, sprinkler system maintenance and testing, corridor wall penetrations, inadequate fire drill scheduling, and unsafe use of electrical/power cords; and five Missouri state rule violations that refer to the Life Safety findings (required corridors, sprinkler inspections, fire drill requirements, facility construction/maintenance, and extension cords/duplex receptacles).
Deficiencies (5)
K311 Vertical Openings - Enclosure: Based on observation and interview, facility staff failed to ensure ceilings did not have penetrations to attic spaces above, affecting multiple smoke sections.
K353 Sprinkler System - Maintenance and Testing: Based on observation and interview, facility staff failed to ensure the sprinkler system was maintained when sprinkler heads were painted or corroded, escutcheon plates did not seal openings, and some heads were encased in lint or otherwise obstructed.
K362 Corridors - Construction of Walls: Based on observation and interview, facility staff failed to maintain the fire-resistance rating of corridor walls when penetrations through the walls for wires and other openings were present.
K712 Fire Drills: Based on interview and record review, facility staff failed to complete fire drills at varied times and conditions as required over the past year.
K920 Electrical Equipment - Power Cords and Extension Cords: Based on observation and interview, facility staff failed to ensure safe use of electrical equipment, including improper use of surge protectors, plugging devices into surge protectors, overloaded surge protectors, and missing outlet plates.
Report Facts
smoke sections affected: 4
smoke sections affected: 3
Inspection Report — May 23, 2023
Routine
Date: May 23, 2023
Visit Reason
Federal health survey (CMS-2567) and Missouri state licensure survey (State Form); the survey type is not stated.
Findings
Seven deficiencies were cited: four federal health deficiencies involving resident rights, environment/housekeeping, comprehensive care planning, and pain management, and three Missouri state licensure deficiencies referencing floor surfaces, wall/ceiling surfaces, and nursing care per resident condition.
Deficiencies (4)
F550 Resident Rights/Exercise of Rights: Based on interview and record review, the facility failed to treat one resident with dignity and respect when staff limited social and activity participation and did not provide emotional/psychological support while the resident was placed on transmission-based/isolation precautions; the resident was confined to their room and the care plan did not address TBP.
F584 Safe/Clean/Comfortable/Homelike Environment: The facility failed to provide a safe, clean, comfortable and homelike environment for residents on the C hallway when rooms and hall surfaces were not kept clean or in good repair, including scuffed and missing paint on doors and baseboards, stained and deteriorating ceiling tiles, broken/missing tile in front of the nursing station, and a corroded eye-wash station pipe with paint flaking.
F656 Develop/Implement Comprehensive Care Plan: The facility failed to develop, review, and revise comprehensive care plans that addressed the use of mattress bolsters and the need for assistive cane rails for sampled residents, and lacked physician orders and care plan documentation for these interventions.
F697 Pain Management: The facility failed to ensure adequate pain management for one resident by not consistently assessing and documenting pain, not providing timely non-pharmacological pain relief measures, and failing to document attempts to reach a physician or to follow up on uncontrolled pain.
Report Facts
residents sampled: 20
Inspection Report — May 23, 2023
Life Safety
Date: May 23, 2023
Visit Reason
Federal Life Safety (CMS-2567) and Missouri state licensure (State Form); life safety survey.
Findings
Twelve deficiencies were cited: seven federal Life Safety Code deficiencies and five Missouri State licensure citations. Findings address egress door locking, emergency lighting, sprinkler system testing/maintenance, corridor wall fire resistance, smoke barrier penetrations, utilities/electrical receptacles, and improper use of power strips/extension cords.
Deficiencies (7)
K222 Egress Doors: The facility failed to maintain delayed-egress and locking arrangements; multiple delayed egress doors did not release with activation of the fire alarm and the facility used unacceptable locking arrangements on two doors requiring a key or combination from the egress side.
K291 Emergency Lighting: The facility failed to properly maintain emergency lighting and to include all emergency lighting with battery back-up on testing records; an emergency light with battery back-up in the basement did not illuminate when tested.
K353 Sprinkler System - Maintenance and Testing: The facility failed to maintain the sprinkler system and did not have required inspection and testing records, including documentation of required full-flow trip and air leakage testing.
K362 Corridors - Construction of Walls: The facility failed to ensure corridor walls maintained the required 1/2-hour fire resistance rating; a return air duct vent exposed wood studs within a corridor wall.
K372 Subdivision of Building Spaces - Smoke Barrier Construction: The facility failed to maintain smoke barrier walls complete from outside wall to outside wall and failed to use approved methods to seal penetrations; multiple unsealed penetrations and gaps were observed in several smoke barrier walls.
K511 Utilities - Gas and Electric: The facility failed to maintain dryers free of lint and failed to ensure replaced receptacles were hospital grade; observations included a dryer caked with lint and multiple receptacles not identified as hospital grade.
K920 Electrical Equipment - Power Cords and Extension Cords: The facility failed to ensure proper use of power strips and extension cords and mixed Patient Care Related Electrical Equipment (PCREE) and non-PCREE power strips; several resident rooms had non-compliant power strips or devices plugged into PS-rated strips.
Report Facts
smoke zones affected: 1
smoke compartments affected: 5
smoke compartments affected: 2
smoke compartments affected: 3
Inspection Report — Nov 4, 2021
Life Safety
Date: Nov 4, 2021
Visit Reason
CMS-2567 federal life safety and emergency preparedness survey pages and Missouri Department of Health and Senior Services State Form licensure pages; life safety.
Findings
27 deficiencies were cited across federal CMS-2567 life-safety/emergency preparedness pages (17 items) and Missouri State Form licensure pages (10 items). Main topics include emergency preparedness subsistence planning, sprinkler system maintenance, exit signage and egress door locking, hazardous area doors and smoke barriers, portable fire extinguisher maintenance, electrical/power strip use and breaker covers, and unsafe smoking/disposing practices.
Deficiencies (14)
E015 Subsistence Needs for Staff and Patients: Based on record review and interview, the facility failed to develop and implement emergency preparedness policies and procedures to maintain subsistence needs and a complete documentation of non-perishable meal supply.
K161 Building Construction Type and Height: Based on observation and interview, the facility failed to maintain the one-hour fire rating of the ceiling where drywall ceilings had holes and penetrations.
K222 Egress Doors: The facility failed to ensure an accepted locking arrangement for one required exit and failed to ensure one exit did not require a key from the egress side, with observations of a delayed egress door that did not release after 15 seconds.
K293 Exit Signage: The facility failed to test and document exit lighting/exit signs per NFPA requirements and had exit signs with inconsistent emergency battery backup and inadequate testing records.
K321 Hazardous Areas - Enclosure: The facility failed to protect hazardous areas with self-closing doors and maintain those areas free of combustible storage, with observation of a room containing many cardboard boxes and loose paper.
K353 Sprinkler System - Maintenance and Testing: The facility failed to ensure sprinkler heads remained free of corrosion, dust and debris and that escutcheon plates were installed correctly; numerous sprinkler heads were corroded, missing plates, had gaps, or had paint on them.
K355 Portable Fire Extinguishers: The facility failed to ensure portable fire extinguishers were inspected and maintained monthly, with several extinguishers lacking current inspection tags or records.
K362 Corridors - Construction of Walls: The facility failed to maintain corridor walls free of penetrations that resist the passage of smoke, with observed unsealed penetrations and holes in corridor walls.
K363 Corridor - Doors: The facility failed to ensure corridor doors resisted passage of smoke; multiple resident room and corridor doors were difficult to close or did not latch.
K372 Subdivision of Building Spaces - Smoke Barrier: The facility failed to maintain smoke barrier walls complete and sealed, with observed unsealed holes and conduit penetrations in smoke barrier walls.
K374 Subdivision of Building Spaces - Smoke Barrier Doors: The facility failed to ensure smoke barrier doors closed fully and met clearance/gap requirements, including observed gaps between paired doors.
K511 Utilities - Gas and Electric: The facility failed to ensure dryer lint and breaker box covers were maintained and that electrical panels and outlets were in good condition; observations included breaker boxes with covers removed and lint build-up near dryers.
K741 Smoking Regulations: The facility failed to ensure safe smoking practices and proper ash receptacles; observations found trash cans and smoking receptacles with cigarette butts and no self-closing metal ash cans.
K920 Electrical Equipment - Power Cords and Extension Cords: The facility failed to ensure safe use of power strips and extension cords, with power strips and extension cords serving multiple appliances and cords run through walls.
Report Facts
smoke zones affected: 4
sprinkler heads with dust/grease/corrosion in kitchen: 10
Inspection Report — Nov 22, 2019
Life Safety
Date: Nov 22, 2019
Visit Reason
Federal CMS-2567 Life Safety (K-tag) survey and Missouri Department of Health and Senior Services State Form; the survey is a life safety survey.
Findings
There are 14 federal life-safety deficiencies (K-tags) concerning building construction and penetrations between ceiling/attic spaces, smoke barrier walls and doors, egress/exit doors and stairwell storage, emergency and exit lighting, portable fire extinguishers, corridor doors, vertical openings, hazardous area enclosures, smoking/disposal, and electrical power strips and inspections. There are 11 Missouri State Form deficiencies reflecting many of the same issues, including hazardous areas, fire extinguisher monthly checks, exit sign requirements, emergency lighting, vertical shaft requirements, smoke section walls/doors, ashtrays, fire drill/consultation, substantial construction/maintenance, and electrical inspection/certification.
Deficiencies (14)
K161 Building Construction Type and Height: The facility failed to maintain required separation between the ceiling and attic and failed to maintain Type II construction, with multiple unsealed ceiling/attic openings and stored wooden planks found in the attic, affecting multiple smoke compartments.
K222 Egress Doors: The facility failed to maintain emergency exit doors in compliance, including an exit door that failed to open on fire alarm activation and exit doors blocked or impeded by stored carts and a Velcro STOP sign, affecting residents in the transitional care unit and main dining areas.
K225 Stairways and Smokeproof Enclosures: Staff stored boxes and clothing in the basement stairwell/exit enclosure, using the open exit enclosure for storage and creating a fire hazard.
K281 Illumination of Means of Egress: The facility failed to ensure emergency lighting was installed/reinstalled at the front entrance after removal of the awning, leaving no visible emergency lighting at that entrance.
K291 Emergency Lighting: Basement emergency lighting was not maintained in working order and documentation of required testing/inspections was missing or incomplete.
K311 Vertical Openings - Enclosure: The facility failed to ensure there were no vertical openings between floors, with breached/busted walls and openings allowing light/air between the oxygen storage/attic areas and the basement furnace room.
K321 Hazardous Areas - Enclosure: Doors to hazardous areas (furnace and electrical rooms) did not resist passage of smoke or shut properly, were held open with magnets or warped, and allowed openings between protected areas.
K355 Portable Fire Extinguishers: The facility failed to provide documentation of monthly inspections for many extinguishers, failed to properly mount an extinguisher, and had an unsecured extinguisher found on the floor.
K363 Corridor - Doors: Corridor doors did not resist passage of smoke, with multiple gaps, drilled holes, missing strike plates, and doors that did not latch or close properly in multiple locations.
K372 Subdivision of Building Spaces - Smoke Barrier: Smoke barrier walls had penetrations/holes and were not maintained to provide a fire barrier, affecting multiple smoke compartments and residents.
K374 Subdivision of Building Spaces - Smoke Barrier Doors: Smoke barrier doors (double-leaf B-Hall doors) failed to completely close upon activation of the fire alarm and did not fully latch, compromising the smoke barrier.
K741 Smoking Regulations: The facility failed to properly dispose of cigarette butts and ash; designated smoking areas and employee/resident smoking receptacles contained cigarette butts, candy wrappers and other debris.
K914 Electrical Systems - Maintenance and Testing: The facility had no electrical inspection documented within the last two years as required, and records/reports of required electrical inspections were not found.
K920 Electrical Equipment - Power Cords and Extension Cords: The facility failed to ensure safe use of power strips and extension cords, with medical equipment, refrigerators, microwaves and oxygen devices connected to power strips, open breaker boxes with missing covers, and heat tape used on a freezer line.
Report Facts
residents affected: 110
residents affected: 14